HomeMy WebLinkAboutJuly - August 2020 InspectionsWATERLOO FIRE RESCUE
INSPECTION REPORT
db
Inspection
Date: 08/19l2020
I Inspection Type:
Rental
Inspection
Inspection
Number: 4579 Shift: N/A Station: N/A
Unit: N/A
Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A Fee:
$50.00
STATUS CODE DESCRIPTION - -
FAIL 1018.1 -General Aisles and aisle accessways serving as a portion of the exit access in the means of
egress system shall comply with the requirements of this section. Aisles or aisle
accessways shall be provided from all occupied portions of the exit access that
contain seats, tables, furnishings, displays and similar fixtures or equipment. The
minimum width or required capacity of aisles shall be unobstructed. Exception:
Encroachments complying with Section 1005.7.
Inspector: BARRY STRATTON - Comments: Egress path still unsafe from rear of
building.
FAIL 901.6 -Inspection, testing and Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust
maintenance systems, and smoke and heat vents shall be maintained in an operative condition at
all times, and shall be replaced or repaired where defective. Nonrequired fire
protection systems and equipment shall be inspected, tested and maintained or
removed.
Inspector: BARRY STRATTON -Comments: Still no records for alarm system in
building.
FAIL 907.2.11.2 -Groups R-2, R-3, Single ormultiple-station smoke alarms shall be installed and maintained in Groups
R-4 and I-1 R-2, R-3, R-4 and I-1 regardless of occupant load at all of the following locations: 1. On
the ceiling or wall outside of each separate sleeping area in the immediate vicinity of
bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a
dwelling unit, including basements but not including crawl spaces and uninhabitable
attics. In dwellings or dwelling units with split levels and without an intervening door
between the adjacent levels, a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is less than one full story
below the upper level.
Inspector: BARRY STRATTON -Comments:
FAIL R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON -Comments: Rear stairs, landings, & no handrails on
rear of building.
rnorea a� os¢erzoza @ oesz
Page 1 of 3
STATUS CODE
DESCRIPTION
FAIL R4 - Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON -Comments: Rear stairs to 12 plex
FAIL RS -Exterior Structure
Is the exterior
of the
structure maintained
in good
repair, structurally sound and
sanitary state?
(IPMC
304)
Inspector: BARRY STRATTON -Comments: Every exterior stairway, deck, porch, and
balcony, and all appurtenances attached thereto, shall be maintained structurally
sound, in good repair, with proper anchorage and capable of supporting the
imposed loads.
GENERAL NOTES
BARRY STRATTON - 08/19/2020 @ 10:26 Property was notified back in May 2020 about stairs and on today's date stairs are still
unsafe. Double fee for rental registration has yet to be received by the Clerk's Office,
BARRY STRATTON - OS/19/2020 @ 10:26 9-7-6 A(3): Failure to correct deficiencies shall result in municipal citations) being
ssued.
REINSPECTION DATE
09/16/2020
CONTACT SIGNATURE
Equity Vestors LLC �/V� �`�
Signed on: 08/19/2020 @ 10:27
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 08/19/2020 @ 10:27
Printetl an 08262D20 @ 09:52
Page 2 of 3
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
ba rry.stratton@waterloo-ia.org
(319) 231-9147
rnmed oo aerzerzozo @ ossz
Page 3 of 3
WATERLOO FIRE RESCUE
INSPECTION REPORT �+
1211 LANGLEY RD, WATERLOO IA 50702
DETAILS -
Inspection Date: 07/21/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4578 1 Shift: N/A Station: N/A
Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A I Fee: $50.00
STATUS 'CODE 'DESCRIPTION
FAIL 7078.1 -General Aisles and aisle accessways serving as a portion of the exit access in [he means of
egress system shall comply with the requirements of this section, Aisles or aisle
accessways shall be provided from all occupied portions of the exit access that
contain seats, tables, furnishings, displays and similar fixtures or equipment. The
nlinirnum width or required capacity of aisles shall be unobstructed Exception:
Encroachments complying with Section 1005.7.
Inspector. BARRY STRATTON - Comments: Egress path from rear of building is unsafe
and not to code.
FAIL 901.E -Inspection, testingand Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust
maintenance systems, and smoke and heat vents shall be maintained in an operative condition at
all times, and shall be replaced or repaired where defective. Nonrequired fire
protection systems and equipment shall be inspected, tested and maintained or
removed.
htspector: BARRY STRATTON -Comments: Records needed for alarm system in
building
PAIL 907.2.7 L2-Groups R-2, R-3, Single onnultiple-station smoke alarms shall be installed and maintained in Groups
R-4 and I-1 R-2, R-3, R-4 and I-t regardless of occupant load at all of the following locations: 1. On
the ceiling or wall outside of each separate sleeping area in the immediate vicinity of
bedrooms. 2. In each room used for sleeping purposes. 3. In each stay within a
dwelling unit, including basements but not including crawl spaces and uninhabitable
attics. In dwellings or dwelling units with split levels and without an intervening door
between the adjacent levels, a smoke alarm installed on the upper level shall suffice
Lot the adjacent lower level provided that the lower level is less than one full story
below the upper level,
Inspector: BARRY STRATTON -Comments:
FAIL R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (I PMC 108.1.2)
Inspector: BARRY STRATTON -Comments: Rear stairs, landings, & no handrails
installed.
v,�� o�esrzerzozo-co3s9 �a Page 1 of2
STATUS CODE DESCRIPTION
FAIL R4 - Exterior PropertyAreas Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes gracling and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON -Comments: Rear stairs to 12 plex.
FAIL RS -Exterior Structure Is the exterior of the structure maintained in good repair, structurally wuncl and
sanitary state? (IPMC 304)
Inspector: BARRY sTRATTON -Comments: Every exterior stairway, deck, porch, and
balcony, and all appurtenances attached thereto, shall be maintained structurally
souncl, in good repair, with property anchorage and capable of supporting the
imposed loads.
GENERAL NOTES
BARRY sTRATTON - 07/21/2020 @ 11:53 Property was notified about violations back in May 2020 and stairs are still unsafe and
not constructed to code. Double fee for rental registration still not received by the
Clerk's Office.
RElNSPECTION DATE
08/19/2020
CONTACT SIGNATURE
Equity Vestors ELC �� A1l
signed on: 07/212020 @ 11:50 r � 1_
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 07/21/2020 @ 11:50
QUESTIONS ABOUT YOUR lNSPECfilON7
BARRY STRATfON
ba ny. stra tton@waterloo-i a.o rg
(319) 231-9147
v,��. a�esrzsaaza�nese
f2oPage 2 of 2
WATERLOOMOMMITM
INSPECTION REPORT
DETAILS
Inspection
Date: 07/21 /2020
I Inspection Type:
Rental
Inspection
Inspection Number: 4584 Shift: N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A
STATUS CODE ` DESCRIPTION
FAIL 1010.1.9 -Door operations Except as specifically permitted by this section, egress doors shall be readily
openable from the egress side without the use of a key or special knowledge or
effort.
Inspector: BARRY STRATTON -Comments: Front door has broken windows and screen
or is broken and needs replaced.
FAIL 605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Kitchen outlets are not grounded. Multi
plug adapters in use and need to be removed because they are not allowed.
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in ail of the following locations: 1. in new
and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: in
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 mm)
of commercial cooking equipment. 3, in areas where flammable or combustible
liquids are stored, used or dispensed. 4. On each floor of structures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1, S.
Where required by the sections indicated in Table 906.1, 6. Special -hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON - Comments: Need a fire extinguisher in unit.
P/intetl an 08/262020 eu 10.00
Page t of 3
STATUS
Id1i1
FAIL
FAIL
FAIL
FAIL
CODE DESCRIPTION
907.2.1 L2 - Groups R-2, R-31 Single or multiple -station smoke alarms shall be installed and maintained in Groups
R-4 and 1-1 R-2, R-3, R-4 and 1-1 regardless of occupant load at all of the following locations: 1. On
the ceiling or wall outside of each separate sleeping area in the immediate vicinity of
bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a
dwelling unit, including basements but not including crawl spaces and uninhabitable
attics. In dwellings or dwelling units with split levels and without an intervening door
between the adjacent levels, a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is less than one full story
below the upper level.
Inspector: BARRY STRATTON -Comments: All smoke detectors need to be in working
condition.
R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON -Comments: Water heater is missing discharge tube.
Water heater installed did not have proper permits & inspections.
R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON -Comments: Guard railing around front parch is broken
and needs replaced. Weeds and garbage.
R6 -Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON -Comments: Need handrails to basement. Floor at rear
door is unstable and needs replaced. Water in basement needs attention. Drain
backed up in basement. Kitchen walls have holes in walls and need fixed. Door trim
missing on door to dining room and needs replaced. Thermostat needs replaced.
Repair all broken glass that is broken.
R6.A. -Interior Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON - Comments: Plumbing backup in basement.
R6.C. -Mechanical Egiupment
Are mechanical appliances
properly installed
and maintained in good
working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON -Comments: Water heater missing discharge tube.
Bathtub leaking into basement.
Printed on 08/26/2020 @ 10:00
Page 2 of 3
STATUS CODE
17#3N7177C77i
FAIL R6.13. - Receptacles Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grounding -type receptacle or a receptacle with a GFCI. Every bathroom shall contain
not less than one receptacle. Any new bathroom receptacle shall have GFCI
protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2)
Inspector: BARRY STRATTON - Comments: Electric system has grounding issues that
need corrected.
REINSPECT/ON DATE
08/19/2020
CONTACT S/fiNATURE
CNC Investments LLC
Signed on: 07/21/2020 @ 15:36
INSPECTOR 5/6NATURE
BARRY STRATTON
Signed on: 07/21 /2020 @ 15:36
QUESTIONS AEOUT YOUR INSPECTION?
BARRY STRATTON
b a rryst ratio n @waterloo-ia. o rg
(319) 231-9147
: / V \/A'�_
Printed on OBI]6R020 @ IQW
Page 3 of 3
WATERLOO FIRE RESCUE
INSPECTION REPORT �a
SS48 SUMMERLAND DR, WATERLOO IA 50701
DETAILS
Inspection
Date: 07/22/2020
1 Inspection Type:
Rental
Inspection I
Inspection Number: 4586 I Shift: N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A
STATUSCODE DESCRIPTION
FAIL 605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazarcis in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiling devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Outlet in mechanical room has hot/neuttal
reversed.
FAIL R6.D. - Receptades Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grounding -type receptacle or a receptacle with a GFCI. Every bathroom shall contain
not less than one receptacle. Any new bathroom receptacle shall have GFCI
protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2)
Inspector: BARRY STRATTON - Comments: Outlet in mechanical room hot/neutral
reversed.
REINSPECTION DATE
08/17/2020
CONTACT SIGNATURE
Troy Luck �Ra`
Signed on: 07/22/2020 @ 10:40 /Y
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 07/22/2020 @ 10:40
VriO an 09/26I2020�10:1_>
��Page 1 of 2
QUESTIONS ABOUT YOUR INSPECTION?
EARRY STRATTON
barry. sttatton @ovate rl o o-i a. o rg
(319) 231-9147
v.�. zee waz
��Page 2 of 2
WATERLOO FIRE SC ll
INSPECTION REPORT Q,.
520 ANKENY ST. WATERLOO IA S0703
DETAILS
Inspection
Date: 07/23/2020
1 Inspection Type:
Rental
Inspection
I Inspection
Number: 4472 IShift N/A Station: N/A
Unit: N/A
( Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A I Fee:
$50.00
STATUS 'CODE - DESCRIPTION
FAIL 1010.7.9.4 -Bolt locks Manually operated flush bolts or surface bolts are not pennit[ed. Exceptions: 1. On
(loots not required for egress in individual dwelling units or sleeping units. 2. Where
a pair of doors serves a storage or equipment room, manually operated edge- or
surface -mounted bolts are permitted on the inactive leaf. 3. Where a pair of doors
serves an occupant load of less than 50 persons in a Group B, F or S occupancy,
manually operated edge- or surface -mounted bolts are permitted on the inactive
leaf. The inactive leaf shall not contain doorknobs, panic bars or similar operating
hat dware.4. Where a pair of doors serves a Group B, F or S occupancy, manually
operated edge- or surface -mounted bolts are permitted on the inactive leaf provided
such inactive leaf is not needed to meet egress capacity requirements and the
building is equipped throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1. The inactive leaf shall not contain doorknobs, panic bars of -
similar operating hardware. 5. Where a pair of doors serves patient care rooms in
Gcup 1-2 occupancies, self -latching edge- or Solface-mounted bolts are permitted on
the inactive leaf provided that the inactive leaf is not needed to meet egress capacity
requirements and the inactive leaf shall not contain doorknobs, panic bars or similar
operating hardware.
Inspector: BARRY STRATTON - Comments: Latch locks on doors need removed.
