Loading...
HomeMy WebLinkAbout65 Conger StreetWATERLOO FIRE RESCUE INSPECTION REPORT 65 CONGER ST, WATERLOO IA 50703 DETAILS Inspection Date: 09/11/2019 | Inspection Type: Rental Inspection | Inspection Number: 3383 | Shift: N/A | Station: N/A | Unit: N/A | Lead Inspector: BARRY STRATTON | Other Inspectors: N/A STATUS CODE DESCRIPTION FAIL 1103.9 - Carbon monoxide alarms Existing Group I-1, I-2, I-4 and R occupancies shall be equipped with carbon monoxide alarms in accordance with Section 915, except that the carbon monoxide alarms shall be allowed to be solely battery operated. Inspector: BARRY STRATTON - Comments: CO detector is needed in unit # 103 and all units in vicinity of the bedrooms. Unit # 202 also needs CO FAIL 1104.6 - Guards Guards complying with this section shall be provided at the open sides of means of egress that are more than 30 inches (762 mm) above the floor or grade below. Inspector: BARRY STRATTON - Comments: Need guard rail repaired on 2nd floor. Also need porch baluster FAIL 506.1 - Where required Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official. Inspector: BARRY STRATTON - Comments: Updated knox boxes required to be installed on building. Contact Fire marshal for locates. Lt Chris Ferguson 319-493- 1136 Printed on 07/24/2020 @ 10:16 Page 1 of 3 STATUS CODE DESCRIPTION FAIL 703.1 - Maintenance The required fire-resistance rating of fire-resistance-rated construction, including, but not limited to, walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems, shall be maintained. Such elements shall be visually inspected by the owner annually and properly repaired, restored or replaced where damaged, altered, breached or penetrated. Records of inspections and repairs shall be maintained. Where concealed, such elements shall not be required to be visually inspected by the owner unless the concealed space is accessible by the removal or movement of a panel, access door, ceiling tile or similar movable entry to the space. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. Inspector: BARRY STRATTON - Comments: FAIL 907.2.11 - Single- and multiple-station smoke alarms Listed single- and multiple- station smoke alarms complying with UL 217 shall be installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. Inspector: BARRY STRATTON - Comments: FAIL 907.2.18.1 - Smoke detectors Not fewer than one smoke detector listed for the intended purpose shall be installed in all of the following areas: 1. Mechanical equipment, electrical, transformer, telephone equipment, elevator machine or similar rooms. 2. Elevator lobbies. 3. The main return and exhaust air plenum of each air-conditioning system serving more than one story and located in a serviceable area downstream of the last duct inlet. 4. Each connection to a vertical duct or riser serving two or more floors from return air ducts or plenums of heating, ventilating and air-conditioning systems, except that in Group R occupancies, a listed smoke detector is allowed to be used in each return air riser carrying not more than 5,000 cfm (2.4 m^3/s) and serving not more than 10 air inlet openings. Inspector: BARRY STRATTON - Comments: Smoke detector in bedroom unit #103 Unit # 202 FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON - Comments: Ceiling in bathroom and walls need repaired. GENERAL NOTES Printed on 07/24/2020 @ 10:16 Page 2 of 3 BARRY STRATTON - 09/11/2019 @ 14:12 All floors shall be maintained in good condition unit # 202 hallway and bedrooms. IPMC 305.6 BARRY STRATTON - 09/11/2019 @ 14:13 Need to secure vent covers in bedroom. IPMC 603 REINSPECTION DATE 10/10/2019 CONTACT SIGNATURE Christin Signed on: 09/11/2019 @ 14:15 INSPECTOR SIGNATURE BARRY STRATTON Signed on: 09/11/2019 @ 14:15 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON barry.stratton@waterloo-ia.org (319) 231-9147 Printed on 07/24/2020 @ 10:16 Page 3 of 3