HomeMy WebLinkAbout416 Nevada St-Rental Property Inspection-2/22/2019 Rental Property Inspection Report
City of Waterloo
715 Mulberry Street,
Waterloo, Iowa 50703
PH(319)-291-4319 Fax(319)-291-4262
Inspection Number 771
Inspector* Barry Stratton
Re-inspection Date 3/22/2019
Re-inspection# 2
File Upload
Property Info
Inspection Date* 2/22/2019
Unit Of
Street Address:* 416 Nevada St
Tenant Name:
Phone Number:
Property Owner Info
Property Owner Name: Roden burgh Rentals
Property Owner
Email
Property Owner 1032 Roosevelt St Waterloo, IA 50707
Address:
Property Owner Phone: 319-231-5872
Inspection Items
Item Status
Address Posted r Pass r Cond r Fail
Siding r Pass r Cond r Fail
Roof r Pass r Cond r Fail
Item Status
Porches f Pass f Cond r Fail
Chimney r Pass r Cond F Fail
Basement r Pass r Cond F Fail
Steps(outside) (Pass f Cond r Fail
Foundation (Pass f Cond r Fail
Hot Water Heater (Pass f Cond F Fail
Heating System r Pass r Cond F Fail
Electric (Pass f Cond F Fail
Plumbing r Pass r Cond F Fail
Egress (Pass f Cond r Fail
Garbage r Pass r Cond r Fail
Dining Room r Pass r Cond r Fail
Livingroom r Pass r Cond r Fail
Bedroom r Pass r Cond F Fail
Kitchen (Pass f Cond r Fail
Batheroom r Pass r Cond F Fail
Appliances (Pass f Cond F Fail
Floors (Pass f Cond r Fail
Windows-Locks (Pass f Cond F Fail
Door-Locks (Pass f Cond F Fail
Smoke Detectors r Pass r Cond F Fail
Stairs(Inside) (Pass f Cond r Fail
Handrails (Pass f Cond F Fail
Misc. Hazards-list r Pass r Cond F Fail
Fire Extinguishers (Pass f Cond F Fail
Common Area r Pass r Cond r Fail
Attach Photos
Comments
Violation Comments
IFC 907 915 IPMC 704 Smoke detectors needed in every bedroom and
outside of the bedrooms. Smoke detector is needed
in basement. CO detector is needed in vicinity of the
bedrooms.
Violation Comments
IPMC 605 All electric outlets need approved covers. Open
fixtures basement need covers. Exposed wires in
boxes.
Electric panel missing fuses.
All light fixtures will need approved globes installed.
IFC 605.5 Electric cords in use and need removed. Multiple
adapters in use and need removed.
IPMC 305.6 Interior doors shall fit reasonably well within its frame
and shall be capable of being opened and closed.
Basement door and door to front area need
replaced.
IPMC 504 Water heater not installed to code. Supply lines are
in pex and need to be hard piped up 18"inches off
top of water heater. NO permit of water heater
installation.
Pex piping not secured as code requires. Pex just
hanging from area in basement.
New sanitary PVC stack and PVC pipe for bathroom
not installed to code. Hire licensed plumbing
contractor to make corrections.
Shower in basement leaking.
1 st floor bathroom not installed to meet code.
NO clean out on sanitary stack. New PVC installed
where clean out is designed to be. No P trap
installed on sink drain.
IPMC 603 Furnace not installed to code. Np permit for the
furnace installation. Gas pipe needs to be black pipe
and not appliance pipe. Licensed contractor needs
to be obtained to make corrections and obtain
permits. Large water leak under furnace needs
corrected.
Need to install cover on open duct n chimney.
IPMC 307 Need handrails to basement the entire length of the
stairs.
IPMC 305 Nails exposed on basement stairs wall going to
basement need removed.
Peeling and abraded paint throughout needs
corrected. Potential for lead base paint in unit with
house being built before 1978.
Paneling coming loose from walls in several areas of
house.
IFC 906 Need updated fire extinguisher in unit.
IPMC 304.15 Back door is not installed and maintained in weather
tight condition. Door shall be maintained in good
condition and shall tightly secure door.
IPMC 304.13 Windows and frames shall be kept in sound
condition good repair,and weather tight.Windows
shall be easily openable and capable of being held
in the position by window,hardware.
IPMC 304.11 Need chimney cap on duct on chimney in basement.
Violation Comments
IPMC 102.5 Workmanship repairs, maintenance work,
alterations, or installations shall be executed and
installed in a workmanship manner and installed in
accordance with the manufacture's instructions and
meet the requirements of the code.
IPMC 108.1.2 Unsafe equipment including heating equipment not
installed to meet code. Equipment is a hazard to the
occupants.
IRC 105 Permits&inspections will be required for the
installation of the furnace and water heater.
Licensed contractors will need to make corrections
to make items safe and installed to code. Inspections
will need to be made by the HVAC inspector.
Plumbing inspector will need to inspect all plumbing
installed that is not installed to meet code.
IPMC 304.4 Structural members shall be maintained from
deterioration and shall be capable of safely
supporting the imposed loads. Support base in
basement is failing.