HomeMy WebLinkAboutJuly - August 2020 InspectionsWATERLOO FIRE RESCUE INSPECTION REPORT db Inspection Date: 08/19l2020 I Inspection Type: Rental Inspection Inspection Number: 4579 Shift: N/A Station: N/A Unit: N/A Lead Inspector: BARRY STRATTON I Other Inspectors: N/A Fee: $50.00 STATUS CODE DESCRIPTION - - FAIL 1018.1 -General Aisles and aisle accessways serving as a portion of the exit access in the means of egress system shall comply with the requirements of this section. Aisles or aisle accessways shall be provided from all occupied portions of the exit access that contain seats, tables, furnishings, displays and similar fixtures or equipment. The minimum width or required capacity of aisles shall be unobstructed. Exception: Encroachments complying with Section 1005.7. Inspector: BARRY STRATTON - Comments: Egress path still unsafe from rear of building. FAIL 901.6 -Inspection, testing and Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust maintenance systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. Inspector: BARRY STRATTON -Comments: Still no records for alarm system in building. FAIL 907.2.11.2 -Groups R-2, R-3, Single ormultiple-station smoke alarms shall be installed and maintained in Groups R-4 and I-1 R-2, R-3, R-4 and I-1 regardless of occupant load at all of the following locations: 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. Inspector: BARRY STRATTON -Comments: FAIL R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON -Comments: Rear stairs, landings, & no handrails on rear of building. rnorea a� os¢erzoza @ oesz Page 1 of 3 STATUS CODE DESCRIPTION FAIL R4 - Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON -Comments: Rear stairs to 12 plex FAIL RS -Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and sanitary state? (IPMC 304) Inspector: BARRY STRATTON -Comments: Every exterior stairway, deck, porch, and balcony, and all appurtenances attached thereto, shall be maintained structurally sound, in good repair, with proper anchorage and capable of supporting the imposed loads. GENERAL NOTES BARRY STRATTON - 08/19/2020 @ 10:26 Property was notified back in May 2020 about stairs and on today's date stairs are still unsafe. Double fee for rental registration has yet to be received by the Clerk's Office, BARRY STRATTON - OS/19/2020 @ 10:26 9-7-6 A(3): Failure to correct deficiencies shall result in municipal citations) being ssued. REINSPECTION DATE 09/16/2020 CONTACT SIGNATURE Equity Vestors LLC �/V� �`� Signed on: 08/19/2020 @ 10:27 INSPECTOR SIGNATURE BARRY STRATTON Signed on: 08/19/2020 @ 10:27 Printetl an 08262D20 @ 09:52 Page 2 of 3 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON ba rry.stratton@waterloo-ia.org (319) 231-9147 rnmed oo aerzerzozo @ ossz Page 3 of 3 WATERLOO FIRE RESCUE INSPECTION REPORT �+ 1211 LANGLEY RD, WATERLOO IA 50702 DETAILS - Inspection Date: 07/21/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4578 1 Shift: N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A I Fee: $50.00 STATUS 'CODE 'DESCRIPTION FAIL 7078.1 -General Aisles and aisle accessways serving as a portion of the exit access in [he means of egress system shall comply with the requirements of this section, Aisles or aisle accessways shall be provided from all occupied portions of the exit access that contain seats, tables, furnishings, displays and similar fixtures or equipment. The nlinirnum width or required capacity of aisles shall be unobstructed Exception: Encroachments complying with Section 1005.7. Inspector. BARRY STRATTON - Comments: Egress path from rear of building is unsafe and not to code. FAIL 901.E -Inspection, testingand Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust maintenance systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. htspector: BARRY STRATTON -Comments: Records needed for alarm system in building PAIL 907.2.7 L2-Groups R-2, R-3, Single onnultiple-station smoke alarms shall be installed and maintained in Groups R-4 and I-1 R-2, R-3, R-4 and I-t regardless of occupant load at all of the following locations: 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. 2. In each room used for sleeping purposes. 