HomeMy WebLinkAbout314 Allen St # 1-Rental Property Inspection-2/13/2017 Rental Property Inspection Report
City of Waterloo
715 Mulberry Street,
Waterloo, Iowa 50703
PH(319)-291-4319 Fax(319)-291-4262
Inspection Number 371
Inspector* Barry Stratton
Re-inspection Date 3/15/2017
Re-inspection# 2
File Upload
Property Info
Inspection Date* 2/13/2017
Unit Of
Street Address:* 314 Allen St#1
Tenant Name:
Phone Number:
Property Owner Info
Property Owner Name: Owl Investments LLC
Property Owner
Email
Property Owner Po Box 83 Denver, IA 50622
Address:
Property Owner Phone:
Inspection Items
Item Status
Address Posted r Pass r Cond r Fail
Siding f Pass f Cond r Fail
Roof (Pass f Cond r Fail
Item Status
Porches C Pass C Cond f Fail
Chimney C Pass C Cond (Fail
Basement C Pass C; Cond (Fail
Steps(outside) C Pass C Cond (Fail
Foundation C Pass C Cond (Fail
Hot Water Heater C Pass C Cond (Fail
Heating System O Pass O Cond (Fail
Electric a Pass C Cond f•Fail
Plumbing a Pass C Cond (Fail
Egress C Pass C Cond (Fail
Garbage C Pass C Cond (Fail
Dining Room C Pass C Cond (Fail
Livingroom O Pass C) Cond C Fail
Bedroom O Pass C Cond F Fail
Kitchen C Pass C Cond f•Fail
Batheroom C Pass C` Cond (Fail
Appliances C Pass C Cond (Fail
Floors f Pass r) Cond (Fail
Windows-Locks C Pass C Cond C Fail
Door-Locks C Pass C Cond (Fail
Smoke Detectors C Pass r Cond f•Fail
Stairs(Inside) C Pass r Cond (Fail
Handrails C Pass r Cond (Fail
Misc. Hazards-list C Pass C Cond F Fail
Fire Extinguishers C Pass C Cond f•Fail
Common Area C Pass C Cond (Fail
Attach Photos
Comments
..................
Violation Comments
IFC 907 915 IPMC 704 Smoke detectors needed in each bedroom and
outside of the bedrooms. CO detector needed in
vicinity of bedrooms.
Violation Comments
IPMC 305 Celling collapsed in bedroom.All interior surfaces
and ceilings shall be capable of supporting normally
imposed loads and shall be maintained in good
condition. Ceiling and track supports were
supporting ceiling fan have now failed.
Ceiling has had sever water damage before Drop
ceiling was installed. Correct damage and repair to
meet code. Since the old ceiling is damaged it has
compromised the fire separation between floors.
IPMC 605 Ceiling fan was not installed correctly and needs to
be hardwired to a fixture box. Currently wiring not to
code. Electrical equipment,wiring and appliances
shall be properly installed and maintained in a safe
and approved manner.
IPMC 309 Mice infestation in unit and structures shall be kept
free from rodent infestation.
IPMC 403.4 Bath Fan is so dirty is needs to be cleaned.
Ventilation system shall provide exhaust to the
exterior and not be recirculated to any space.
IPMC 305 Ceiling and walls going to the upper unit need
removed and repaired.Walls and ceilings shall be
maintained structurally sound,and be capable of
supporting the imposed loads. Currently behind walls
is decayed and in such condition that is needs
removed and replaced.
Fees
Initial Fees $
Initial Unit $
Additional Units $
Common Area $
Total Fee* $ 0
Does the property r No F Yes
require another
inspection?
Time TBA