FAIL 1031.7 - 6nergency escape Required emergency escape and rescue openings shall be maintained in accordance
and resare openings with the code in effect at the tinne of construction, and the following: Required
emergency escape and rescue openings shall be operational from the inside of the
room without the use of keys or tools. Bars, grilles, grates or similar devices are
allowed to be placed over emergency escape and rescue openings provided the
mininnurn net clear opening size complies with the code that was in effect at the time
Of construction and such devices shall be releasable or removable from the inside
without the use of a key, tool or force greater than that which is required for normal
operation of the emergency escape and rescue opening.
Inspector: BARRY STRATTON - Comments: Latch locks on doors need removed.
FAIL 605.1 - Abatement of Identified elecuical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code offcial.
Electrical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Outlets in house do not have grounds.
Some outlets have the hot/neutral reversed. Exposed wires on porch were light is
missing.
v,i"zfOo"oarz5rzozoEio_iz
Page t of 4
STATUS CODE
DESCRIPTION
FAIL
FAIL
FAIL
FAIL
FAIL
FAIL
906.1 -Whet e required For fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, Be E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 1B-B: C. 2. Within 30 feet (9144 mm)
of commercial cooking equipment 3, In at where flammable or combustible
liquids are stored, used or dispensed. 4. On each floor of structures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1. 6, Special -hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON -Comments; Need updated fire extinguisher in unit.
907.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be
nutltiple-station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72,
alarms
Inspector: BARRY STRATTON - Comments: Need smoke detectors in each bedroom,
outside becitcorns, and in basement.
915.4 -Carbon monoxide Carbon monoxide alarms shall comply with Sections 915.4.1 through 915.4.3,
alarms
Inspector. BARRY STRATTON -Comments CO detector is needed in vicinity of the
bedrooms.
R4 -Exterior Property Areas Is [he exterior property area maintained in a clean, safe, and sanitary condition?This
includes grading and dtainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON -Comments: Window sills and framing is rotten and
need replaced. Roof leaking and gutters need attention. Broken windows, windows
not capable of opening.
RS - ExteriaStructwe Is the exterior of the structure maintained in good repair, structurally sound and
sanitary state? (IPMC 304)
Inspector. BARRY STRATTON -Comments: Windows, gutters, &doors.
RG -Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
e��c oo csrz�rzom r�io.iz E Page 2 of 4
STATUS CODE DESCRIMON
Inspector: BARRY STRATTON - Comments: Ceiling has collapsed in bechoom. kitchen,
and back entryway that is still not repaired/replaced. Front porch floor is unstable.
Windows are not functional and do not open in house. Doorjamb and hardware to
front door needs replaced. The condition of the h on[ door needs attention.
bativoom cabinets missing drawer fronts. Handrail is needed to Bleed code to
basement. Kitchen floor needs replaced. Any wet drywall from ceilings needs
removed and replaced. Door trim and jamb to bathroom needs replaced. Latch locks
need removed. Bedroom doors broken and need replaced.
FAIL
R6.A. - Interior Structure-
Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON - Comments: Cellulose from attic all over house. Electric
issues. peeling paint, windows. doors, water heater.
FAIL
R6.B. - Residential Heating
Are dwellings provided with heating facilities capable of maintaining a room
temperature of 68P (IPMC 602.2)
Inspector: BARRY STRATTON - Comments: Furnace filter
FAIL
R6.C. - Mechanical Eqiupment
Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON - Comments: Water heater missing cover. Stove is not in
working condition.
FAIL
R6.D. - Receptacles
Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grounding -type receptacle or a receptacle with a GFCI. Every bativoom shall contain
not less than one receptacle. Any new bathroom receptacle shall have GFCI
protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2)
Inspector. BARRY STRATTON - Comments: Grounding issues, and wiring issues.
REINSPECTION DATE
08/24/2020
CONTACT SIGNATURE
LDN Properties LLC
Signed on: 07/23/2020 @ 09:21 /
v,mra oo es¢erzoze _ inrz
Page 3 of 4
INSPECTOR SIGNATURE
EARRY ON
on: 07/
Signed on: 07/23/2020 @ 09:21
QUESTIONS ABOUT YOUR INSPECTION?
EARRY STRATTON
ba ny. stra tton@waterloo-i a. org
(319) 231-9147
Pn� on OB/2E/E026 �r 1012
Page 4 of 4
/ m#r ,
WATERLOOINSPECTION REPORT
IA 50703
DETAILS
Inspection
Date: 07/23/2020
1 Inspection Type:
Rental
Inspection
I Inspection
Number: 4472 1Shift: N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A I Fee:
$50.00
STATUSCODE - DESCRIPTION
FAIL 1010.1.9.4 -Bolt locks Manually operated flush bolts or surface bolts are no[ permitted. Exceptions: 1. On
cloors not required for egress in individual dwelling units or sleeping units. 2. Where
a pair of doors serves a storage or equipment room, manually operated edge- or
surface -mounted bolts are permitted on the inactive leaf. 3. Where a pair of doors
serves an occupant load of less than 50 persons in a Group B, F or S occupancy,
manually operated edge- or surface -mounted bolts are permitted on the inactive
leaf. The inactive leaf shall not contain doorknobs, panic bars or similar operating
hardware. 4. Where a pair of doors serves a Group B, F or S occupancy, manually
operated edge- or surface -mounted bolts are permitted on the inactive leaf provided
such inactive leaf is not needed to meet egress capacity requirements and the
building is equipped throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1. The inactive leaf shall not contain doorknobs, panic bars or
similar operating hardware. 5. Where a pair of door s serves patient care rooms in
Group 1-2 occupancies, self latching edge- or surface -mounted bolts are permitted on
the inactive leaf provided that the inactive leaf is not needed to meet egress capacity
requirements and the inactive leaf shall not contain doorknobs, panic bars or similar
operating hardware.
Inspector: BARRY STRATTON - Comments: Latch locks on doors need removed.
FAIL 1031.7 -Emergency escape Required emergency escape and rescue openings shall he maintained in accordance
and rescue openings with the code in effect at the time of construction, and the following: Required
emergency escape and rescue openings shall be operational from the inside of the
room without the use of keys or tools. Bars, grilles, grates or similar devices are
allowed to be placed over emergency escape and rescue openings provided the
minimum net dear opening size complies with the code that was in effect at the time
Of construction and such devices shall be releasable or removable from the inside
without the use of a key, tool or for greater than that which is required for normal
operation of the emergency escape and rescue opening.
Inspector: BARRY STRATTON - Comments: Latch locks on doors need removed.
PAIL 605.1 - Abatement of Identified elecuical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Outlets in house do not have grounds.
Some outlets have the hot/neutral reversed. Exposed wiles on porch were light is
missing.
v,ipaa on esrzsrzozo e- m:a
Page 1 of 4
STATUS
CODE DESCRIPTION
FAIL
FAIL
FAIL
FAIL
FAIL
FAIL
906.1 - Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 nun)
of commercial cooking equipment 3, In at where flammable or combustible
liquids are stored, used or dispensed. 4. On each floor of structures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1. 6. Special -hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON -Comments: Need updated fire extinguisher in unit.
9D7.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Need smoke detectors in each bedroom,
outside bedrooms, and in basement.
915.4 -Carbon monoxide Carbon monoxide alarms shall comply with Sections 915.4.1 through 975.43.
alarms
Inspector: BARRY STRATTON -Comments CO detector is needed in vicinity of the
bedrooms.
R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations- (IPMC 302)
Inspector. BARRY STRATTON -Comments: Window sills and framing is rotten and
need replaced. Roof leaking and gutters need attention. Broken windows, windows
not capable of opening.
RS - Exterior Structure Is the exterior of the structw-e maintained in goad repair, strucriirally sound and
sanitary state? (IPMC 304)
Inspector: BARRY STRATTON -Comments: Windows, gutters, & doors.
R6 -Interior- Structure Has the interior of the struc[tu-e and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Grin on 06/25R020�1012
Page 2 of 4
STATUS CODE
DESCRIPTION
Inspector: BARRY STRATTON - Comments: Ceiling has collapsed in bedroom. kitchen,
and back entryway that is still not repairedheplaced. Font porch floor is unstable.
Windows are notfunctional and do not open in house. Doorjamb and hardware to
front door needs replaced. The condition of the front door needs attention.
bathroom cabinets missing drawer fronts. Handrail is needed to meed code to
basement. Kitchen floor needs replaced. Any wet drywall from ceilings needs
removed and replaced. Door trim and jamb to bathroom needs replaced Latch locks
need removed. Bedroom doors broken and need replaced.
FAIL R6.A. - Interior Structure-
Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON - Comments: Cellulose from attic all over house- Electric
issues. peeling paint, windows. doors, water heater.
FAIL R6.B. - Residential Heating
Are dwellings provided with heating facilities capable of maintaining a room
temperature of 68F? (IPMC 602.2)
Inspector: BARRY STRATTON - Comments: Furnace filter
FAIL R6.C. -Mechanical Egiupmeni Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON - Comments: Water heater missing cover. Stove is not in
working condition.
FAIL R6,13. - Receptacles Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grounding -type receptacle or a receptacle with a GFCI. Every ha[hroom shall contain
not less than one receptacle. Any new bathroom receptacle shall have GFCI
Ell otection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2)
Inspector: BARRY STRATTON - Comments: Grounding issues, and wiring issues.
REINSPECTION DATE
oa/zn/zozo
CONTACT SIGNATURE
LDN Properties LLC
Signed on: 07/23/2020 @ 09:21
�II
Print on GS25ri020� iG.�2
xtlPage 3 of 4
INSPECTOR SIGNATURE
BARRY on: ATFON
07/2
Signed on: 07/2312020 @ 09:21
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
ba rry. s n-a tton@waterloo-i a.o rg
(319) 231-9147
a�= oo asr�zozc�iciz
Page 4 of 4
WATERLOO FIRE RESCUEINSPECTION REPORT
WATERLOO IA 50702
DETAILS
Inspection
Date: 07/23/2020
1 Inspection Type:
Rental
Inspection
I Inspection Number: 4596 1 Shift: N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A
STATUS `CODE MCRIPTION
FAIL 1010.1.9 -Door operations Except as specifically permitted by this section, egress doors shall be readily
openable from the egress side without the use of a key or special knowledge or
effort.
Inspector: BARRY STRATTON -Comments: All doors shall he openable and capable of
preforming their intended function. All doors shall have proper hardware installecl on
doors. Screen/front door at front entrance has broken threshold. Door to out of back
of unit can not be locked and must remain open for egress purposes.
FAIL 5D5.1 -Address identification New and existing buildings shall be provided with approved address identification.
The address identification shall be legible and placed in a position that is visible from
the street or road fronting the property. Address identification characters shall
contrast with their background. Address numbers shall be At numbers or
alphabetical letters. Numbers shall not be spelled out. Each character shall be not
less than 4 inches (102 run) high with a minimum stroke width of 112 (12.7 mrn).
Where required by the fire code official, address identification shall be provided in
additional approved locations to facilitate emergency response. Where access is by
means of a private road and the building cannot be viewed from the public way, a
monument, pole or other sign or means shall be used to identify the structure.
Address identification shall be maintained.
lospector: BARRY STRATTON - Comments: Aparunents are not numbered.
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identifed hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code offcial.
Electrical wiring, devices, appliances and other equipment that is modified or
clamaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Outlets in several rooms have grounding
issues. Some outlets do not work. Extension cords need to be removed. Multi
adapters also need to be removed. Bathroom light has open sockets and needs
replaced. Outlet on porch is pulling out of wall and is not grounded,
v+�� o�osrzwzozcc �m�s
cEePage i of 4
STATUS
CODE DESCRIPTION -
FAIL
FAIL
Iy=111
FAIL
FAIL
FAIL
906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E, F, H, I, M, R-11 R-21 R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 nmn)
of commercial cooking equipment. 3. In areas where flammable or combustible
liquicls are stored, used or dispensed. 4. On each floor of structures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1.6. Special -hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON -Comments: Need fire extinguishers in all units.
907.2.11.2 -Groups R-2, R-3, Single ormultiple-station smoke alarms shall be installed and maintained in Groups
R-4 and 1-1 R-2, R-3, R-4 and 1-1 regardless of occupant load at all of the following locations: 1. On
the ceiling or wall outside of each separate sleeping area in the immediate vicinity of
bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a
dwelling unit, including basements but not including crawl spaces and uninhabitable
attics. In dwellings or dwelling units with split levels and without an intervening door
between the adjacent levels, a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is less than one full story
below the upper level.
Inspector: BARRY STRATTON -Comments: Smoke detectors are needed in each
bedI oom, outside of the bedrooms, and in basement.
975.1.1 -Where required Carbon monoxide detection shall be provided in Group I-1, I-2, I-4 and R occupancies
and in classrooms in Group E occupancies in the locations specified in Section 915.2
where any of the conditions in Sections 915,1,2 through 915.1.6 exist.
Inspector: BARRY STRATTON -Comments: CO detectors are needed in vicinity of any
room used for sleeping purposes.