3. In each stay within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice Lot the adjacent lower level provided that the lower level is less than one full story below the upper level, Inspector: BARRY STRATTON -Comments: FAIL R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (I PMC 108.1.2) Inspector: BARRY STRATTON -Comments: Rear stairs, landings, & no handrails installed. v,�� o�esrzerzozo-co3s9 �a Page 1 of2 STATUS CODE DESCRIPTION FAIL R4 - Exterior PropertyAreas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes gracling and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON -Comments: Rear stairs to 12 plex. FAIL RS -Exterior Structure Is the exterior of the structure maintained in good repair, structurally wuncl and sanitary state? (IPMC 304) Inspector: BARRY sTRATTON -Comments: Every exterior stairway, deck, porch, and balcony, and all appurtenances attached thereto, shall be maintained structurally souncl, in good repair, with property anchorage and capable of supporting the imposed loads. GENERAL NOTES BARRY sTRATTON - 07/21/2020 @ 11:53 Property was notified about violations back in May 2020 and stairs are still unsafe and not constructed to code. Double fee for rental registration still not received by the Clerk's Office. RElNSPECTION DATE 08/19/2020 CONTACT SIGNATURE Equity Vestors ELC �� A1l signed on: 07/212020 @ 11:50 r � 1_ INSPECTOR SIGNATURE BARRY STRATTON Signed on: 07/21/2020 @ 11:50 QUESTIONS ABOUT YOUR lNSPECfilON7 BARRY STRATfON ba ny. stra tton@waterloo-i a.o rg (319) 231-9147 v,��. a�esrzsaaza�nese f2oPage 2 of 2 WATERLOOMOMMITM INSPECTION REPORT DETAILS Inspection Date: 07/21 /2020 I Inspection Type: Rental Inspection Inspection Number: 4584 Shift: N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS CODE ` DESCRIPTION FAIL 1010.1.9 -Door operations Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Inspector: BARRY STRATTON -Comments: Front door has broken windows and screen or is broken and needs replaced. FAIL 605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Kitchen outlets are not grounded. Multi plug adapters in use and need to be removed because they are not allowed. FAIL 906.1 -Where required Portable fire extinguishers shall be installed in ail of the following locations: 1. in new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: in Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 mm) of commercial cooking equipment. 3, in areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1, S. Where required by the sections indicated in Table 906.1, 6. Special -hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector: BARRY STRATTON - Comments: Need a fire extinguisher in unit. P/intetl an 08/262020 eu 10.00 Page t of 3 STATUS Id1i1 FAIL FAIL FAIL FAIL CODE DESCRIPTION 907.2.1 L2 - Groups R-2, R-31 Single or multiple -station smoke alarms shall be installed and maintained in Groups R-4 and 1-1 R-2, R-3, R-4 and 1-1 regardless of occupant load at all of the following locations: 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. Inspector: BARRY STRATTON -Comments: All smoke detectors need to be in working condition. R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON -Comments: Water heater is missing discharge tube. Water heater installed did not have proper permits & inspections. R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON -Comments: Guard railing around front parch is broken and needs replaced. Weeds and garbage. R6 -Interior Structure Has the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON -Comments: Need handrails to basement. Floor at rear door is unstable and needs replaced. Water in basement needs attention. Drain backed up in basement. Kitchen walls have holes in walls and need fixed. Door trim missing on door to dining room and needs replaced. Thermostat needs replaced. Repair all broken glass that is broken. R6.A. -Interior Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1) Unsafe Conditions Inspector: BARRY STRATTON - Comments: Plumbing backup in basement. R6.C. -Mechanical Egiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON -Comments: Water heater missing discharge tube. Bathtub leaking into basement. Printed on 08/26/2020 @ 10:00 Page 2 of 3 STATUS CODE 17#3N7177C77i FAIL R6.13. - Receptacles Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grounding -type receptacle or a receptacle with a GFCI. Every bathroom shall contain not less than one receptacle. Any new bathroom receptacle shall have GFCI protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2) Inspector: BARRY STRATTON - Comments: Electric system has grounding issues that need corrected. REINSPECT/ON DATE 08/19/2020 CONTACT S/fiNATURE CNC Investments LLC Signed on: 07/21/2020 @ 15:36 INSPECTOR 5/6NATURE BARRY STRATTON Signed on: 07/21 /2020 @ 15:36 QUESTIONS AEOUT YOUR INSPECTION? BARRY STRATTON