HomeMy WebLinkAbout626 Boston Ave-Rental Property Inspection-6_22_2017 Rental Property Inspection Report
City of Waterloo
715 Mulberry Street,
Waterloo, Iowa 50703
PH(319)-291-4319 Fax(319)-291-4262
Inspection Number 472
Inspector* Barry Stratton
Re-inspection Date 7/24/2017
Re-inspection# 2
File Upload
Property Info
Inspection Date* 6/22/2017
Unit Of
Street Address:* 626 Boston Ave
Tenant Name: Tracy
Phone Number: 319-486-3894
Property Owner Info
Property Owner Name: Effie Burt
Property Owner Mark Pregler
Email (budgetservices001 @gmail.com)
Property Owner 604 Kyra Dr Oxford, MS 38655
Address:
Property Owner Phone:
Inspection Items
Item Status
Address Posted r Pass r Cond r Fail
Siding f Pass f Cond r Fail
Roof (Pass f Cond r Fail
Item Status
Porches C Pass C Cond f Fail
Chimney C Pass C Cond (Fail
Basement C Pass C; Cond f•Fail
Steps(outside) C Pass C Cond (Fail
Foundation C Pass C Cond (Fail
Hot Water Heater C Pass C Cond (Fail
Heating System O Pass O Cond (Fail
Electric a Pass C Cond f•Fail
Plumbing a Pass C Cond (Fail
Egress C Pass C Cond (Fail
Garbage C Pass C Cond (Fail
Dining Room C Pass C Cond (Fail
Livingroom O Pass C) Cond C Fail
Bedroom O Pass C Cond C Fail
Kitchen C Pass C Cond (Fail
Batheroom C Pass C` Cond (Fail
Appliances C Pass C Cond f•Fail
Floors f Pass r) Cond (Fail
Windows-Locks C Pass C Cond C Fail
Door-Locks C Pass C Cond (Fail
Smoke Detectors C Pass r Cond f•Fail
Stairs(Inside) C Pass r Cond (Fail
Handrails C Pass r Cond (Fail
Misc. Hazards-list C Pass C Cond F Fail
Fire Extinguishers C Pass C Cond f•Fail
Common Area C Pass C Cond (Fail
Attach Photos
Comments
.......................................................................
Violation Comments
IFC 907 915 IPMC 704 Need smoke detectors in each bedroom and
basement.
Violation Comments
IPMC 605 Light in hallway not working. Missing switch covers
needed installed in bedroom
Some outlets not working in bedrooms and living
room.
Appliances such as freezers(2)need direction
connection to outlets. Currently 2 freezers are
plugged in to power strips.
Tenant advised breakers keep blowing from using
appliances. Checked breaker panel and all breaker
are functional at time of inspection.
IPMC 603 Mechanical equipment shall be properly installed
and maintained in working condition. Condensate
pump in basement is not pumping discharge out.
Pump is leaking on floor. Currently a lot of water is
all over basement floor.
IPMC 403.5 Dryer needs to exhaust directly to the outside and
currently connection is disconnected at elbow.
IFC 315 Storage of lawn mower in basement is not allowed.
Lawn mower will need removed from basement.
IPMC 403.2 Bath exhaust is not working. Possible fan needs
replaced/repaired.
IPMC 506 Sanitary drain in basement overflows according to
tenant and currently drain was not backed up. Have
check for obstruction.
Fees
Initial Fees $
Initial Unit $
Additional Units $
Common Area $
Total Fee* $ 0.00
Does the property r No F Yes
require another
inspection?
Time 10:30