R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON -Comments: Gas Leak at stove
R5 -Exterior- Structure Is the exterior of the structure maintained in good repair, structurally sound and
sanitary state? (IPMC 304)
Inspector:
BARRY STRATTON -Comments: Need
gripable
handrails on
all stairs to
units.
R6 -Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Ptirtcd aii osnV2o2o.o w:a
Page 2 of 4
STATUS CODE ` DESCRIPTION
Inspector: BARRY STRATTON - Comments: Floors shall be maintained in good
condition. Several areas have large holes that give potential for somebody to fall into
basement Vent registers shall be maintained in good condition and be in place over
gravity fed grates. Windows shall be capable of being opened and closed. Broken
windows shall be replaced. Ceilings in unit need to be maintained in good condition.
Ceilings appear to have water damage from some type of leak. Kitchen cabinets shall
be in good condition. Under sink cabinet is decayed and cabinet needs replaced.
Transition strips are needed to be in place between rooms/hallways. Bed bug
infestation in building. Contact exterminator to do pest control on building.
FAIL R6.A. -Interior Structure-
Were any w�safe conditions noted during the interim inspection?(IPMC 305.1,1)
Unsafe Conditions
Inspector: BARRY STRATTON - Comments: Electric issues, gas leak
FAIL R6.B. - Residential Heating
Are dwellings provided with heating facilities capable of maintaining a room
temperature of 68F7 (IPMC 602.2)
Inspector: BARRY STRATTON - Comments: Floor- registers need to be in place. Gravity
air registers need to be in good condition and in place.
FAIL R6.C. - Mechanical Eyiupment
Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON - Comments: Stove has gas leak. Toilet is leaking in unit.
FAIL R&D. - Receptacles
Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grounding -type receptacle or a receptacle with a GFCI. Every bathroom shall contain
not less than one receptacle. Any new bathroom receptacle shall have GFCI
protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2)
Inspector: BARRY STRATTON - Comments: Outlets in unit are not grounded and some
pulling out of wall. Need licensed electrician to make repairs and have inspected.
REINSPECfiION DAfiE
08/24/2020
CONTACT SIGNATURE
Randy Schmidt M ��
Signed on: 07/23/2020 @ 13:58 l \
v��.ra an asrzerzazo c- io: i3
Page 3 of 4
INSPECTOR SIGNATURE
BARRY ON
on: 07/
Signed on: 07/23/2020 @ 1359
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
b a try. st ra tton @water) oo-ia.o rg
(319)231-9147
Pnnc on 09I25�E020 C10 13 E Page 4 of 4
WATERLOO FIRE RESCUEPo{
INSPECTION REPORT h
907 DOWNING AVE, WATERLOO IA 50701
DETAILS
Inspection
Date: 07/27/2020
1 Inspection Type:
Rental
Inspection
I Inspection
Number: 4461 Shift: N/A Station: N(A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors
N/A I Fee:
$50.00
STATUS CODE - DESCRIPTION
FAIL 906.1 -Where required
Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E, F, H, I, MIR-1, R-2, R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a mininwtn rating of 1-A: 10-13: C. 2. Within 30 feet (9144 tutu)
of commercial cooking equipment. 3. In areas where flammable or combustible
liquids are stored, used or dispensed. 4. On each floor of St JCtures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1.6. Special -hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON - Comments: Need Fire Extinguisher in unit.
FAIL 907.2.11 - Single- and
Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke
installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Smoke detectors installed per code are
located in all bedrooms, outside bedrooms, and in basement
FAIL 915A - Carbon monoxide
Carbon monoxide alarms shall comply with Sections 915.4.1 through 915.4.3.
alarms
Inspector: BARRY STRATTON - Comments:
FAIL R4 - Exterior Property At
Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON - Comments: Debris and nailer parked in rear yarcl.
FAIL R5 - Exterior Structure
Is the exterior of the structure maintained in good repair, structurally sound and
sanitary state? (IPMC 304)
v,�� oo usrzs�zoze 2^-ma3
�fePage 1 of 3
STATUS CODE DESCRIPTION
Inspector: BARRY STRATTON - Comments: Peeling paint, front and rear doors not
weather tight and should be replaced, front steps still not to code, broken windows,
& soffits still not repaired,
FAIL R6 -Interior SUuchire Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: Basement window needs replaced. Wood
and foam in place now and this installation is not an approved window covering.
FAIL R6.C. -Mechanical Egiuprnent Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON -Comments: Water heater draft hood need secured to
water heater. Dryer exhaust need to exhaust to the exterior of the house.
GENERA! NOTES
BARRY STRATTON-07/27l2020 @ 12:22 47-4 9-7-5; 2020 rental registration still not filed with the City of Waterloo.
BARRY STRATTON - 07/27/2020 @ 12:24 9-7-6 A (3): Failure to correR defciencies the Ciry of Waterloo will issue citation (s) for
all noted violation.
BARRY STRATTON - 07/27/2020 @ 12:25 IPMC 108.5 Prohibi[ed Occupancy: Unit shall not he occupied/rented un[il all violations
are f xed.
REINSPECTION DATE
OII/26/2020
CONTACT SIGNATURE
Nihacl Masic /� � r I
Signed on: 07/27/2020 @ 12:25 � 1Vf \VJ\ `
Pnn[x0 an OS/35/2026 � �G:13
Page 2 of 3
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 07/27/2020 @ 12:25
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
batty.st i atton@oratetloo-ia.otg
(319)231-9147
e��. o�eaawmze z-imis
E�Page 3 of 3
11ATERL00 FIRE RESCAC
INSPECTION REPORT
DETAILS
Inspection
Date: 07/28/2020
1 Inspection Type:
Rental
Inspection
I Inspection Number: 4615 Shift: N/A Statimt: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A
VIOLATIONS
No Violations Found
GENERAL NOTES
BARRY STRATTON - 07/282020 @ 10:39 Superior Pire 8/2019 extinguishers
NEXfi INSPECfiION DATE
07/282023
CONTACfi SIGNATURE
Premier Waterloo IA LLC
Signed on: 07/28/2020 @ 10:39
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 07l28/2020 @ 10:39
QUESTIONS ABOUT YOUR /NSPECTlON7
BARRY STRA.TTON
b a rry, stra t[on @waterloo-i a.o rg
(319) 231-9147
Print on 0d/26/2024�10_i3 �a Page 1 of 1
WATERLOO FIR E � °°
INSPECTION REPORT ..�"
205 ARGYLE ST, WATERLOO IA 50703
DETAILS
Inspection Date: 07/29/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4632 1 Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 506.1 -Where required Where access to or within a structure or an area is restricted because of secured
openings or where immediate access is necessary for life-saving or fire -fighting
purposes, the fire code official is authorized to require a key box to be installed in an
approved location. The key box shall be of an approved type listed in accordance with
UL 1037, and shall contain keys to gain necessary access as required by the fire code
official.
Inspector: BARRY STRATTON - Comments: Old Ti acess still not removed from building.
FAIL 907.2,11 - Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Smoke detectors need to be installed and
functioning to code.
FAIL R2 - Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON - Comments: Plumbing leaks wet and peeling paint,
carpet wet wall in closet needs closed up with drywall.
FAIL R3 - Unfit for Human Is the structure found to be fit for human occupancy according to the code? (IPMC
Occupancy 108.1.3)
Inspector: BARRY STRATTON - Comments: Water damaged carpet, drywall, and wood
flooring. All needs removed and replaced.
FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: MOLD in sink and bath cabinets. Water
damage carpet, flooring, and walls. Fire wall in closet need holes closed up with
drywall.
Prinretl on Q8/26R0]0 L^� iG:l3
Page 1 of 2
STATUS CODE DESCRIPTION
FAIL R6.A. - Interior Structure- Were any unsafe conditions noted during the intedor inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON - Comments: MOLD
FAIL R6.C. -Mechanical Egiupment Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON - Comments: Plumbing leaks, wet floors, wet carpet,
REINSPECTION DATE
08/31/2020
CONTACT SIGNATURE
John Foley
Signed on: 07/29/2020 @ 14:08
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 07/29/2020 @ 14:08
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
Lai ry.stratton@waterloo-ia.org
(319)231-9147
N�A IV�
eoo- z�izozoe io_ie
��oPage 2 of 2
WATERLOO /RESCUE
INSPECTION REPORT
205 ARGYLE ST, WATERLOO /A 50703
DETAILS
Inspection
Date: 07/29/2020
1 Inspection Type:
Rental
Inspection
I Inspection Number: 4634 1 Shift: N/A I Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A
STATUS 'CODE DESCRIPTION '.
PAIL
506.1 -Where required
Where access to or within a structure or an area is restricted because of secured
openings or where immediate access is necessary for life-saving or fire -fighting
Pill poses, the fire code official is authorized to require a key box to be installed in an
approved location. The key box shall be of an approved type listed in accordance with
UT 1037, and shall contain keys to gain necessary access as required by the fire code
official.
Inspector: BARRY STRATTON - Comments: Old Tracess Knox boxes still not removed
from building.
FAIL
907.2.11 - Single- and
Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke
installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Smoke detectors need to he installed and
functioning to code.
FAIL
Rt - Unsafe Structures
Is the structure found to be clangerous to the life, health, property or safety of either
the public or occupants of the structure? (IPMC 108.1.1)
Inspector: BARRY STRATTON - Comments: Water clannage
FAIL
R3 - Unfit for Human
Is the structure found to be fit for human occupancy according to the code? (IPMC.
Occupancy
108.1.3)
Inspector: BARRY STRATTON - Comments: MOLD and water damage
FAIL
R6 - Interior Structure
Has the interior of the structure and equipnnent inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: Carpet not secured to floor. Carpet coming
up in several areas of apartment Water damage floors.
FAIL
R6.C. - Mechanical Eqiupment
Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
wiorEa on esrzerzoza c i¢i 3
Page 1 of 2
STATUS CODE
REINSPFMON DATE
OII/31/2020
CONTACT SIGNATURE
DESCRIPTION
Inspector: RARRY STRATTON - Comments: Kitchen faucet needs replaced.
Jogs Foley //" ��
Signed on: 07/29/2020 @ 14:14 / ��
INSPECTOR SIGNATURE
BARRY n: 07/2 /
Signed oon: 7/292020 @ 14:14
QUESTIONS ABOUT YOUR INSPECTION?
EARRY STRATTON
bar Y.Stratton@waterloo-ia.org
(319)231-9147
wmaa o0 oarzsrzozc z ions
Page 2 of 2
REPORTINSPECTION
WATERLOO
DETAILS
Inspection
Date: 07/29/2020
1 Inspection Type:
Rental
Inspection
I Inspection Number: 4628 1 Shift: N/A I Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
NIA
STATUS -CODE DESCRIPTION
FAIL 506.1 -Where required Where access to or within a suvcture or an area is restricted because of secured
openings or where immediate access is necessary for life-saving or fire -fighting
put poses, the fire code official is authorized to require a key box to be installed in an
approved location. The key box shall be of an approved type listed in accordance with
UL 1037, and shall contain keys to gain necessary access as required by the fire code
official.
Inspector: BARRY STRATTON - Comments: Still have not removed old Tracsess knox
boxes.
FAIL 605.1 -Abatement of
Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards
in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Dehumidifiers running sitting on wet
carpet.
FAIL 907.2.11 - Single- and
Listed single- and multiple- station smoke alarms complying with UT 217 shall be
multiple -station smoke
installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: All smoke detectors need to be installed to
code and be in functioning condition.
FAIL 915.1.1 - Where required
Carbon monoxide detection shall be provided in Group I-1, 1-2, 1-4 and R occupancies
and in classrooms in Group E occupancies in the locations specified in Section 915.2
where any of the conditions in Sections 9151.2 through 915.1.6 exist.
Inspector: BARRY STRATTON - Comments:
FAIL R2 - Unsafe Equipment
Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON - Comments: Furnace not working. Plumbing leak in
walls. Floors wet and damage to drywall, carpet, and wood flooring.
Printed on 03/26/2020� 10.i4
Page 1 of 3
STATUS CODE
DESCRIPTION
FAIL
FAIL
FAIL
FAIL
FAIL
R3 -Unfit for Human
Occupancy
R6 -Interior Structure
R6.A. -Interior Sbvcarre-
Unsafe Conditions
R6.B. -Residential Heating
R6.C. -Mechanical Egiupmem
REINSPECTION DATE
08/31/2020
Is the
stiucture found to befit for
human occupancy according to
the code? (IPMC
108.1.3)
Inspector: BARRY STRATTON - Comments: Units 102, 103, 104 are unfit to occupy.
Eecause of the water leaks, and the degree to which the structure/apartments are in
disrepair, lacks maintenance, is insanitary, vermin infested, contains filth, and
contamination. Unit lacks ventilation and other essential equipment required by
code to maintain humidity levels in apartments. These units are a hazard to the
occupants.
Has the interior of
the structure
and equipment inside
been
maintained
in good
repair, structm ally
sound, and in
a sanitary condition?
