Loading...
HomeMy WebLinkAbout1720 Black Hawk RdWATERLOO FIRE RESCUE INSPECTION REPORT 1720 BLACK HAWK RD, WATERLOO IA 50701 DETAILS Inspection Date: 08/13/2019 | Inspection Type: Annual Inspection (1Yr)| Inspection Number: 3260 | Shift: N/A | Station: N/A | Unit: N/A | Lead Inspector: BARRY STRATTON | Other Inspectors: N/A STATUS CODE DESCRIPTION FAIL 105.6.44 - Storage of scrap tires and tire byproducts An operational permit is required to establish, conduct or maintain storage of scrap tires and tire byproducts that exceeds 2,500 cubic feet (71 m^3) of total volume of scrap tires, and for indoor storage of tires and tire byproducts. Inspector: BARRY STRATTON - Comments: FAIL 2005.6 - At fuel-dispensing stations Portable fire extinguishers at fuel-dispensing stations shall be located such that pumps or dispensers are not more than 75 feet (22,860 mm)from one such extinguisher. Fire extinguishers shall be provided as follows: 1. Where the open-hose discharge capacity of the fueling system is not more than 200 gallons per minute (13 L/s), not less than two listed portable fire extinguishers complying with Section 906 and having a minimum rating of 20-B: C shall be provided. 2. Where the open-hose discharge capacity of the fueling system is more than 200 gallons per minute (13 L/s) but not more than 350 gallons per minute (22 L/s), not less than one listed wheeled extinguisher complying with Section 906 and having a minimum extinguishing rating of 80-B: C, and a minimum agent capacity of 125 pounds (57 kg), shall be provided. 3. Where the open-hose discharge capacity of the fueling system is more than 350 gallons per minute (22 L/s), not less than two listed wheeled extinguishers complying with Section 906 and having a minimum rating of 80-B: C each, and a minimum capacity agent of 125 pounds (57 kg) of each, shall be provided. Inspector: BARRY STRATTON - Comments: Diesel fuel needs extinguishers and hazmat placards. FAIL 2309.6.1.2.3 - Stability of cylinders, containers and tanks A method of rigidly supporting cylinders, containers or tanks used during the closed transfer system discharge or defueling of hydrogen shall be provided. The method shall provide not less than two points of support and shall be designed to resist lateral movement of the receiving cylinder, container or tank. The system shall be designed to resist movement of the receiver based on the highest gas-release velocity through valve orifices at the receiver’s rated service pressure and volume. Supporting structures or appurtenances used to support receivers shall be constructed of noncombustible materials in accordance with the International Building Code. Inspector: BARRY STRATTON - Comments: All tanks shall be chained for fall protection Printed on 07/24/2020 @ 09:11 Page 1 of 4 STATUS CODE DESCRIPTION FAIL 2803.6 - Fire apparatus access roads Fire apparatus access roads shall be provided for buildings and facilities in accordance with Section 503. Inspector: BARRY STRATTON - Comments: FAIL 2809.3 - Fire apparatus access roads Fire apparatus access roads in accordance with Section 503 shall be located so that a maximum grid system unit of 50 feet by 150 feet (15 240 mm by 45,720 mm) is established. Inspector: BARRY STRATTON - Comments: FAIL 315.3 - Storage in buildings Storage of materials in buildings shall be orderly and stacks shall be stable. Storage of combustible materials shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. Inspector: BARRY STRATTON - Comments: FAIL 315.4 - Outside storage Outside storage of combustible materials shall not be located within 10 feet (3048 mm) of a lot line. Exceptions: 1. The separation distance is allowed to be reduced to 3 feet (914 mm) for storage not exceeding 6 feet (1829 mm) in height. 2. The separation distance is allowed to be reduced where the fire code official determines that no hazard to the adjoining property exists. Inspector: BARRY STRATTON - Comments: FAIL 503.4 - Obstruction of fire apparatus access roads Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in Sections 503.2.1 and 503.2.2 shall be maintained at all times. Inspector: BARRY STRATTON - Comments: FAIL 605.1 - Abatement of electrical hazards Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Open Electric panel needs cover, indoor 220V recepticle in use outdoors. Printed on 07/24/2020 @ 09:11 Page 2 of 4 STATUS CODE DESCRIPTION FAIL 906.1 - Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 mm) of commercial cooking equipment. 3. In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1. 6. Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector: BARRY STRATTON - Comments: FAIL 906.2 - General requirements Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Exceptions: 1. The distance of travel to reach an extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies. 2. Thirty-day inspections shall not be required and maintenance shall be allowed to be once every 3 years for dry-chemical or halogenated agent portable fire extinguishers that are supervised by a listed and approved electronic monitoring device, provided that all of the following conditions are met: 2.1. Electronic monitoring shall confirm that extinguishers are properly positioned, properly charged and unobstructed. 2.2. Loss of power or circuit continuity to the electronic monitoring device shall initiate a trouble signal. 2.3. The extinguishers shall be installed inside of a building or cabinet in a noncorrosive environment. 2.4. Electronic monitoring devices and supervisory circuits shall be tested every 3 years when extinguisher maintenance is performed. 2. 5. A written log of required hydrostatic test dates for extinguishers shall be maintained by the owner to verify that hydrostatic tests are conducted at the frequency required by NFPA 10. 3. In Group I-3, portable fire extinguishers shall be permitted to be located at staff locations. Inspector: BARRY STRATTON - Comments: FAIL 906.5 - Conspicuous location Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Inspector: BARRY STRATTON - Comments: FAIL 906.6 - Unobstructed and unobscured Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. Inspector: BARRY STRATTON - Comments: Printed on 07/24/2020 @ 09:11 Page 3 of 4 STATUS CODE DESCRIPTION FAIL 906.9 - Extinguisher installation The installation of portable fire extinguishers shall be in accordance with Sections 906.9.1 through 906.9.3. Inspector: BARRY STRATTON - Comments: Fire Extinguishers are needed FAIL R1 - Unsafe Structures Is the structure found to be dangerous to the life, health, property or safety of either the public or occupants of the structure? (IPMC 108.1.1) Inspector: BARRY STRATTON - Comments: Collapsed garage FAIL R2 - Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON - Comments: Electric on pole. Open box and wiring of 22O v receptacle. NEXT INSPECTION DATE 08/13/2020 CONTACT SIGNATURE Liz Litzkow Signed on: 08/14/2019 @ 07:36 INSPECTOR SIGNATURE BARRY STRATTON Signed on: 08/14/2019 @ 07:36 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON barry.stratton@waterloo-ia.org (319) 231-9147 Printed on 07/24/2020 @ 09:11 Page 4 of 4