b a rryst ratio n @waterloo-ia. o rg (319) 231-9147 : / V \/A'�_ Printed on OBI]6R020 @ IQW Page 3 of 3 WATERLOO FIRE RESCUE INSPECTION REPORT �a SS48 SUMMERLAND DR, WATERLOO IA 50701 DETAILS Inspection Date: 07/22/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4586 I Shift: N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUSCODE DESCRIPTION FAIL 605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions electrical hazarcis in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiling devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Outlet in mechanical room has hot/neuttal reversed. FAIL R6.D. - Receptades Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grounding -type receptacle or a receptacle with a GFCI. Every bathroom shall contain not less than one receptacle. Any new bathroom receptacle shall have GFCI protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2) Inspector: BARRY STRATTON - Comments: Outlet in mechanical room hot/neutral reversed. REINSPECTION DATE 08/17/2020 CONTACT SIGNATURE Troy Luck �Ra` Signed on: 07/22/2020 @ 10:40 /Y INSPECTOR SIGNATURE BARRY STRATTON Signed on: 07/22/2020 @ 10:40 VriO an 09/26I2020�10:1_> ��Page 1 of 2 QUESTIONS ABOUT YOUR INSPECTION? EARRY STRATTON barry. sttatton @ovate rl o o-i a. o rg (319) 231-9147 v.�. zee waz ��Page 2 of 2 WATERLOO FIRE SC ll INSPECTION REPORT Q,. 520 ANKENY ST. WATERLOO IA S0703 DETAILS Inspection Date: 07/23/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4472 IShift N/A Station: N/A Unit: N/A ( Lead Inspector: BARRY STRATTON I Other Inspectors: N/A I Fee: $50.00 STATUS 'CODE - DESCRIPTION FAIL 1010.7.9.4 -Bolt locks Manually operated flush bolts or surface bolts are not pennit[ed. Exceptions: 1. On (loots not required for egress in individual dwelling units or sleeping units. 2. Where a pair of doors serves a storage or equipment room, manually operated edge- or surface -mounted bolts are permitted on the inactive leaf. 3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F or S occupancy, manually operated edge- or surface -mounted bolts are permitted on the inactive leaf. The inactive leaf shall not contain doorknobs, panic bars or similar operating hat dware.4. Where a pair of doors serves a Group B, F or S occupancy, manually operated edge- or surface -mounted bolts are permitted on the inactive leaf provided such inactive leaf is not needed to meet egress capacity requirements and the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The inactive leaf shall not contain doorknobs, panic bars of - similar operating hardware. 5. Where a pair of doors serves patient care rooms in Gcup 1-2 occupancies, self -latching edge- or Solface-mounted bolts are permitted on the inactive leaf provided that the inactive leaf is not needed to meet egress capacity requirements and the inactive leaf shall not contain doorknobs, panic bars or similar operating hardware. Inspector: BARRY STRATTON - Comments: Latch locks on doors need removed. FAIL 1031.7 - 6nergency escape Required emergency escape and rescue openings shall be maintained in accordance and resare openings with the code in effect at the tinne of construction, and the following: Required emergency escape and rescue openings shall be operational from the inside of the room without the use of keys or tools. Bars, grilles, grates or similar devices are allowed to be placed over emergency escape and rescue openings provided the mininnurn net clear opening size complies with the code that was in effect at the time Of construction and such devices shall be releasable or removable from the inside without the use of a key, tool or force greater than that which is required for normal operation of the emergency escape and rescue opening. Inspector: BARRY STRATTON - Comments: Latch locks on doors need removed. FAIL 605.1 - Abatement of Identified elecuical hazards shall be abated. Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code offcial. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Outlets in house do not have grounds. Some outlets have the hot/neutral reversed. Exposed wires on porch were light is missing. v,i"zfOo"oarz5rzozoEio_iz Page t of 4 STATUS CODE DESCRIPTION FAIL FAIL FAIL FAIL FAIL FAIL 906.1 -Whet e required For fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, Be E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 1B-B: C. 2. Within 30 feet (9144 mm) of commercial cooking equipment 3, In at where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1. 