(IPMC
305)
Inspector: BARRY STRATTON -Comments: Water damaged flooring carpet, walls, all
need REMOVED & REPLACED. Mold growing on walls, closet doors, and all paint
surfaces.
Were any unsafe conditions noted dwing the interior inspection?(IPMC 305.1.1)
Inspector; BARRY STRATTON -Comments: MOLD
Are dvdellings provided with heating facilities capable of maintaining a room
temperature of 68R (IPMC 602.2)
Inspector: BARRY STRATTON -Comments: Have licensed contractor see why furnace
is not functioning.
Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector: EARRY STRATTON -Comments: Plumbing leak somewhere in walls.
Bathroom, 6ec600ms ,kitchen have water damage. Bath fan is missing and needs
replaced. Open wires in wall where fan was.
vrt�rEo 0o asrz�zozo � io rs
Page 2 of 3
CONTACT SIGNATURE
John Foley
Signed on: 07/29/2020 @ 13:48
INS➢ECTOR SIGNATURE
BARRY TON
on: 07
Signed on: 07/29/2020 @ 73:48
QUESTIONS ABOUT YOUR INS➢ECTION7
BARRY STRATTON
bar ry. stra tto n@waterloo-ia. org
(319)231-9147
vn�.aa o� esrzwzum c- io.ia
Page 3 of 3
WATERLOO FIRE RESCUE
INSPECTION REPORT
205 ARGYLE ST. WATERLOO lA 50703 �eAE
DETAILS
Inspection
Date: 07/29/2020
1 Inspection Type:
Rental
Inspection I
Inspection Number: 4630 1 Shift: N/A I Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A
STATUS CODE DESCRIPTION
FAIL 506.1 -Where required Where access to or within a structure or an area is restricted because of secured
openings or where immediate access is necessary for life-saving or fire -fighting
purposes, the fire code official is authorized to require a key box to be installed in an
approved location. The key box shall be of an approved type listed in accordance with
UL 1037, and shall contain keys to gain necessary access as required by the fire code
official.
Inspector. BARRY STRATTON -Comments: Old TYacess Knox boxes still not removed
from building.
FAIL 907.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Smoke detectors needed in each bedroom
and outside of the bedrooms. All cetectors need to be in working/functioning
condition.
FAIL R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON - Comments: MOLD and water clamage floors, carpet and
walls.
FAIL R3 -Unfit for Human Is the structure found to befit for human occupancy according to the code? (IPMC
Occupancy 108,1.3)
Inspector: BARRY STRATTON - Comments: Unit is unfit to occupy in current condition.
MOLD and water clamage. Mice in unit.
FAIL R6 -Interior Structure Has the interior of the suucture and equipment inside been maintained in good
repair, structwally sound, and in a sanitary condition? (IPMC 305)
e,��.- o�esrzwzozo�imis
tl Page 1 of 3
STATUS CODE DESCRIPTION
Inspector: BARRY STRATTON - Comments: Water damage on floors, walls, and carpet.
Remove all water damaged material and replace Front door does not open and is
catching on floor. Furnace cabinet is wet possible condensate line is backed
up/plugged. Wall installed above sink is not fire rated material and wall needs
replaced with drywall. Remove and replace all damaged carpet and wood flooring.
FAIL R6.A. -Interior S[ruc[ure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON - Comments: MOLD
FAIL R6.6. -Residential Heating Are dwellings provided with heating facilities capable of maintaining a room
temperature of 68P (IPMC 602.2)
Inspector: BARRY STRATTON - Conunen[s: Condensate line plugged.
FAIL R6.C. -Mechanical Eyiupment
Are mechanical appliances
properly installed
and maintained in good
working
condition? (R)MC 603,1)
Inspector. EARRY STRATTON -Comments: Kitchen faucet needs replaced. Kitchen
cabinets need replace what have water damage.
REINSPECTION DATE
08/31/2020
CONTACT SIGNATURE
Signed on: 07/29/2020 @ 14;00
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 07/29/2020 @ 14:00 t
Frtn[eU on OS/26/2J20= iG 19
Page 2 of 3
QUESTIONS ABOUT YOUR INSPECTION?
EARRY STRATTON
ba ny.st ratto n@wa to t I oo-ia. org
(319)231-9147
v��, o�esrzerzoze� io:w �m Page 3 of 3
WATERLOO FIRE RESCUE00
INSPECTION REPORT
1012 W DRD Sr. WATERLOO IA 50701 M<.E
DETAILS
Inspection
Date: 07/30/2020
1 Inspection Type:
Rental
inspection
I Inspection Number: 4639 ShifC N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A
STATUS CODE DESCRIPTION
FAIL 1018.1 - General Aisles and aisle accessways serving as a portion of the exit access in the means of
egress system shall comply with the requirements of this section. Aisles or aisle
accessways shall be provided from all occupied portions of the exit access that
contain seats, tables, furnishings, displays and similar fixtures or equipment. The
minimum width of required capacity of aisles shall be unobstructed. Exception:
Encroachments complying with Section 1005.7.
Inspector. BARRY STRATTON -Comments: Obstructions in egress paths, storage of
items in basement.
FAIL 1031.7 -Emergency escape Required emergency escape and rescue openings shall be maintained in accordance
and rescue openings with the code in effect at the time of construction, and the following: Required
emergency escape and rescue openings shall be operational from the inside of the
room without the use of keys or tools. Bars, grilles, grates or similar devices are
allowed to be placed over emergency escape and rescue openings provided the
minimum net clear opening size complies with the code that was in effect at the time
of consu uction and such devices shall be releasable or removable from the inside
without the use of a key, tool or force greater than that which is required for normal
operation of the emergency escape and rescue opening.
Inspector: BARRY STRATTON - Comments: Broken windows, windows not capable of
opening.
FAIL 315.3.2 - Means of egress Combustible materials shall not be stored in exits or encloswes for stairways and
ramps.
Inspector: BARRY STRATTON - Comments: Storage in basement and upper unit. All
storage shall be maintained safe. Large accumulation of items in basement.
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
elecnical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Several extension cords in use and need
removed. Electric switches hanging off walls, outlets missing covers. Elecu is panel in
basement has cover not sn ewed on box. Need 3 IT clearance to electric panels.
vnm.a o� esrzs+zozo �� +oay
Page 1 of 4
STATUS
CODE DESCRIPTION
FAIL
FAIL
FAIL
FAIL
FAIL
906.1 - Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, P,, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of i-A: 10-B: C. 2. Within 30 feet (9144 nvn)
of commercial cooking equipment. 3. In at where flammable or combustible
liquids are stored, used or dispensed. 4. On each floor of structures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1. 6. Special-hazarcl areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector. BARRY STRATTON -Comments: Need fire extinguishers in all units.
907.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Smoke detectors are needed in each
bedroom, outside of the bedrooms and in basement. This is code for both units,
915,1 -General Carbon monoxide detection shall be installed in new buildings in accordance with
Sections 915.1.1 through 915, 6. Carbon monoxide detection shall be installed in
existing buildings in accordance with Section 1103.9.
Inspector: EARRY STRATTON - Conunents: CO detectors are required to be installed in
vicinity of bedrooms in both units.
R7 -Unsafe Structures Is the suuchire found to be dangerous to the life, health, property or safety of either
the public or occupants of the structure? (IPMC 108.1.1)
Inspector: BARRY STRATTON - Comments: Storage, obsh actions in egress paths,
electric issues throughout units/basement
R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON - Comments: Stove has gas leak. Electric outlets hanging
off wall by back door. Romex can not be used in this location. Wire needs to be in
EMT,
v.ora a� esrzsimm � rt. ra
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL R3 -
Unfit for I iuman
Is the structure found
to befit for human occupancy according to
the code? (IPMC
Occupancy
108.1.3)
Inspector: BARRY STRATTON - Comments: Condition of building is unsafe for
occupants. IPMC 108.5 Prohibited Occupancy: Any occupied su uciure condemned
and placarded by the code official shall be vacated as ordered by the code official.
Any person who shall occupy a placarded premises or shall operate placarded
equipment, and any owner or any person responsible for the premises who shall let
anyone occupy a placarced premises or operate placarded equipment shall be liable
for the penalties provided by this code. Units shall be vacated until such time repairs
can be made. Permits shall be obtained by licensed contractors and units will need
inspected before anyone moves back in.
PAIL R4 - Exterior Propel ty Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON - Comments: Debris all over property.
FAIL RS -Exterior SUuctwe Is the exterior of the structure maintained in good repair, snucturally sound and
sanitary state? (IPMC 304)
Inspector: BARRY STRATTON - Comments: Roof, Soffit, & Gutters need attention.
Missing soffit material, roof is rotten and leaking into units.
FAIL R6 -Interior Structure flas the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON -Comments: Missing doa s, holes in walls need repaired,
globes needed on all lights, handrails needed Io upstairs and to basement, bath floor
needs replaced, shower faucet needs replaced, stove needs replaced holes in
ceilings and walls, doorjambs need replaced, door hardware needs replaced.
FAIL R6.A. - Interior Structwe- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON - Comments: Egress paths blocked and storage
throughout units and basement.
FAIL R6.6. -Residential Nearing Are dwellings provided with heating facilities capable of maintaining a room
temperature of 68 F? (IPMC 602.2)
Inspector: BARRY STRATTON -Comments: Need 3 ft clearance around water heater
and boiler.
v,�� a�esrzwzozoc iaia
sEoPage 3 of 4
STATUS CODE
DESCRIPTION
FAIL R6.C. - Mechanical Egiupment
Are mechanical
appliances
properly installed
and maintained in good
working
condition?
(IPMC 603.1)
Inspector: BARRY STRATTON - Comments Need 3 It clearance around water heater
and boiler.
FAIL R6.D. - Receptades Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grounding -type receptacle of a receptacle with a GFCI. Every bathroom shall contain
not less than one receptacle. Any new bathroom receptacle shall have GFCI
protection. All receptacles shall have the appropriate faceplate cover, (IPMC 605.2)
Inspector. BARRY STRATTON - Comments: Licensed electrician needs to make
corrections to electric system of rental units. Several unsafe outlets, electric
extension cords all over basement and upper unit. Outlets not working. Globes
needed on all light fixtures.
RElNSPECTION DATE
08/31/2020
CONTACT SIGNATURE
Stan Shaw
Signed on: 07/30/2020 @ 10:4II M I
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 07/30/2020 @ 10:49
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
b a r ry. s [ra tto n @waterloo -i a. o rg
(319) 231-9147
piincea on 6u'�2E/202� �� I G.IJ
Page 4 of 4
WATERLOO FIRE RESCUE
INSPECTION REPORT
2001 CITY VIEW ST, WATERLOO IA 50703
DETAILS
Inspection
Date: 07/30/2020
1 Inspection Type:
Rental
Inspection
Inspection
Number: 4496 Shift N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors
N/A I Fee:
$50.00
STATUS CODE DESCRIPTION
FAIL 1031.7 -Emergency escape Required emergency escape and rescue openings shall be maintained in accordance
and rescue openings with the code in effect at the time of construction, and the following: Required
emergency escape and rescue openings shall be operational from the inside of the
room without the use of keys or tools. Bars, grilles, grates or similar devices are
allowed to be placed over emergency escape and rescue openings provided the
minimum net clear opening size complies with the code that was in effect at the time
of construction and such devices shall be releasable or removable from the inside
without the use of a key, tool or force greater than that which is required for normal
operation of the emergency escape and rescue opening.
Inspector: BARRY STRATTON - Comments: Back door still blocked by items.
Obstruction to get out of back door. Items on both sides of door.
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments Electric hazards in basement with
flooding/backup. Electric outlet in bathroom and bedroom needs replaced. Exterior
egress lights do not work. Exposed electric wires in basement.
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 nun)
of commercial cooking equipment. 3, In areas where flammable or combustible
liquids are stored, used or dispensed. 4. On each floor of structures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1. 6. Special -hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON - Comments: Need fire extinguisher in unit.
frig. an OS/25/2020 c^^-10:11
��Page 1 of 3
STATUS
I m
FAIL
FAIL
FAIL.
FAIL
FAIL
FAIL
CODE DESCRIPTION
907.2.11 - Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke installed in accordance with Sections 907,2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Smoke detectors needed in each bedroom,
outside bedrooms, and in basement.
916.4-Carbon monoxide Carbon monoxide alarms shall comply with Sections 915.4.1 through 915.4.3.
alarms
Inspector: BARRY STRATTON - Comments: CO detector needs to be in working
condition.
RZ -Unsafe Equiprnent Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON - Comments: Basement flooded Appliances plugged in
sitting in water.
R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON -Comments: Debris around property,
R6 -Interior Structwe Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 306)
Inspector: BARRY STRATTON -Comments: Basement Flooded, front door needs
replaced. Doorjamb and door plate are broken. Vent registers not staying in place.
Mold in basement on walls caused by water in basement. Broken interior doors need
eplaced.
