HomeMy WebLinkAbout1815 Lafayette St_01072020WATERLOO FIRE RESCUE
INSPECTION REPORT
1815 LAFAYETTE ST, WATERLOO IA 50703
DETAILS
Inspection Date: 01/07/2020 | Inspection Type: Rental Inspection | Inspection Number: 3925 | Shift: N/A | Station: N/A |
Unit: N/A | Lead Inspector: BARRY STRATTON | Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 1031.2 - Reliability Required exit accesses, exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied. An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector: BARRY STRATTON - Comments: Wall needs repaired going to lower level #
3.
FAIL 1031.7 - Emergency escape
and rescue openings
Required emergency escape and rescue openings shall be maintained in accordance
with the code in effect at the time of construction, and the following: Required
emergency escape and rescue openings shall be operational from the inside of the
room without the use of keys or tools. Bars, grilles, grates or similar devices are
allowed to be placed over emergency escape and rescue openings provided the
minimum net clear opening size complies with the code that was in effect at the time
of construction and such devices shall be releasable or removable from the inside
without the use of a key, tool or force greater than that which is required for normal
operation of the emergency escape and rescue opening.
Inspector: BARRY STRATTON - Comments: Egress window in bedroom does not meet
code. Bed in living room being used for sleeping purposes. No egress window in living
room.
FAIL 1103.9 - Carbon monoxide
alarms
Existing Group I-1, I-2, I-4 and R occupancies shall be equipped with carbon monoxide
alarms in accordance with Section 915, except that the carbon monoxide alarms shall
be allowed to be solely battery operated.
Inspector: BARRY STRATTON - Comments:
FAIL 605.1 - Abatement of
electrical hazards
Identified electrical hazards shall be abated. Identified hazardous electrical conditions
in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Electric outlets have tension issues that
need addressed. Outlets need changed out. All light fixtures need approved globes
installed. Open neutral on outlet in living room. Need knockouts installed on all open
areas in electric panels.
Printed on 07/24/2020 @ 15:13
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 906.3 - Size and distribution The size and distribution of portable fire extinguishers shall be in accordance with
Sections .1 through .4.
Inspector: BARRY STRATTON - Comments: Fire extinguisher needs replaced.
FAIL 906.9 - Extinguisher
installation
The installation of portable fire extinguishers shall be in accordance with Sections
906.9.1 through 906.9.3.
Inspector: BARRY STRATTON - Comments:
FAIL 907.2.11 - Single- and
multiple-station smoke
alarms
Listed single- and multiple- station smoke alarms complying with UL 217 shall be
installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
Inspector: BARRY STRATTON - Comments: Need smoke detectors in each bedroom
and outside of the bedrooms.
FAIL 915.4 - Carbon monoxide
alarms
Carbon monoxide alarms shall comply with Sections 915.4.1 through 915.4.3.
Inspector: BARRY STRATTON - Comments: CO detectors needed in vicinity of the
bedrooms.
FAIL R1 - Unsafe Structures Is the structure found to be dangerous to the life, health, property or safety of either
the public or occupants of the structure? (IPMC 108.1.1)
Inspector: BARRY STRATTON - Comments: Potential mold growth and bug infestation.
FAIL R5 - Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and
sanitary state? (IPMC 304)
Inspector: BARRY STRATTON - Comments: Need handrails to lower apartment # 3.
FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: Entry door needs to be weather tight. Door
hardware needs replaced. Holes in walls need repaired. Peeling paint needs
corrected. Ceiling tiles need replaced in living room and bathroom. Carpet in living
room has tears and needs replaced. Several trip hazards from condition of carpet.
Need handrail installed on stairs to lower unit # 3.
Printed on 07/24/2020 @ 15:13
Page 2 of 3
STATUS CODE DESCRIPTION
FAIL R6.A. - Interior Structure-
Unsafe Conditions
Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Inspector: BARRY STRATTON - Comments: Open holes on electric panel. Egress
window does not meet code.
FAIL R6.C. - Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON - Comments: Toilet does not flush possible flushing valve
needs replaced. Sink needs mounting to wall in bathroom. Sewer stack leaking in
kitchen.
REINSPECTION DATE
02/05/2020
CONTACT SIGNATURE
Encanto Associates LLC
Signed on: 01/07/2020 @ 11:23
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 01/07/2020 @ 11:23