6, Special -hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector: BARRY STRATTON -Comments; Need updated fire extinguisher in unit. 907.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be nutltiple-station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72, alarms Inspector: BARRY STRATTON - Comments: Need smoke detectors in each bedroom, outside becitcorns, and in basement. 915.4 -Carbon monoxide Carbon monoxide alarms shall comply with Sections 915.4.1 through 915.4.3, alarms Inspector. BARRY STRATTON -Comments CO detector is needed in vicinity of the bedrooms. R4 -Exterior Property Areas Is [he exterior property area maintained in a clean, safe, and sanitary condition?This includes grading and dtainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON -Comments: Window sills and framing is rotten and need replaced. Roof leaking and gutters need attention. Broken windows, windows not capable of opening. RS - ExteriaStructwe Is the exterior of the structure maintained in good repair, structurally sound and sanitary state? (IPMC 304) Inspector. BARRY STRATTON -Comments: Windows, gutters, &doors. RG -Interior Structure Has the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) e��c oo csrz�rzom r�io.iz E Page 2 of 4 STATUS CODE DESCRIMON Inspector: BARRY STRATTON - Comments: Ceiling has collapsed in bechoom. kitchen, and back entryway that is still not repaired/replaced. Front porch floor is unstable. Windows are not functional and do not open in house. Doorjamb and hardware to front door needs replaced. The condition of the h on[ door needs attention. bativoom cabinets missing drawer fronts. Handrail is needed to Bleed code to basement. Kitchen floor needs replaced. Any wet drywall from ceilings needs removed and replaced. Door trim and jamb to bathroom needs replaced. Latch locks need removed. Bedroom doors broken and need replaced. FAIL R6.A. - Interior Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1) Unsafe Conditions Inspector: BARRY STRATTON - Comments: Cellulose from attic all over house. Electric issues. peeling paint, windows. doors, water heater. FAIL R6.B. - Residential Heating Are dwellings provided with heating facilities capable of maintaining a room temperature of 68P (IPMC 602.2) Inspector: BARRY STRATTON - Comments: Furnace filter FAIL R6.C. - Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON - Comments: Water heater missing cover. Stove is not in working condition. FAIL R6.D. - Receptacles Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grounding -type receptacle or a receptacle with a GFCI. Every bativoom shall contain not less than one receptacle. Any new bathroom receptacle shall have GFCI protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2) Inspector. BARRY STRATTON - Comments: Grounding issues, and wiring issues. REINSPECTION DATE 08/24/2020 CONTACT SIGNATURE LDN Properties LLC Signed on: 07/23/2020 @ 09:21 / v,mra oo es¢erzoze _ inrz Page 3 of 4 INSPECTOR SIGNATURE EARRY ON on: 07/ Signed on: 07/23/2020 @ 09:21 QUESTIONS ABOUT YOUR INSPECTION? EARRY STRATTON ba ny. stra tton@waterloo-i a. org (319) 231-9147 Pn� on OB/2E/E026 �r 1012 Page 4 of 4 / m#r , WATERLOOINSPECTION REPORT IA 50703 DETAILS Inspection Date: 07/23/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4472 1Shift: N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A I Fee: $50.00 STATUSCODE - DESCRIPTION FAIL 1010.1.9.4 -Bolt locks Manually operated flush bolts or surface bolts are no[ permitted. Exceptions: 1. On cloors not required for egress in individual dwelling units or sleeping units. 2. Where a pair of doors serves a storage or equipment room, manually operated edge- or surface -mounted bolts are permitted on the inactive leaf. 3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F or S occupancy, manually operated edge- or surface -mounted bolts are permitted on the inactive leaf. The inactive leaf shall not contain doorknobs, panic bars or similar operating hardware. 4. Where a pair of doors serves a Group B, F or S occupancy, manually operated edge- or surface -mounted bolts are permitted on the inactive leaf provided such inactive leaf is not needed to meet egress capacity requirements and the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The inactive leaf shall not contain doorknobs, panic bars or similar operating hardware. 