R6.6. -Residential Healing Are dwellings provided with heating facilities capable of maintaining a room
temperatwe of 68F? (IPMC 602.2)
Inspector: BARRY STRATTON -Comments: Registers/vent covers
R6.C. -Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector. BARRY STRATTON -Comments: Water damage in basement may cause
damage for water heater, furnace and other appliances to malfunction.
v.;��:n oa esrzsrzoze ry io: w
Page 2 of 3
STATUS CODE
DESCRIPTION
FAIL R6.D. - Receptacles Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grounding -type receptacle or a receptacle with a GECI. Every bathroom shall contain
not less than one receptacle. Any new bathroom receptacle shall have GECI
protection. All receptacles shall have the appropriate faceplate cover (IPMC 605.2)
REINSPECTION DATE
OS/31/2020
CONTACT SIGNATURE
Dorothy Haugebak
Signed on: 07/30/2020 @ 11:03
INSPECTOR SIGNATURE
BARRY TON
Signed on: on: 0707/30/2020 @ 11:03
QUESTIONS AROUT YOUR INSPECTION?
BARRY STRATTON
ba rry. Stratton @waterloo-ia. org
(319)231-9147
Inspector: BARRY STRATTON -Comments:
N L
trine on Qa'/26ri020 _=1G'.IY
f�Page 3 of 3
WATERLOO FIRE RESCUE
INSPECTION REPORT
1649 CAMELOT DR, WATERLOO IA 50702
DETAILS
Inspection Date: 08/07/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4677 1 Shift: N/A 1 Station: N/A
Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A
STATUS CODE DESCRIPTION
y�A"
FAIL 505.1 - Address identification New and existing buildings shall be provided with approved address identification.
The address identification shall be legible and placed in a position that is visible from
the street or road fronting the property. Address identification characters shall
court ast with their background. Address numbers shall be Arabic numbers or
alphabetical letters. Numbers shall not be spelled out. Each chatacter shall be not
less than 4 inches (102 mm) high with a minimum stroke width of 112 (12.7 min).
Where required by the fire code official, address identification shall be provided in
additional approved locations to facilitate emergency response. Where access is by
means of a private road and the building cannot be viewed from the public way, a
monument, pole or other sign or means shall be used to identify the structure.
Address identification shall be maintained.
Inspector: BARRY STRATTON - Comments: Addresses need to be legible frour street
and all apartment building exterior doors and all interior cloors shall have
identification on all apartment doors.
FAIL 605.1 - Abatement of Identified elecvical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Light switches in both bedrooms need
replaced Have all switches and outlet checked to ensure working acid safe. Water
coming out of outlets and light fixtures.
FAIL 703.2 -Opening protectives Opening protectives shall be maintained in an operative condition in accordance with
NFPA 80. Where allowed by the fire code official, the application of field -applied labels
associated with the maintenance of opening protectives shall follow the
requirements of the approved third -party certification organization accredited for
listing the opening protective. Fire doors and smoke barrier doors shall not be
blocked or obstructed, or otherwise made inoperable. Fusible links shall be replaced
promptly whenever fused or damaged. Fire door assemblies shall not be modified.
Inspector: BARRY STRATTON - Comments: Doors in corridors shall be capable of
closing and latching. Doots also shall fit reasonably in the doorjamb.
FAIL 9DL6.1 -Standards Fire protection systems shall be inspected, tested and maintained in accordance with
the referenced standards listed in Table .
v,�ro 0o earzarzozo c io.w
Page 1 of 3
STATUS CODE
DESCRIPTION -
FAIL
FAIL
FAIL
FAIL
FAIL
Inspector: BARRY STRATTON - Comments: Will need records that the alarm in building
has been in working condition and has had proper maintenance.
9D6.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E, F, H, I, M, R-12 R-21 R-4 and S occupancies. Exception: In
Group R-2 occupancies, per fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 mm)
of commercial cooking equipment. 3. In areas where flammable or combustible
liquids are stored, used or dispensed. 4. On each floor of structures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1. 6. Special -hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON - Comments:
907.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON -Comments: All smoke detectors installed shall be in
or condition, In hallway smoke detector is hanging from ceiling and appears to
have water damage from a leak.
R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON - Comments: Baseboard units.
RS -Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and
sanitary state? (IPMC 304)
Inspector: BARRY STRATTON - Comments: Window screes missing on some windows
and some screens damaged.
R6 - Interior Suucture Has the interior of the struchre and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON -Comments: Water damage to walls and ceilings.
Bathroom, living room, bedrooms have water damage flooring ceilings, &walls.
Peeling and abraded paint will need corrected. Tub tiles coming off tub surround.
Tiles have water damage and will need removed and replaced. Proper wall board
shall be installed to ensure water will not damage surround. Carpets are water
damaged and show signs of mold forming under carpet where carpet pad was
removed. Kitchen floors shall be removed and replaced. All floors shall be maintained
in a clean, sanitary, and good repair, Knockdown plaster is bubbling from water
damage. Remove all water damage and replace. Mold mitigation is needed in unit. 0� CIS
w„rtl zsrzozac 10a4
Page 2 of 3
STATUS CODE
DESCRIPTION
FAIL R6.A. - Interior Structtn e-
Unsafe Conditions
FAIL R6.6.-Residential Heating
FAIL R6.C. -Mechanical Egiupment
REINSPECTION DATF
09/14/2020
CONTACT SIGNATURE
Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Inspector: BARRY STRATTON - Comments: Mold
Are dwellings provided with heating facilities capable of maintaining a room
temperature of 58R (IPMC 602.2)
Inspector: BARRY STRATTON -Comments: Baseboard heating shall be checked and
covers attached as manufactured. Debris is in heating element area and could cause
potential fire hazard.
Are mechanical appliances properly ins[alled and maintained in good waking
condition? (IPMC 603.1)
inspector: BARRY STRATTON -Comments: Baseboard heating and Air conditioner not
installed correctly for unit. Window air installed in P-Tec box in wall. Towels holding AC
n place.
Paramark �/� I�
Signed on: 08/07/2020 @ 10:37 / 1 j-\
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: OS/07/202.0 @ 10:38
QUESTIONS ABOUfi YOUR INSPECTIONT
BARRY STRATTON
b a r ry. s V a tto n @waterloo- i a. o rg
(319)231-9147
wm�Ea o� oan_c�zozo e io: is
Page 3 of 3
WATERLOO FIRE RESCUE
INSPECTION REPORT
402112 WELLINGTON ST. WATERLOO IA 50701
DETAILS
Inspection
Date: 08/10/2020
1 Inspection Type:
Rental
Inspection
I Inspection Number: 4687 1 Shift: N/A ( Station: N/A I
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A
STATUS CODE DESCRIPTION -
FAIL 7010.1.9 - Uoor operations Except as specifically permitted by this section, egress doors shall be readily
openable fiom the egress side without the use of a key or special knowledge or
effort.
Inspector. BARRY STRATTON -Comments: Doors need to be installed and be
functional. Main entrance door to 402 112 is missing molding and not installed in
opening. Screen door is broken and needs replaced.
FAIL 7031.2 -Reliability Required exit accesses, exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire of other
emergency where the building area served by the means of egress is occupied. An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector: BARRY STRATTON - Comments: Rear doors are blocked by weeds and
foliage. Egress path needs to be free h om obstructions. Need to replace rear stairs
on both units.
FAIL 505.1 -Address iden[ificatia� New and existing buildings shall be provided with approved adchess identification.
The address identification shall be legible and placed in a position that is visible from
the street or road fronting the property. Address identification characters shall
contrast with their background. Address numbers shall be At numbers or
alphabetical letters. Numbers shall not be spelled out. Each character shall be not
less than 4 inches (102 ram) high with a minimum stroke width of 1/2 (127 Mill).
Where required by the fire code official, address identification shall be provided in
additional approved locations to facilitate emergency response. Where access is by
means of a private road and the building cannot be viewed from the public way, a
monument, pole or other sign or means shall be used to identify the structure.
Address identification shall be maintained.
Inspector. BARRY STRATTON -Comments: Need numbers on all apartment doors.
Need addresses on building.
a,�o� o�esrzeaozc�m:�a Ea Page 7 of 4
STATUS
CODE DESCRIPTION
FAIL
FAIL
FAIL
FAIL
FAIL
605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible cocle official.
Electrical wiring devices, appliances and other equipment that is modified or
clamaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRA, MN - Comments: Extension cords need to be removed. All
outlets & fixtures need to be in good condition. All lights need to work and have
proper globes.
906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E F, H, E M, R-1, R-2, R-4 and S occupancies, Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-13: C. 2, Within 30 feet (9144 mm)
of commercial cooking equipment. 3. In areas where flammable or combustible
liquids are stored, used or dispensed. 4. On each floor of structures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1.6. Special -hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON -Comments: Need f re extinguishers in all units.
907.2.11 -Single- and Listed single- and multiple -station smoke alarms complying with UL 217 shall be
multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON -Comments: Need smoke detectors in each bedrooms,
outside of the bedrooms, and in basemen[.
915.1.1 -Where required Cathon monoxide detection shall be provided in Group I-1, I-2, I-4 and R ocaipancies
and in classrooms in Group E occupancies in the locations specified in Section 915.2
where any of the conditions in Sections 915.1.2 through 915.1.6 exist.
Inspector: BARRY STRATTON - Comments: Need CO detectors in vicinity of bedrooms.
Rt -Unsafe Struttures Is the structure fowld to be dangerous to the life, health, property or safety of either
the public or occupants of the structure? (IPMC 108.1.1)
Inspector: BARRY STRATTON -Comments: Need handrails installed on all stairs.
v.� - o�earzsimzc� i¢ia
��tlPage 2 of 4
STATUS CODE DESCRIPTION
FAIL R2 - Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON - Comments: Stove plugged in with electric extension
cords. Extension cot cis in use in all units and needs to be removed. Porch supports
are rotten and do not support roof. Porch & supports will need removed and
replaced.
FAIL R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON - Comments: Need to replace roof. Roof is leaking. Front
poach is weak and needs replaced. Front steps are unsafe and need replaced.
FAIL R6 -Interior Structure
Has the interior of
the structure
and equipment inside
been
maintained
in good
repair, structurally
sound, and
in a sanitary condition?
(IPMC
305)
Inspector: BARRY STRATTON -Comments: Replace all broken windows, and picture
windows that are broken. Repair all holes in walls. Basement is flooded by backed up
drain. Sewer stack is leaking in basement. Toilet in upper unit is leaking at base of
toilet. Bathroom window is not installed to code and is not safety glazed. Window in
not approved for this location.
FAIL R6.A. -Interior Structure- Were any unsafe caiditions noted during the interior- inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON -Comments: Ceiling collapsed in kitchen. Extension
cords need removed. All electric outlets and fixtures need to be in function condition.
FAIL R6.C. -Mechanical Egiupment
Are mechanical appliances
properly installed and
maintained in good
working
condition? (IPMC 603.1)
Inspector. BARRY STRATTON -Comments: Water heater is missing cover. Dryer is not
exhausting to thebutside. Dryer is exhausting in basement. Drain in basement is
backed up. Sewer gas in basement.
GENERAL NO iES
BARRY STRATTON - O8/10/2020 @ 1443 9-7-4 9-7-5: Need all tenant information for ALL aparunents under your control turned
into the City Clerk's Office.
Prin[=tl on OS/25/2020� �G.iJ
Page 3 of 4
REINSPECTION DATE
09/15/2020
CONTACT SIGNATURE
LDN Properties LLC
Signed on: 08/10/2020 @ 14:43
fNSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 08/10/2020 @ 14:44
QUESTIONS ABOUT YOUR lNSPECTIONT
BARRY STRATTON
ba ny. strattoii@waterioo-ia.org
(319)231-9147
`V- IL
v���c mze�iu:w zo Page 4 of 4
WATERLOO FIRE RESCUE
INSPECTION REPORT it
2141 LOGAN AVE, WATERLOO IA 50703
DETAILS
Inspection Date: 08/10/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4546 1 Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A
VIOLATIONS
No Violations Found
NEXT INSPECTION DATE
06/09/2023
CONTACT SIGNATURE
Vieth Reality LLC
Signed on: 08/10/2020 @ 10:13
INSPECTOR SIGNATURE
BARRY n: 08/ON
Signed oon: 8/10Q020 @ 10:13
QUESTIONS ABOUfi YOUR INSPECTION?
BARRY STRATTON
ba ny. Stratton @waterloo-ia. o rg
(319) 231-9147
Frir. an OS/2E/3020 e10:15
rfaPage 1 of 1
WATERLOO ► RESCUE
INSPECTION REPORT �a
656W11THST, WATERLOO IAS0701
DETAILS
Inspection
Date: 08/11/2020
1 Inspection Type:
Rental
Inspection
I Inspection
Number: 4553 Shift: N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY SFRATTON
I Other
Inspectors:
N/A I Fee:
$50.00
STATUS -CODE DESCRIPTION
FAIL 1070.19 -Door operations Except as specifically permitted by this section, egress doors shall be readily
openable from the egress side without the use of a key or special knowledge or
effort.
hispector: BARRY STRATTON -Comments: Front doorjamb not seuned to house.
