INSPECTION REPORT
BLDG 416 SULLIVAN AVE, 416 SULLIVAN AVE, WATERLOO IA 50701
DETAILS
Inspection Date: 09/12/2019 | Inspection Type: Rental Inspection | Inspection Number: 3409 | Shift: N/A | Station: N/A |
Unit: N/A | Lead Inspector: BARRY STRATTON | Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 1008.1 - Means of egress
illumination
Illumination shall be provided in the means of egress in accordance with Section
1008.2. Under emergency power, means of egress illumination shall comply with
Section 1008.3.
Inspector: BARRY STRATTON - Comments:
FAIL 1010.1.9 - Door operations Except as specifically permitted by this section, egress doors shall be readily
openable from the egress side without the use of a key or special knowledge or
effort.
Inspector: BARRY STRATTON - Comments: Egress doors shall be maintained. Brock
advised owner during inspection
FAIL 703.2 - Opening protectives Opening protectives shall be maintained in an operative condition in accordance with
NFPA 80. Where allowed by the fire code official, the application of field-applied labels
associated with the maintenance of opening protectives shall follow the
requirements of the approved third-party certification organization accredited for
listing the opening protective. Fire doors and smoke barrier doors shall not be
blocked or obstructed, or otherwise made inoperable. Fusible links shall be replaced
promptly whenever fused or damaged. Fire door assemblies shall not be modified.
Inspector: BARRY STRATTON - Comments: Egress doors shall be maintained in
working condition.
FAIL 901.6 - Inspection, testing and
maintenance
Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust
systems, and smoke and heat vents shall be maintained in an operative condition at
all times, and shall be replaced or repaired where defective. Nonrequired fire
protection systems and equipment shall be inspected, tested and maintained or
removed.
Inspector: BARRY STRATTON - Comments: Information is being given to Brock
FAIL 907.2.11 - Single- and
multiple-station smoke
alarms
Listed single- and multiple- station smoke alarms complying with UL 217 shall be
installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
Inspector: BARRY STRATTON - Comments: Smoke detector in hallway unit # 307
Printed on 07/24/2020 @ 11:13
Page 1 of 2
STATUS CODE DESCRIPTION
FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: Egress lights, dryer vent in laundry room
need attached, baluster needs replaced on stairs. Egress doors west end need
maintenance. Unit # 103 toilet needs repaired.
GENERAL NOTES
BARRY STRATTON - 09/12/2019 @ 11:16 Dryer vents need to be attached. IPMC 403.5
REINSPECTION DATE
10/10/2019
CONTACT SIGNATURE
Christiin
Signed on: 09/12/2019 @ 11:14
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 09/12/2019 @ 11:14