HomeMy WebLinkAbout211 Randolph St-Rental Property Inspection-6/15/2018 Rental Property Inspection Report
City of Waterloo
715 Mulberry Street,
Waterloo, Iowa 50703
PH(319)-291-4319 Fax(319)-291-4262
Inspection Number 648
Inspector* Barry Stratton
Re-inspection Date 7/16/2018
Re-inspection# 2
File Upload
Property Info
Inspection Date* 6/15/2018
Unit Of
Street Address:* 211 Randolph St
Tenant Name:
Phone Number:
Property Owner Info
Property Owner Name: Dream Investments LLC
Property Owner
Email
Property Owner 11 Silver Lake Dr Waterloo, IA 50702
Address:
Property Owner Phone:
Inspection Items
Item Status
Address Posted r Pass r Cond r Fail
Siding r Pass r Cond r Fail
Roof r Pass r Cond r Fail
Item Status
Porches f Pass f Cond r Fail
Chimney r Pass r Cond r Fail
Basement r Pass r Cond F Fail
Steps(outside) (Pass f Cond r Fail
Foundation (Pass r Cond r Fail
Hot Water Heater (Pass (Cond F Fail
Heating System r Pass r Cond r Fail
Electric (Pass (Cond F Fail
Plumbing r Pass r Cond F Fail
Egress (Pass (Cond r Fail
Garbage r Pass r Cond F Fail
Dining Room r Pass r Cond F Fail
Livingroom r Pass r Cond F Fail
Bedroom r Pass r Cond F Fail
Kitchen (Pass (Cond F Fail
Batheroom r Pass r Cond F Fail
Appliances (Pass (Cond r Fail
Floors (Pass (Cond F Fail
Windows-Locks (Pass (Cond F Fail
Door-Locks (Pass (Cond F Fail
Smoke Detectors r Pass r Cond F Fail
Stairs(Inside) (Pass (Cond F Fail
Handrails (Pass (Cond F Fail
Misc. Hazards-list r Pass r Cond F Fail
Fire Extinguishers (Pass (Cond F Fail
Common Area r Pass r Cond r Fail
Attach Photos
Comments
Violation Comments
IFC 907 915 IPMC 704 Smoke detectors are needed in each bedroom and
out side of the bedrooms. Smoke detectors are also
needed on each level and in basement. CO
detectors are need in vicinity of bedrooms or areas
used for sleeping purposes.
Violation Comments
IFC 605.5 Extension cords are not allowed and need to be
removed.
IPMC 605 Electrical outlets in kitchen do not work and there
are outlets missing covers. Exposed wires in
basement need removed or terminated in boxes.
GFCI outlets not working.
Have electrical contractor check the units service to
ensure all is functional.
Light switch in basement not secured to code it is
just hanging.
Outlets not secure in fixtures throughout the house.
Porch light on ceiling has exposed wire that needs
corrected.
All lights will need the proper globes installed on all
lights that do not have covers.
IPMC 304.15 Side door needs replaced. Doors and assemblies
shall be maintained in good condition.
IPMC 305 All peeling and abraded paint shall be corrected.
All walls shall be maintained in good sanitary
condition. Cracked or loose plaster, decayed wood,
and other defective conditions shall be corrected.
Waling surfaces missing transition strips and floors
not maintained in safe and sanitary condition.
IPMC 304.13 Every window&frame shall be kept in sound
condition,good repair and weather tight.Windows in
stairwell and other windows broken.
IPMC 403.2 Upstairs bathroom exhaust fan needs replaced.
IPMC 305.4 307 Stairs and handrails to basement will need removed
and replaced. Stairs are very unsafe. Stairs shall be
maintained in sound condition and in good repair.
Need handrail installed on stairs to the upstairs.
IPMC 504 Need to install a newwater heater. Need to have
proper permits and done by licensed contractor.
Water heater is leaking out of the base of the water
heater.
Water is leaking all over basement floor.
Serer sanitary stack has been replaced without
permits and inspections. Have licensed contractor
make corrections to sanitary sewer.
IPMC 403.5 Dryer is venting in room and needs to vent to the
exterior of the house.
Fees
Initial Fees $
Initial Unit $
Additional Units $
Common Area $
Total Fee* $ 0.00
Does the property r No F Yes
require another
inspection?
Time 11:00