Door still not corrected. Back cloor strike plates still not fixed. All doors shall fit
reasonably in their openings and capable pf providing security and pet forming their
intended function.
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock of fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Outlets not grounded in living room and
kitchen still not repaired.
FAIL R2 - Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON - Comments: Water heater needs discharge tube, No
permits & inspections have been clone since 1 st inspection. Electric outlets have bad
grounds.
FAIL R4 - Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector. BARRY STRATTON -Comments: Drainage into basement.
FAIL R6 -Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
v��, o"esrzwzomc roas �Ea Page 1 of 2
STATUS
CODE DESCRIPTION -
FAIL
FAIL
Inspector: BARRY STRATTON - Comments: Basement has mice and rodent feces in
basement. Foundation walls are leaking and shall be maintained in good condition.
Concrete shall be used to fill cracks not spray foam. Floor in basement has debris and
water leaking up through Floor. Windows shall be capable of opening and dosing.
bathroom window in not safety glazed. Kitchen cabinets have holes and holes in
floors. Walls in basement stairwell need to be maintained free from cracks and holes.
Strike plates and hardware need attention on all doors,
R6.C. -Mechanical Eqiupment
Are mechanical appliances
properly installed and
maintained in good
working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON -Comments: Water heater no permits for installation
and no inspections.
R6. D. -Receptacles Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grouncling-type receptacle or a receptacle with a GFCI. Every bathroom shall contain
not less than one receptacle. Any new bathroom receptacle shall have GFCI
protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2)
Inspector: BARRY STRATTON - Comments: Grounding,
REiNSPECTION DATE
09/15/2020
CONTACT SIGNATURE
Travis Davenport JVt A �
Signed on: 08/11/2020 @ 13:27 ( \ f�
fNSPECTOR SIGNATURE
BARRY STRATTON
Signed on: Oi3/11 /2020 @ 13:21
QUESTIONS ABOUT YOUR INSPECfilON7
BARRY STRATTON
ba rry. Stratton@waterloo-i a. org
(319) 231-9147
a�o- o�esearzoze �ioas
��oPage 2 of 2
WATERLOO FIRE RESC E
INSPECTION REPORT
306JULIE CT, WATERLOO IA 50702
DETAILS
Inspection
Date: 08/13/2020
1 Inspection Type:
Rental
Inspection
I Inspection
Number: 4702 1 Shift N/A I Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A I Fee:
$50.00
STATUS CODE DESCRIPTION
FAIL 906.1 - Where required
Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fine extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-13: C. 2. Within 30 feet (9144 torn)
of commercial cooking equipment. 3. In at where flammable or combustible
liquids are stored, used or dispensed. 4.On each floor Of structures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1.6. Special -hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON - Comments: Fire Extinguishers are needed in each
bedroom.
FAIL 907,2.11 - Single- and
Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke
installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Smoke detectors are needed in each
bedroom, outside of the bedrooms and in basement.
FAIL 915.1 - General
Carbon monoxide detection shall be installed in new buildings in accordance with
Sections 915.1.1 through 915, 6. Carbon monoxide detection shall be installed in
existing buildings in accordance with Section 1103.9.
Inspector: BARRY STRATTON - Comments: CO detectors are needed in vicinity of the
bedrooms.
GENERAL NOTES
BARRY STRATTON -08/13/2020 @ 0700 9-7-4 9-7-5: Landlad license and rental registration is needed for all rental units in
Waterloo. Registration is required every year.
e�,�e o�esrzsrzwo_ m.a <d Page 1 of 2
GENERAL NOTES
BARRY STRATTON - 02/13/2020 @ 07:09 562A.19 Access: The landlord shall not abuse the right of access or use it to harass the
tenant. Except in case of emergency or if it is impracticable to do so, the landlord shall
give the tenant at least twenty-four hours' notice of the landlord's intent to enter and
enter only at reasonable times.
REINSPECfiION DAfiE
09/16/2020
CONTACTS/GNATURE
Thomas8/1 [�L
Signed onn::08/t'/2020 @ 07:13
INSPECTOR SIGNAfiURE
BARRY STRATTON
Signed on: 08/13/2020 @ 07:13
QUEST/ONS ABOUT YOUR INSPECTION?
BARRY STRATTON
ba rry. Stratton@waterloo-i a. o rg
(319)231-9147
Pnn[e9 an 03125/3030 2 iG:15
Page 2 of 2
WATERLOO FIRE RESCUE
INSPECTION REPORT
9625 MT CARMEL DR, WATERLOO /A 50703
DETAILS
Inspection
Date: 08/11/2020
1 Inspection Type:
Rental
Inspection I
Inspection Number: 4692 1 Shift: N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A
STATUS CODE DESCRIPTION
FAIL 605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Extension cords in use and need removed.
FAIL R6 -Interior Structure Has the interior of the structwe and equipment inside peen maintained in good
repair, suuctually sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON -Comments: Ceiling in living morn and dining room area
are cracked and drywall is falling in. Replace all damaged drywall. Mice reported in
At but @ time of inspection no noted mice found. Bugs reported in unit.
Management on site notified of complaint.
FAIL R6.C. -Mechanical Egiupment
Are mechanical appliances
properly
installed and maintained in good
working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON -Comments: Bathroom fan need repaired/replaced. Fan
is very loud and is blowing out debris when turned on.
REINSPECTION DATE
09/16/2020
CONTACT' SIGNATURE
Waterloo Indelible Housing LLC �/ ��
Signed on: 08/11/2020@ 14:00 (�
v,mrea o0 osrzerzoze -�- iae s
Page 1 of 2
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 08/11/2020 @ 14:00
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
ba rty.stra tton@waterloo-ia. org
(319) 231-9147
Prin[fa on 05126/E030 � 1015
Page 2 of 2
WATERLOO FIRE RESCUE
INSPECTION REPORT
162S MT CARMEL DR, WATERLOO IA S0703
DETAILS
Inspection Date: 08/11/2020 1 Inspection Type: Rental Inspection I inspection Number: 4692 1 Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A
STATUS ` CODE DESCRIPTION -
FAIL 605.1 -Abatement of Identified electrical hazards shall he abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Elecu ical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector. BARRY STRATTON - Comments: Extension cords in use and need removed.
FAIL R6 - Interior Structure Has the interior of the structw e and equipment inside been maintained in good
repair, Sit Mint sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: Ceiling in living roorn and dining room area
are packed and drywall is falling in. Replace all damaged drywall. Mice reported in
unit but @ time of inspection no noted mice found. Bugs reported in unit.
Management on site notified of complaint.
FAIL R6.C. - Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON - Comments: Bathroom fan need repaired/replaced. Fan
is very loud and is blowing out debris when turned on.
REINSPECTION DATE
09/16/2020
CONTACT SIGNATURE -`
Waterloo Indelible Housing LLC
Signed on: OS/11/2020 @ 14:00 (� `
Prin(xd on GS/26/2020 ,�-- 10.)5
Page 1 of 2
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 08/11/2020 @ 14:00
QUEST/ONS ABOUT YOUR INSPECTION?
BARRY STRATTON
bar y.stratton@waterloo-ia.org
(319)231-9147
v��o zsrzozo cnuas
�aPage 2 of 2
WATERLOO FIRE RESCUE
INSPECTION REPORT
412 DANE ST, WATERLOO IA 50703
DETAILS
nspection Date: 08/12/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4697 1 Shift: N/A Station: N/A
Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A
STATUS -CODE DESCRIPTION -
FAIL 1031.2 - Reliability Required exit accesses, exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied. An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector: BARRY STRATTON - Comments: Egress paths in unit are obstructecl.
FAIL R4 - Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON - Comments: Garbage, debris, & weeds present.
FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: Closet has been torn up. Drywall removed
& concrete floor removed. Replace drywall with rated wall board that is approved to
retain firewall rating. Replace concrete floor. Possible looking for water leak and work
being done to fix water leak done by an unlicensed contractor.
REINSPECTION DATE
09/77/2020
CONTACT SIGNATURE
John Poley E/ ' VT \�
Signed on: 08/72/2020 @ 10:25
er�c<o o� osrzsizoze e- iooe
Page 1 of 2
INSPECTOR SIGNATURE
BARRY ON
on: 081
Signed on: OS/12/2020 @ 10:25
QUES;IONS ABOUT YOUB iNSPEC;ION?
BARRY STRATTON
bany.sti atton@waterloo-ia.org
(319)231-9147
Grn CSi2WT026 �0:16 �E Page 2 of 2
WATERLOO FIRE RESCUE
INSPECTION REPORT
3719 W 9TN ST, WATERLOO IA 50702
DETAILS
Inspection
Date: 08/12/2020
1 Inspection Type:
Rental
Inspection
I Inspection
Number: 4551 Shift: N/A I Station: N/A i
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A I Fee:
$50.00
STATUS '.CODE DESCRIPTION -
FAIL 1010.1.9 -Door operations Except as specifically pennit[ed by this secTion, egress doors shall be readily
openable from the egress side without the use of a key or special knowledge or
effort.
Inspector: BARRY STRATTON -Comments: Deadbolt still no[ replaced. Key access only
on both sides of door not allowed. Need to install thumb turn style of deadbolt on
or. Need to be done ASAP.
PgIL 906.1 -Where required
Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E, F, H, I, M, R-11 R-21 R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 1043: C. 2. Within 30 feet (9144 turn)
of commercial cooking equipment. 3. In areas where flammable or combustible
liquids are stored, used or dispensed. 4. On each floor of structures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1. 6, Special -hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
Inspector: BARRY STRATTON - Comments: Fire extinguishers still not updated at listed
address. 4/19/2019 Is date on extinguishers.
FAIL R3 - Unfit for Human
Is tie structure found to be fit for human occupancy according to the code? (IPMC
Occupancy
108.1.3)
Inspector: BARRY STRATTON - Comments: Mold. Moisture levels in units are high.
FAIL R4- Exterior Property At
Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON - Comments: Potential for mold to form with wet
damaged ceilings and carpets. Moisture levels in units still reading high 96s..
Repair/replace damage affected at of drywall.
v,�ro 0o esrzsrzozo c ivv
Page 1 of 3
STATUS CODE DESCRIPTION -
FAIL R5 - Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and
sanitary state? (IPMC 304)
Inspector. HARRY STRATTON - Comments:
FAIL R6 -Interior Structure Has the interior 01 the stucture and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON -Comments: Water damage throughout unit # 6. Carpet
damaged with water shall be removed and replaced. Ceilings in bathroom & living
room/kitchen is damaged and needs replaced. Plaster damage from leak. Unit # 7
doorjamb is broken and trim to jamb is not attached at latch plate. Ceiling in unit # 7
kitchen/bath has water damage.
FAIL R6,A. - Inrerior Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON - Comments: Mold
FAIL R6.C. -Mechanical Eqiupment
Are mechanical appliances
properly installed and
maintained in good
working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON -Comments: AC unit in # 6 still does not have control
knobs to operate AC.
GENERAL NOTES
HARRY STRATTON - OS/12/2020 @ 10:10 9-7-6 A (3):
failure
to correct
deficiencies
citations) will be issued to management
company
and/or
landlord.
REINSPECTION DATE
09/15/2020
CONTACT SIGNATURE
R &) Kelly Trust
Signed on: 08/12/2020 @ 10:11 E�1�/p �, �1�
vn�.�Ea o� esrzsrozo c^^- io:v
Page 2 of 3
INSPECTOR SIGNATURE
BARRY STRAITON
Signed on: 08/12/2020 @ 10:11
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
b a r iy, s t ra tto n@ wa to r l o o -i a. o rg
(319)231-9147
a�mro 0o carzarzozc � m.n
Page 3 of 3
WATERLOO FIRE RESCUE
INSPECTION REPORT
428 OAKLAWN AVE, WATERLOO IA $0701
DETAILS
Inspection
Date: 08/24/2020
1 Inspection Type:
Rental
Inspection
I Inspection
Number. 456II Shift: N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
NIA I Fee:
$50.00
STATUS CODE DESCRIPTION
FAIL 1010.1.9 - Door operations Except as specifically permitted by this section, egress doors shall be readily
openable from the egress side without the use of a key or special knowledge or
effort.
hispector: BARRY STRATTON -Comments: Bathroom door does not have suike plates.
FAIL 605.1 -Abatement of
Identified electrical hazards shall be abated. Identifed hazardous electrical conditions
electrical hazards
in permanent wiring shall he brought to the attention of the responsible code official.
Flecu-ical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Bathroom GFCI outlet has grounding
issues. Electric system grounding.
FAIL 907.2.11 - Single- and
Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke
installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Need smoke detectors in each bedroom,
outside of the bedrooms. and in basement.