5. Where a pair of door s serves patient care rooms in Group 1-2 occupancies, self latching edge- or surface -mounted bolts are permitted on the inactive leaf provided that the inactive leaf is not needed to meet egress capacity requirements and the inactive leaf shall not contain doorknobs, panic bars or similar operating hardware. Inspector: BARRY STRATTON - Comments: Latch locks on doors need removed. FAIL 1031.7 -Emergency escape Required emergency escape and rescue openings shall he maintained in accordance and rescue openings with the code in effect at the time of construction, and the following: Required emergency escape and rescue openings shall be operational from the inside of the room without the use of keys or tools. Bars, grilles, grates or similar devices are allowed to be placed over emergency escape and rescue openings provided the minimum net dear opening size complies with the code that was in effect at the time Of construction and such devices shall be releasable or removable from the inside without the use of a key, tool or for greater than that which is required for normal operation of the emergency escape and rescue opening. Inspector: BARRY STRATTON - Comments: Latch locks on doors need removed. PAIL 605.1 - Abatement of Identified elecuical hazards shall be abated. Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Outlets in house do not have grounds. Some outlets have the hot/neutral reversed. Exposed wiles on porch were light is missing. v,ipaa on esrzsrzozo e- m:a Page 1 of 4 STATUS CODE DESCRIPTION FAIL FAIL FAIL FAIL FAIL FAIL 906.1 - Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 nun) of commercial cooking equipment 3, In at where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1. 6. Special -hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector: BARRY STRATTON -Comments: Need updated fire extinguisher in unit. 9D7.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Need smoke detectors in each bedroom, outside bedrooms, and in basement. 915.4 -Carbon monoxide Carbon monoxide alarms shall comply with Sections 915.4.1 through 975.43. alarms Inspector: BARRY STRATTON -Comments CO detector is needed in vicinity of the bedrooms. R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations- (IPMC 302) Inspector. BARRY STRATTON -Comments: Window sills and framing is rotten and need replaced. Roof leaking and gutters need attention. Broken windows, windows not capable of opening. RS - Exterior Structure Is the exterior of the structw-e maintained in goad repair, strucriirally sound and sanitary state? (IPMC 304) Inspector: BARRY STRATTON -Comments: Windows, gutters, & doors. R6 -Interior- Structure Has the interior of the struc[tu-e and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Grin on 06/25R020�1012 Page 2 of 4 STATUS CODE DESCRIPTION Inspector: BARRY STRATTON - Comments: Ceiling has collapsed in bedroom. kitchen, and back entryway that is still not repairedheplaced. Font porch floor is unstable. Windows are notfunctional and do not open in house. Doorjamb and hardware to front door needs replaced. The condition of the front door needs attention. bathroom cabinets missing drawer fronts. Handrail is needed to meed code to basement. Kitchen floor needs replaced. Any wet drywall from ceilings needs removed and replaced. Door trim and jamb to bathroom needs replaced Latch locks need removed. Bedroom doors broken and need replaced. FAIL R6.A. - Interior Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1) Unsafe Conditions Inspector: BARRY STRATTON - Comments: Cellulose from attic all over house- Electric issues. peeling paint, windows. doors, water heater. FAIL R6.B. - Residential Heating Are dwellings provided with heating facilities capable of maintaining a room temperature of 68F? (IPMC 602.2) Inspector: BARRY STRATTON - Comments: Furnace filter FAIL R6.C. -Mechanical Egiupmeni Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON - Comments: Water heater missing cover. Stove is not in working condition. FAIL R6,13. - Receptacles Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grounding -type receptacle or a receptacle with a GFCI. Every ha[hroom shall contain not less than one receptacle. Any new bathroom receptacle shall have GFCI Ell otection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2) Inspector: BARRY STRATTON - Comments: Grounding issues, and wiring issues. REINSPECTION DATE oa/zn/zozo CONTACT SIGNATURE LDN Properties LLC Signed on: 07/23/2020 @ 09:21 �II Print on GS25ri020� iG.