HomeMy WebLinkAbout65 Conger StreetWATERLOO FIRE RESCUE
INSPECTION REPORT
65 CONGER ST, WATERLOO IA 50703
DETAILS
Inspection Date: 09/11/2019 | Inspection Type: Rental Inspection | Inspection Number: 3383 | Shift: N/A | Station: N/A |
Unit: N/A | Lead Inspector: BARRY STRATTON | Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 1103.9 - Carbon monoxide
alarms
Existing Group I-1, I-2, I-4 and R occupancies shall be equipped with carbon monoxide
alarms in accordance with Section 915, except that the carbon monoxide alarms shall
be allowed to be solely battery operated.
Inspector: BARRY STRATTON - Comments: CO detector is needed in unit # 103 and all
units in vicinity of the bedrooms. Unit # 202 also needs CO
FAIL 1104.6 - Guards Guards complying with this section shall be provided at the open sides of means of
egress that are more than 30 inches (762 mm) above the floor or grade below.
Inspector: BARRY STRATTON - Comments: Need guard rail repaired on 2nd floor. Also
need porch baluster
FAIL 506.1 - Where required Where access to or within a structure or an area is restricted because of secured
openings or where immediate access is necessary for life-saving or fire-fighting
purposes, the fire code official is authorized to require a key box to be installed in an
approved location. The key box shall be of an approved type listed in accordance with
UL 1037, and shall contain keys to gain necessary access as required by the fire code
official.
Inspector: BARRY STRATTON - Comments: Updated knox boxes required to be
installed on building. Contact Fire marshal for locates. Lt Chris Ferguson 319-493-
1136
Printed on 07/24/2020 @ 10:16
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 703.1 - Maintenance The required fire-resistance rating of fire-resistance-rated construction, including,
but not limited to, walls, firestops, shaft enclosures, partitions, smoke barriers,
floors, fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems, shall be maintained. Such
elements shall be visually inspected by the owner annually and properly repaired,
restored or replaced where damaged, altered, breached or penetrated. Records of
inspections and repairs shall be maintained. Where concealed, such elements shall
not be required to be visually inspected by the owner unless the concealed space is
accessible by the removal or movement of a panel, access door, ceiling tile or similar
movable entry to the space. Openings made therein for the passage of pipes,
electrical conduit, wires, ducts, air transfer openings and holes made for any reason
shall be protected with approved methods capable of resisting the passage of smoke
and fire. Openings through fire-resistance-rated assemblies shall be protected by
self- or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector: BARRY STRATTON - Comments:
FAIL 907.2.11 - Single- and
multiple-station smoke
alarms
Listed single- and multiple- station smoke alarms complying with UL 217 shall be
installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
Inspector: BARRY STRATTON - Comments:
FAIL 907.2.18.1 - Smoke detectors Not fewer than one smoke detector listed for the intended purpose shall be installed
in all of the following areas: 1. Mechanical equipment, electrical, transformer,
telephone equipment, elevator machine or similar rooms. 2. Elevator lobbies. 3. The
main return and exhaust air plenum of each air-conditioning system serving more
than one story and located in a serviceable area downstream of the last duct inlet. 4.
Each connection to a vertical duct or riser serving two or more floors from return air
ducts or plenums of heating, ventilating and air-conditioning systems, except that in
Group R occupancies, a listed smoke detector is allowed to be used in each return air
riser carrying not more than 5,000 cfm (2.4 m^3/s) and serving not more than 10 air
inlet openings.
Inspector: BARRY STRATTON - Comments: Smoke detector in bedroom unit #103 Unit
# 202
FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: Ceiling in bathroom and walls need
repaired.
GENERAL NOTES
Printed on 07/24/2020 @ 10:16
Page 2 of 3
BARRY STRATTON - 09/11/2019 @ 14:12 All floors shall be maintained in good condition unit # 202 hallway and bedrooms. IPMC
305.6
BARRY STRATTON - 09/11/2019 @ 14:13 Need to secure vent covers in bedroom. IPMC 603
REINSPECTION DATE
10/10/2019
CONTACT SIGNATURE
Christin
Signed on: 09/11/2019 @ 14:15
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 09/11/2019 @ 14:15
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
barry.stratton@waterloo-ia.org
(319) 231-9147
Printed on 07/24/2020 @ 10:16
Page 3 of 3