FAIL R2 - Unsafe Equipment
Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1 -2)
Inspector: BARRY STRATTON - Comments: Windows, window frames, and casings
damaged by water from leaking. Water heater is leaking from base of water heater.
Water heater will need replaced.
FAIL R4 - Exterior Property Areas
Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector. BARRY STRATTON - Comments: Gutters still leaking.
w� o�osrzs�zozo c+o:n
�foPage 1 of 2
STATUS CODE DESCRIPTION
FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: Peeling and abraded paint still needs
corrected. Ceilings nad walls have water damage from roof leak. Need gripable
handrails on basement stairs and back stairs.
FAIL R6.C. -Mechanical Eqiuprnent
Are mechanical appliances
properly installed and maintained
in good
working
condition? (IPMC 503.1)
Inspector. BARRY STRATTON -Comments: Replace Water heater Toilet still has liter
pop bottle in tank.
FAIL R6.D. -Receptacles Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grounding -type receptacle or a receptacle with a GFCL Every bathroom shall contain
not less than one receptacle. Any new bathroom receptacle shall have GFCI
protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2)
Inspector: BARRY STRATTON - Comments:
RE/NSPECfi/ON DAfiE
09/24/2020
CONTACfi S/ONATURE
Hawthorne Rentals
Signed on: 08/24/2020 @ 14:41
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 08/24/2020 @ 14:41
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
b a rrystra tton @waterloo-i a. o rg
(319)231-9147
Ginn (''ol2fi/3020C 10:1>
��Page 2 of 2
WATERLOO (FIRE RECOJ
INSPECT/ON REPORT
5548 SUMMERLAND OR, WATERLOO IA 50701
DETAILS
Inspection
Date: 08/04/2020
1 Inspection Type:
Rental
Inspection
I Inspection Number: 4587 1 Shift: N/A I Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A
VIOLATIONS
No Violations Found
NEXT INSPECTION DATE -
07/22/2023
CONTACT SIGNAfiURE
Troy Luck
Signed on: 08/04/2020 @ 10:45
1NSP£CTOR SIONAfiURE
BARRY ON
Signed on: on: 08/08/04/2020 @ 10:45
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
ba nystratton @waterloo-ia.o rg
(319)231-9147
Pnn[ on 03I26i2020� iG:i)
E�Page i of 1
WATERLOO FIRE RESCUE
INSPECTION REPORT
5548 SUMMERLAND DR, WATERLOO /A 50701
DETAILS
Inspection
Date: 08f04/2020
I Inspection Type:
Rental
Inspection
Inspection Number: 4587 Shift: N/A Station: N/A
Unit: N/A
Lead Inspector:
BARRY StRATTON
I Other
Inspectors:
N/A
VIOLATIONS
No Violations Found
NEXT INSPECTION DATE - -
07/22/2023
CONfiACfi SIGNATURE
Troy Luck
Signed on: 08/04/2020 @ 10:45
INSPECTOR SIGNATURE - -
BARRY STRATTON
Signed on: 08/04/2020 @ 10:45
QUESfi1ONS ABOUT YOVR INSPECfilON7
BARRY STRATTON
b a rry. Stratton @water to o-ia.o rg
(319)231-9147
vr��.ra o� oarzdzom � m.n
Page 1 of 1
WATERLOO FIRE RESCUE
INSPECTION REPORT
314E ARLINGTON ST, WATERLOO IA 50703
DETAILS
Inspection
Date: 08/20/2020
1 Inspection Type:
Rental
inspection
I Inspection Number: 4585 Shift N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A
STATUS -CODE DESCRIPTION
FAIL 605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: 2 open boxes in basement on ceiling need
covers. No electricity supplied to house at time of re -inspection so grounding could
not be checked.
FAIL 9D7211.2 -Groups R-Z, R-3, Single or nnultiple-station smoke alarms shall be installed and maintained in Groups
R-4 and 1-1 R-20 R-31 R-4 and 1-1 regardless of occupant load at all of the following locations: 1. On
the ceiling or wall outside of each separate sleeping area in the immediate vicinity of
bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a
dwelling unit, including basements but not including ciawl spaces and uninhabitable
attics. In dwellings or dwelling units with split levels and without an intervening door
between the adjacent levels, a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is less than one full story
below the upper level.
Inspector: BARRY STRATTON - Comments: Smoke detector is needed in basement.
FAIL R4 - Exterior Property At Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON - Comments: Garbage all over yard from snowing
FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, shvcturally sound and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: Handrails to basement are mounted to
close to wall. Handrail height need to he between 34-38 inches and shall be at least 1
112 inches away from wall. Hand ails ends shall return or terminate back to wall,
Floor at rear door is still soft and wood under is rotten and needs replaced.
FAIL R6.C. - Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
wTnt<o on esrzeizoxo Timis
Pa9e 1 of 2
STATUS .CODE DESCRIPTION
Inspectot: BARRY STRATTON - Comments: Water heater installation still does not have
proper permits & inspections. Inspections required by Plumbing Inspector.
FAIL R6,D. -Receptacles Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grounding -type receptacle or a receptacle with a GFCI. Every bathroom shall contain
not less than one receptacle, Any new bathroom receptacle shall have GFCI
protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2)
Inspector: BARRY STRATTON - Comments: No power supplied to house to check
grounding of outlets.
REINSPECTION DATE
09/21/2020
CONTACT SIGNATURE
CNC Investments ,(p
Signed on: 0II/20202020 @ 10:30 C� 11 / � `t
/NSP£CTOR SIGNATURE
BARRYSTRATTON
Signed on: 08/20/2020 @ 10:30
QUESTIONS ABOUT YOUR /NSPECTION?
BARRY STRATTON
b a r ry. stra tto n@ w a [e r l o o -i a. o rg
(319) 231-9147
an�.cEa on esrzerzoxo e- w:�s
Page 2 of 2
WATERLOO FIRE RESC E
INSPECTION REPORT
412 DANE ST. WATERLOO IA 50703
DETAILS
Inspection
Date: 08/19/2020
1 Inspection
Type:
Rental
Inspection
I Inspection Number: 4723 1 Shift N/A 1 Station: N/A I
Unit: N/A
I Lead Inspector:
BARRY
STRATTON
I Other
Inspectors
N/A
STATUS 'CODE DESCRIPTION
FAIL 1010.L9 -Door operations Except as specifically permitted by this section, egress doors shall be readily
openable from the egress side without the use of a key or special knowledge or
effort.
Inspector: BARRY STRATTON -Comments: Patio door does not lock. Building security:
Doors shall be provided with devices designed to provide security to occupants and
property within. Front door is broken at latch and hardware is not secured in door.
out door will need replaced.
FAIL 9072.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Smoke detectors are needed to be in
working condition.
FAIL 915.1 -General Carbon monoxide detection shall be installed in new buildings in accordance with
Sections 915.1.1 through 915. 6. Carbon monoxide detection shall be installed in
existing buildings in accordance with Section 1103.9.
Inspector: BARRY STRATTON - Comments: CO detectors need to be in working
condition.
FAIL R1 -Unsafe Sttuctures Is the structure found to be dangerous to the life, health, property or safety of either
the public or occupants of the structure? (IPMC 108.1.1)
Inspector: BARRY STRATTON - Comments: Mold
FAIL R2 -Unsafe Equipment Was [he presence of mtsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON - Comments: Kitchen cabinets have fallen off wall.
Kitchen cabinets missing drawer fronts. Kitchen sink base has water damage and
mold forming in cabinet. Water heater pipe penetrations are not fire caulked. No
open penetrations allowed in walls.
Prinrxd on OS/26/2020 �^ iP'.19
Page 1 of 2
STATUS .-.CODE
DESCRIPTION
FAIL R3 - Unfit for Human
Occupancy
FAIL R6 -Interior Structure
FAIL R6.C. -Mechanical EGiupment
REINSPECTION DATE
09/17/2020
CONTACT SIGNATURE
)ohn Foley
Signed on: OS/19/2020 @ 14:49
INSPEC►OR SIGNATURE
BARRY STRATTON
Signed on: 08/19/2020 @ 14:49
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
b a ny. s tra tto n@ wa to r l o o- i a, o rg
(319)231-9147
Is the structure found to befit for human occupancy according to the code? (IPMC
108.1.3)
Inspector: BARRY STRATTON - Comments: No carpet in living room. Carpet needs
removed in dining room and stairs. Carpet needs removed and replaced in areas that
have been water damaged. Walls that have been water damaged will need removed
and replaced. Mold will need mitigated.
Has [he interior of
the structure
and equipment inside
been
maintained
in good
repair, structurally
sound, and in
a sanitary condition?
(IPMC
305)
Inspector: BARRY STRATTON -Comments: No carpet in living room. Carpet in dining
room damage and needs removed and replaced. Kitchen cabinets need replaced.
Drawer fronts missing on cabinets. Carpet is not sanitary. Mold mitigation is needed.
Closet doors need installed in closets that doors have fallen off.
Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON -Comments: Need fire caulk on water heater heater
peneu-ations in mechanical closet.
v���� o�esaerzozo�iooz
ftlPage 2 of 2
WATERLOO FIRE RESCUE
INSPECTION REPORT
1211 LANGLEY RD, WATERLOO IA 50702
DETAILS
Inspection
Date: 08/19/2020
1 Inspection Type:
Rental
Inspection
I Inspection
Number: 4579 1 Shift N/A (Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A I Fee:
$50.00
STATUS CODE DESCRIPTION
FAIL 1018.1 -General Aisles and aisle accessways serving as a potion of the exit access in the means of
egress system shall comply with the requirements of this section. Aisles or aisle
accessways shall be provided from all occupied For of the exit access that
contain seats, tables, furnishings, displays and similar fixtures or equipment. The
minimum width or required capacity of aisles shall be unobstructed. Exception:
Encroachments complying with Section 1005.7.
Inspector: BARRY STRATTON - Comments: Egress path still unsafe from rear of
building.
FAIL 90L6 -Inspection, testing and Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust
maintenance systems, and smoke and heat vents shall be maintained in an operative condition at
all times, and shall be replaced or repaired where defective. Nonrequired fire
protection systems and equipment shall be inspected tested and maintained or
removed.
Inspector: BARRY STRATTON -Comments: Still no records for alarm system in
building.
FAIL 907.2.1 L2 -Groups R-2, R-3, Single ormultiple-station smoke alarms shall be installed and maintained in Groups
R-4 and I-1 R-2, R-3, R-4 and I-1 regardless of occupant load at all of the following locations: 1. On
the ceiling or wall outside of each separate sleeping area in the immediate vicinity of
bedrooms. 2. In each room used for sleeping purposes. 3. In each stay within a
dwelling unit, including basements but not including crawl spaces and uninhabitable
attics. In dwellings or dwelling units with split levels and without an intervening door
between the adjacent levels, a smoke alarm installed on the upper level shall suffice
for the adjacent lower level provided that the lower level is less than one full story
below the upper level.
Inspector: BARRY STRATTON -Comments:
FAIL R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, elearical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON -Comments: Rear stairs, landings, & no handrails on
rear of building.
PriP. on OSl26/2020 (^10:19 �Ea Pege 1 of 3
STATUS CODE
DESCRIPTION
FAIL R4- Extetlor Property At
FAIL RS -Exterior Structure
GENERAL NOTES
BARRY STRATTON - 08/19/2020 @ 10:26
BARRY sTRATTON - OII/19/2020 @ 10:26
REINSPECT/ON DATE
09/16/2020
CONTACT SIGNATURE
Equity Ves[ors LLC
Signed on; 08/19/2020 @ 10:27
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on; 08/19/2020 @ 10:27
Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON -Comments: Rear stairs to 12 plex
Is the exterior of the structure maintained in good repair, structurally sound and
sanitary state? (IPMC 304)
Inspector: BARRY STRATTON -Comments: Every exterior stairway, deck, porch, and
baIrony, and all appurtenances attached thereto, shall be maintained structurally
sound, in good repair, with proper anchorage and capable of supporting the
imposed loads.
Property was notified back in May 20"LO about stairs and on today's date stairs are still
unsafe. Double fee for rental registration has yet to be received by the Clerk's Office.
9-7-6 A(3): Failure to correct deficiencies shall result in municipal citations) being
ssued.
ec��cm o� esrzsizozc �-loos
Page 2 of 3
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
bat ty.st ra tton @waterloo-ia. org
(319)231-9147
Prnre o0 oaiu zozu e- ioa9
Page 3 of 3
WATERLOO FIRE RESCUE
INSPECTION REPORT
713112 RANDOLPH ST. WATERLOO IA 50702
DETAILS
Inspection
Date: 08/20/2020
1 Inspection Type:
Rental
Inspection I
Inspection Number; 4729 Shift: N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors
N/A
STATUS (CODE DESCRIPTION
FAIL 505.1 -Address identification New and existing buildings shall be provided with approved address identification.