�2 xtlPage 3 of 4 INSPECTOR SIGNATURE BARRY on: ATFON 07/2 Signed on: 07/2312020 @ 09:21 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON ba rry. s n-a tton@waterloo-i a.o rg (319) 231-9147 a�= oo asr�zozc�iciz Page 4 of 4 WATERLOO FIRE RESCUEINSPECTION REPORT WATERLOO IA 50702 DETAILS Inspection Date: 07/23/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4596 1 Shift: N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS `CODE MCRIPTION FAIL 1010.1.9 -Door operations Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Inspector: BARRY STRATTON -Comments: All doors shall he openable and capable of preforming their intended function. All doors shall have proper hardware installecl on doors. Screen/front door at front entrance has broken threshold. Door to out of back of unit can not be locked and must remain open for egress purposes. FAIL 5D5.1 -Address identification New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be At numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 4 inches (102 run) high with a minimum stroke width of 112 (12.7 mrn). Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address identification shall be maintained. lospector: BARRY STRATTON - Comments: Aparunents are not numbered. FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identifed hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code offcial. Electrical wiring, devices, appliances and other equipment that is modified or clamaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Outlets in several rooms have grounding issues. Some outlets do not work. Extension cords need to be removed. Multi adapters also need to be removed. Bathroom light has open sockets and needs replaced. Outlet on porch is pulling out of wall and is not grounded, v+�� o�osrzwzozcc �m�s cEePage i of 4 STATUS CODE DESCRIPTION - FAIL FAIL Iy=111 FAIL FAIL FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E, F, H, I, M, R-11 R-21 R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 nmn) of commercial cooking equipment. 3. In areas where flammable or combustible liquicls are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1.6. Special -hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector: BARRY STRATTON -Comments: Need fire extinguishers in all units. 907.2.11.2 -Groups R-2, R-3, Single ormultiple-station smoke alarms shall be installed and maintained in Groups R-4 and 1-1 R-2, R-3, R-4 and 1-1 regardless of occupant load at all of the following locations: 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. Inspector: BARRY STRATTON -Comments: Smoke detectors are needed in each bedI oom, outside of the bedrooms, and in basement. 975.1.1 -Where required Carbon monoxide detection shall be provided in Group I-1, I-2, I-4 and R occupancies and in classrooms in Group E occupancies in the locations specified in Section 915.2 where any of the conditions in Sections 915,1,2 through 915.1.6 exist. Inspector: BARRY STRATTON -Comments: CO detectors are needed in vicinity of any room used for sleeping purposes. R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON -Comments: Gas Leak at stove R5 -Exterior- Structure Is the exterior of the structure maintained in good repair, structurally sound and sanitary state? (IPMC 304) Inspector: BARRY STRATTON -Comments: Need gripable handrails on all stairs to units. R6 -Interior Structure Has the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Ptirtcd aii osnV2o2o.o w:a Page 2 of 4 STATUS CODE ` DESCRIPTION Inspector: BARRY STRATTON - Comments: Floors shall be maintained in good condition. Several areas have large holes that give potential for somebody to fall into basement Vent registers shall be maintained in good condition and be in place over gravity fed grates. Windows shall be capable of being opened and closed. Broken windows shall be replaced. Ceilings in unit need to be maintained in good condition. Ceilings appear to have water damage from some type of leak. Kitchen cabinets shall be in good condition. Under sink cabinet is decayed and cabinet needs replaced. Transition strips are needed to be in place between rooms/hallways. Bed bug infestation in building. Contact exterminator to do pest control on building. FAIL R6.A. -Interior Structure- Were any w�safe conditions noted during the interim inspection?