HomeMy WebLinkAbout1408 Washington Street_091219WATERLOO FIRE RESCUE
INSPECTION REPORT
1408 WASHINGTON ST, WATERLOO IA 50702
DETAILS
Inspection Date: 09/12/2019 | Inspection Type: Rental Inspection | Inspection Number: 3401 | Shift: N/A | Station: N/A |
Unit: N/A | Lead Inspector: BARRY STRATTON | Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 1010.1.9 - Door operations Except as specifically permitted by this section, egress doors shall be readily
openable from the egress side without the use of a key or special knowledge or
effort.
Inspector: BARRY STRATTON - Comments: All egress doors shall be in working
condition able to close and latch.
FAIL 1103.9 - Carbon monoxide
alarms
Existing Group I-1, I-2, I-4 and R occupancies shall be equipped with carbon monoxide
alarms in accordance with Section 915, except that the carbon monoxide alarms shall
be allowed to be solely battery operated.
Inspector: BARRY STRATTON - Comments: CO detectors needed in vicinity of the
bedrooms.
FAIL 506.1 - Where required Where access to or within a structure or an area is restricted because of secured
openings or where immediate access is necessary for life-saving or fire-fighting
purposes, the fire code official is authorized to require a key box to be installed in an
approved location. The key box shall be of an approved type listed in accordance with
UL 1037, and shall contain keys to gain necessary access as required by the fire code
official.
Inspector: BARRY STRATTON - Comments: Knox boxes shall be installed per Fire
Marshal. Contact Lt Chris Ferguson 319-493-1136 for locates and key placement.
FAIL 907.2.11 - Single- and
multiple-station smoke
alarms
Listed single- and multiple- station smoke alarms complying with UL 217 shall be
installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
Inspector: BARRY STRATTON - Comments: Smoke detectors need to be in working
condition.
FAIL 915.4 - Carbon monoxide
alarms
Carbon monoxide alarms shall comply with Sections 915.4.1 through 915.4.3.
Inspector: BARRY STRATTON - Comments:
Printed on 07/24/2020 @ 10:29
Page 1 of 2
STATUS CODE DESCRIPTION
FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: Door hardware, needed on entrance door,
bedroom door needs repaired/replaced, furnace door needs replaced.
GENERAL NOTES
BARRY STRATTON - 09/12/2019 @ 10:31 Unit # 102
REINSPECTION DATE
10/10/2019
CONTACT SIGNATURE
Christin
Signed on: 09/12/2019 @ 10:33
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 09/12/2019 @ 10:33
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
barry.stratton@waterloo-ia.org
(319) 231-9147
Printed on 07/24/2020 @ 10:29
Page 2 of 2