The address identification shall be legible and placed in a position that is visible from
the street or road ft on[ing the property. Address identification characters shall
contrast with their background. Address numbers shall be At numbers or
alphabetical letters. Numbers shall not be spelled out. Each character shall be not
less than 4 inches (102 nun) high with a minimum stroke width of 112 (12.7 mm).
Where required by the fire code official, address identification shall be provided in
additional approved locations to facilitate emergency response. Where access is by
means of a private road and the building cannot be viewed from the public way, a
monument, pole or other sign or means shall be used to identify the structure.
Address identification shall be maintained.
Inspector: BARRY STRATTON -Comments: Address is required for rear apartment.
FAIL 605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent witing shall be brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment that is modified or
damaged and constitutes an electrical shock or file hazard shall not he used.
Inspector: BARRY STRATTON - Comments: Need light replaced outside back door with
approved outdoor fixture. Outlet above dryer is not grounded. Open lightfixture in
basement with exposed wires X 2 (in ceiling above washer). Electric panel has open
slots and needs approved slugs. Extension coed running from window AC to outlet
act oss room. Window AC will need direct connection to an outlet.
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E, F, N, I, M, R-1, R-$ R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 mm)
of commercial cooking equipment. 3. In areas where flammable or combustible
liquids are stored, used or dispensed. 4. On each floor of structures under
construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1. 6. Special -hazard areas,
including but not limited to laboratories, computer rooms and generates rooms,
where required by the fit code official.
Inspector: BARRY STRATTON - Comments: Need fire extinguishers in units.
Prin(ee on 4o'/2W302J C 1G'.19
Page 1 of 3
STATUS
CODE DESCRIPTION
FAIL
FAIL
FAIL
FAIL
FAIL
FAIL
FAIL
907.2.11 - Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be
multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Need smoke detectors installed in
bedrooms, outside bedrooms, and in basement.
915.1 -General Carbon monoxide detection shall be installed in new buildings in accordance with
Sections 915.1.1 through 915. 6. Carbon monoxide detection shall be installed in
existing buildings in accordance with Section 1103.9.
Inspector: HARRY STRATTON -Comments CO deteRor is needed in vicinity of the
bedrooms.
R2 -Unsafe Equipment Was [he presence of unsafe equipment noted during the inspection? Equipment may
include boilers, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON -Comments: Rear deck, landing, &stairs need replaced.
Water heater flue has no seal at chimney and installed without permits and
inspections. PVC sewer stack installed in between case without any permits and
inspections.
R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON -Comments: Weed obstruction at rear stairs. Rear deck,
landing &stairs need replaced.
RS -Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and
sanitary state? (IPMC 304)
Inspector: BARRY STRATTON -Comments: Roof needs replaced. Several areas has
exposed underlayment, (tar paper).
R6 -Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair, structwally soun$ and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON -Comments: Peeling paint needs corrected in upper unit
in several areas. Closet has water damage with peeling &abraded paint.
R6.A. - Interim -Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: HARRY STRATTON -Comments: Extension cords and water heater venting.
F/lrce0 on 03/25/2020 3 1019
Page 2 of 3
STATUS CODE DESCRIPTION
FAIL R6.C. - Mechanical Equipment Are mechanical appliances properly installed and maintained in good working
conclition? (IPMC 603.1)
Inspector: BARRY STRATTON -Comments: Water heater in stalled in 2019 did not have
permits & inspections. Water heater flue is not installed in chimney correctly and is
missing seal. PVC pipe installed in between cast pipe.
FAIL R6.D. -Receptacles Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grounding -type receptacle or a receptacle with a GECL Every bathroom shall contain
not less than one receptacle. Any new bathroom receptacle shall have GECI
protection. All receptacles shall have the appropriate faceplate cover. (IPMC 60S.2)
tnspector: BARRY STRATTON -Comments: Grounding required for all outlets.
REINSPFCTION DATE
09/22/2020
CONTACT SIGNATURE
Hagedom Housing LLC
Signed on: 08/20/2020 @ 12:07
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 08/20/2020 @ 12:07
QUESTIONS ABOUT YOUR INSPECTION? -
PARRY STRATTON
ba rry. s[ratton @wa to rloo-i a. o rg
(319)231-9147
v�mao o�carzrzozo� was
Page 3 of 3
WATERLOO FIRE RESCUE �
INSPECTION REPORT M<.E
520 ANKENY ST, WATERLOO fA 50703
DETAILS
Inspection
Date: 08/24/2020
1 Inspection Type:
Rental
Inspection
I Inspection
Number: 4592 1 Shift N/A I Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A I Fee:
$50.00
STATUS '.CODE - DESCRIPTION..` -
FAIL 1010.1.9.4 - 60l[ locks Manually operated flush bolts a surface bolls are not permitted. Exceptions: 1.On
doors not required for egress in individual dwelling units or sleeping units. 2. Where
a pair of doors serves a storage or equipment roost, manually operated edge- or
surface -mounted bolts are permitted on the inactive leaf. 3. Where a pair of doors
serves an occupant load of less than 50 persons in a Group B, F or S occupancy,
manually operated edge- or surface -mounted bolts are per on the inactive
leaf. The inactive leaf shall not contain doorknobs, panic bars or similar operating
hardware. 4. Where a pair of doors serves a Group B, F or S occupancy, manually
operated edge- or surface -mounted bolts are permitted on the inactive leaf provided
such inactive leaf is not needed to meet egress capacity requirements and the
building is equipped throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1. The inactive leaf shall not contain doorknobs, panic bars or
similar operating hardware. 5. Where a pair of doors serves patient care rooms in
Group 1-2 occupancies, self -latching edge- or surface -mounted bolts are permitted on
the inactive leaf provided that the inactive leaf is not needed to meet egress capacity
requirements and the inactive leaf shall not contain doorknobs, panic bars or similar
operating hardware.
Inspector: BARRY STRATTON - Car nments: Latch locks on doors need removed. Doors
now blocked by 2 X 4's on exterior of doors.
FAIL 1031.7 -Emergency escape Required emergency escape and rescue openings shall be maintained in accordance
and rescue openings with the code in effect at the time of construction, and the following: Required
emergency escape and rescue openings shall be operational front the inside of the
room without the use of keys or tools. Bars, grilles, grates or similar devices are
allowed to be placed over emergency escape and rescue openings provided the
minimum net clear opening size complies with the code that was in effect at the time
of construction and such devices shall be releasable or removable fi ont the inside
Without the use of a key, tool or for greater than that which is required for normal
operation of the emergency escape and rescue opening.
Inspector: BARRY STRATTON - Comments: latch locks & doors blocked with 2 X 4's.
vr�ra o�esrzerzozo c-ioaz
Page 1 of 4
STATUS CODE
DESCRIPTION - -
FAIL
FAIL
FAIL
FAIL
FAIL
FAIL
605.1 -Abatement of Identified electrical hazards shall be abated Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment that is modified of
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Outlets in house do not have grounds.
Some outlets have the hot/neutral reversed. Exposed wire still exist on exterior light
at front door.
906.1 -Where required Parable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-13: C. 2. Within 30 feet (9144 nun)
of commercial cooking equipment. 3. In areas where flammable or combustible
liquids are stored, used or dispensed. 4. On each floor of structures under
cons0uction, except Group R-3 occupancies, in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1. 6. Special -hazard areas,
including but not limited to laboratories, computer rooms and generator rooms,
where required by the fire code official.
InspeRor: BARRY STRATTON -Comments: Need updated fire extinguisher in unit.
907.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 277 shall he
multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector: BARRY STRATTON - Comments: Need smoke detectors in each bedroom,
outside bedrooms, and in basement.
915.4 -Carbon monoxide Carbon monoxide alarms shall comply with Sections 915.4.1 through 915.43.
alarms
Inspector: BARRY STRATTON -Comments: CO detector is needed in vicinity of the
bedrooms.
R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This
includes grading and drainage, sidewalks and driveways, weeds, and pest
infestations. (IPMC 302)
Inspector: BARRY STRATTON -Comments: Windows sills and framing rotten. Roof
leaking and gutters need repaired. Broken windows and windows not capable of
opening. Several tubes of roof tar all over property. Several tubes of caulk around
property where window is boarded up.
RS -Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and
sanitary state? (IPMC 304)
vrinzE On eaaarzazo�ioae
Page 2 of 4
STATUS CODE DESCAIPTION - -
htspector: BARRY STRATTON - Comments: Windows, gutters, doors.
FAIL R6 - Interior Structure
Has the intetior of the structure and equipment inside been maintained in good
repair, structurally sound, and in a sanitary condition? (IPMC 305)
Inspector: BARRY STRATTON - Comments: Ceiling has collapsed in bedroom, kitchen,
and back entryway that has still not been repaired/ replaced. Front porch floor is
unstable. Windows are not functional. Doorjambs and hardware to front door needs
replaced The condition of the front door need attention. Bathroom cabinets missing
drawer fronts. Handrail is needed to meet code to basement. Kitchen floor needs
replaced Any wet drywall from ceilings needs removed and replaced Door trim and
jamb to bathroom needs replaced Latch locks need removed. Bedroom doors
broken and need replaced.
FAIL R6.A. - Interior Structure-
Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON - Comments: Cellulose from attic all over house,. Electric
issues, peeling paint, windows, doors, water heater.
FAIL R6.13. - Residential Heating
Ate dwellings provicled with heating facilities capable of maintaining a room
temperahire of 68P (IPMC 602.2)
Inspector: BARRY STRATTON - Comments: Furnace filter
FAIL R6.C. - Mechanical Eqiupment
Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON - Comments: Water heater missing cover and stove is
not in working condition.
FAIL R6.D. - Receptacles
Every habitable space in a dwelling shall contain not less than two separate and
remote receptacle outlets. Every laundry area shall contain not less than one
grounding -type receptacle or a receptacle with a GFCL Every bathroom shall contain
not less than one receptacle. Any new bathroom receptacle shall have GFCI
protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2)
Inspector: BARRY STRATTON - Comments: Grounding issues, and wiring issues.
AEINSPECTION DATE
09/22/2020
v,��.ra o� esrzsrzozo e ioae
Page 3 of A
CONTACT SIGNATURE
LDN Properties LLC
Signed on: 08/24/2020 @ 10:15
INSPECTOR SIGNAfiUFE
6ARRY STRATTON
Signed on: 0812412020 @ 10:15
QUESTIONS ABOUfi YOUR 1NSPECTION7
BARRY STRATTON
b a oy.stra tton@waterloo-i a. o rg
(319) 231-9147
w,� o�esrzsrzomc ioae
E Page 4 of 4
WATERLOO FIRE RES UE
INSPECTION REPORT
725 W STH ST. WATERLOO ►A 50702
DETAILS
Inspection
Date: 08/24/2020
1 Inspection Type:
Rental
Inspection
I Inspection
Number: 4597 Shift: N/A Station: N/A
Unit: N/A
I Lead Inspector:
BARRY STRATTON
I Other
Inspectors:
N/A I Fee:
$50.00
STATUS -CODE DESCRIPTION
FAIL 1010.L9 -Door operations Except as specifically permitted by this section, egress doors shall he readily
operable from the egress side without the use of a key or special knowledge or
effort.
Inspector: BARRY STRATTON -Comments: Rear egress door is now boarded up. Need
alI egress doors to be accessible and capable of being used.
FAIL 605.1 -Abatement of
Identified electrical hazards shall be abated. Identified hazardous elecUical conditions
electrical hazards
in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring devices, appliances and other equipment that is modified or
damaged and constitutes an elect ical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON - Comments: Need service in building to be grounded to
code.
FAIL R2 - Unsafe Equipment
Was the presence of unsafe equipment noted during the inspection? Equipment may
include ballets, heating equipment, elevator, moving stairways, electrical wiring, and
flammable liquid containers. (IPMC 108.1.2)
Inspector: BARRY STRATTON - Comments: Water heater draft flue need to be
changed. Draft hood need to be installed to code and have a continuous rise in
discharge. Need to install discharge tube on water heater.
FAIL R5 - Exterior Structure
Is the exterior of the structure maintained in good repair, structurally sound and
sanitary state? (IPMC 304)
Inspector: BARRY STRATTON - Comments: Need gripable handrails to run the full
length of the stairs. Install handrails at a height of between 34"-38" inches. Handrails
need to be turned back and top and bottom of handrails.
FAIL R6.A. - Interior Structure-
Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON - Comments: Electric
Pr�n. on OSI2fi/2020 G'C iO:'20 «o Page 1 of 2
STATUS CODE DESCRIPTION
FAIL R6.C. - Mechanical Ecliupment Are mechanical appliances properly installed and maintained in good working
condition? (IPMC 603.1)
Inspector: BARRY STRATTON - Comments: Water heater need flue changed to meet
code and install a discharge tube.
REINSPECTION OAfiE
D9124/2.020
CONTACT SIONATURE
Randy Schmidt Signed on: 08/24/2020 @ 14:28 \
INSPECTOR SIGNATURE
BARRY n: 08/2 /
Signed oon: 8/24/2020 @ 14:28