(IPMC 305.1,1) Unsafe Conditions Inspector: BARRY STRATTON - Comments: Electric issues, gas leak FAIL R6.B. - Residential Heating Are dwellings provided with heating facilities capable of maintaining a room temperature of 68F7 (IPMC 602.2) Inspector: BARRY STRATTON - Comments: Floor- registers need to be in place. Gravity air registers need to be in good condition and in place. FAIL R6.C. - Mechanical Eyiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON - Comments: Stove has gas leak. Toilet is leaking in unit. FAIL R&D. - Receptacles Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grounding -type receptacle or a receptacle with a GFCI. Every bathroom shall contain not less than one receptacle. Any new bathroom receptacle shall have GFCI protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2) Inspector: BARRY STRATTON - Comments: Outlets in unit are not grounded and some pulling out of wall. Need licensed electrician to make repairs and have inspected. REINSPECfiION DAfiE 08/24/2020 CONTACT SIGNATURE Randy Schmidt M �� Signed on: 07/23/2020 @ 13:58 l \ v��.ra an asrzerzazo c- io: i3 Page 3 of 4 INSPECTOR SIGNATURE BARRY ON on: 07/ Signed on: 07/23/2020 @ 1359 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON b a try. st ra tton @water) oo-ia.o rg (319)231-9147 Pnnc on 09I25�E020 C10 13 E Page 4 of 4 WATERLOO FIRE RESCUEPo{ INSPECTION REPORT h 907 DOWNING AVE, WATERLOO IA 50701 DETAILS Inspection Date: 07/27/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4461 Shift: N/A Station: N(A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors N/A I Fee: $50.00 STATUS CODE - DESCRIPTION FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E, F, H, I, MIR-1, R-2, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a mininwtn rating of 1-A: 10-13: C. 2. Within 30 feet (9144 tutu) of commercial cooking equipment. 3. In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of St JCtures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1.6. Special -hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector: BARRY STRATTON - Comments: Need Fire Extinguisher in unit. FAIL 907.2.11 - Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Smoke detectors installed per code are located in all bedrooms, outside bedrooms, and in basement FAIL 915A - Carbon monoxide Carbon monoxide alarms shall comply with Sections 915.4.1 through 915.4.3. alarms Inspector: BARRY STRATTON - Comments: FAIL R4 - Exterior Property At Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON - Comments: Debris and nailer parked in rear yarcl. FAIL R5 - Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and sanitary state? (IPMC 304) v,�� oo usrzs�zoze 2^-ma3 �fePage 1 of 3 STATUS CODE DESCRIPTION Inspector: BARRY STRATTON - Comments: Peeling paint, front and rear doors not weather tight and should be replaced, front steps still not to code, broken windows, & soffits still not repaired, FAIL R6 -Interior SUuchire Has the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON - Comments: Basement window needs replaced. Wood and foam in place now and this installation is not an approved window covering. FAIL R6.C. -Mechanical Egiuprnent Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON -Comments: Water heater draft hood need secured to water heater. Dryer exhaust need to exhaust to the exterior of the house. GENERA! NOTES BARRY STRATTON-07/27l2020 @ 12:22 47-4 9-7-5; 2020 rental registration still not filed with the City of Waterloo. BARRY STRATTON - 07/27/2020 @ 12:24 9-7-6 A (3): Failure to correR defciencies the Ciry of Waterloo will issue citation (s) for all noted violation. BARRY STRATTON - 07/27/2020 @ 12:25 IPMC 108.5 Prohibi[ed Occupancy: Unit shall not he occupied/rented un[il all violations are f xed. REINSPECTION DATE OII/26/2020 CONTACT SIGNATURE Nihacl Masic /� � r I Signed on: 07/27/2020 @ 12:25 � 1Vf \VJ\ ` Pnn[x0 an OS/35/2026 � �G:13 Page 2 of 3 INSPECTOR SIGNATURE BARRY STRATTON Signed on: 07/27/2020 @ 12:25 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON batty.st i atton@oratetloo-ia.otg (319)231-9147 e��. o�eaawmze z-imis E�Page 3 of 3 11ATERL00 FIRE RESCAC INSPECTION REPORT DETAILS Inspection Date: 07/28/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4615 Shift: N/A Statimt: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A VIOLATIONS No Violations Found GENERAL NOTES BARRY STRATTON - 07/282020 @ 10:39 Superior Pire 8/2019 extinguishers NEXfi INSPECfiION DATE 07/282023 CONTACfi SIGNATURE Premier Waterloo IA LLC Signed on: 07/28/2020 @ 10:39 INSPECTOR SIGNATURE BARRY STRATTON Signed on: 07l28/2020 @ 10:39 QUESTIONS ABOUT YOUR /NSPECTlON7 BARRY STRA.TTON b a rry, stra t[on @waterloo-i a.o rg (319) 231-9147 Print on 0d/26/2024�10_i3 �a Page 1 of 1 WATERLOO FIR E � °° INSPECTION REPORT ..�" 205 ARGYLE ST, WATERLOO IA 50703 DETAILS Inspection Date: 07/29/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4632 1 Shift: N/A I Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS CODE DESCRIPTION FAIL 506.1 -Where required Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire -fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official. Inspector: BARRY STRATTON - Comments: Old Ti acess still not removed from building. FAIL 907.2,11 - Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Smoke detectors need to be installed and functioning to code. FAIL R2 - Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON - Comments: Plumbing leaks wet and peeling paint, carpet wet wall in closet needs closed up with drywall. FAIL R3 - Unfit for Human Is the structure found to be fit for human occupancy according to the code? (IPMC Occupancy 108.1.3) Inspector: BARRY STRATTON - Comments: Water damaged carpet, drywall, and wood flooring. All needs removed and replaced. FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON - Comments: MOLD in sink and bath cabinets. Water damage carpet, flooring, and walls. Fire wall in closet need holes closed up with drywall. Prinretl on Q8/26R0]0 L^� iG:l3 Page 1 of 2 STATUS CODE DESCRIPTION FAIL R6.A. - Interior Structure- Were any unsafe conditions noted during the intedor inspection?(IPMC 305.1.1) Unsafe Conditions Inspector: BARRY STRATTON - Comments: MOLD FAIL R6.C. -Mechanical Egiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON - Comments: Plumbing leaks, wet floors, wet carpet, REINSPECTION DATE 08/31/2020 CONTACT SIGNATURE John Foley Signed on: 07/29/2020 @ 14:08 INSPECTOR SIGNATURE BARRY STRATTON Signed on: 07/29/2020 @ 14:08 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON Lai ry.stratton@waterloo-ia.org (319)231-9147 N�A IV� eoo- z�izozoe io_ie ��oPage 2 of 2 WATERLOO /RESCUE INSPECTION REPORT 205 ARGYLE ST, WATERLOO /A 50703 DETAILS Inspection Date: 07/29/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4634 1 Shift: N/A I Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS 'CODE DESCRIPTION '. PAIL 506.1 -Where required Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire -fighting Pill poses, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UT 1037, and shall contain keys to gain necessary access as required by the fire code official. Inspector: BARRY STRATTON - Comments: Old Tracess Knox boxes still not removed from building. FAIL 907.2.11 - Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Smoke detectors need to he installed and functioning to code. FAIL Rt - Unsafe Structures Is the structure found to be clangerous to the life, health, property or safety of either the public or occupants of the structure? (IPMC 108.1.1) Inspector: BARRY STRATTON - Comments: Water clannage FAIL R3 - Unfit for Human Is the structure found to be fit for human occupancy according to the code? (IPMC. Occupancy 108.1.3) Inspector: BARRY STRATTON - Comments: MOLD and water damage FAIL R6 - Interior Structure Has the interior of the structure and equipnnent inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON - Comments: Carpet not secured to floor. Carpet coming up in several areas of apartment Water damage floors. FAIL R6.C. - Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) wiorEa on esrzerzoza c i¢i 3 Page 1 of 2 STATUS CODE REINSPFMON DATE OII/31/2020 CONTACT SIGNATURE DESCRIPTION Inspector: RARRY STRATTON - Comments: Kitchen faucet needs replaced. Jogs Foley //" �� Signed on: 07/29/2020 @ 14:14 / �� INSPECTOR SIGNATURE BARRY n: 07/2 / Signed oon: 7/292020 @ 14:14 QUESTIONS ABOUT YOUR INSPECTION? EARRY STRATTON bar Y.Stratton@waterloo-ia.org (319)231-9147 wmaa o0 oarzsrzozc z ions Page 2 of 2 REPORTINSPECTION WATERLOO DETAILS Inspection Date: 07/29/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4628 1 Shift: N/A I Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: NIA STATUS -CODE DESCRIPTION FAIL 506.1 -Where required Where access to or within a suvcture or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire -fighting put poses, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official. Inspector: BARRY STRATTON - Comments: Still have not removed old Tracsess knox boxes. FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Dehumidifiers running sitting on wet carpet. FAIL 907.2.11 - Single- and Listed single- and multiple- station smoke alarms complying with UT 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: All smoke detectors need to be installed to code and be in functioning condition. FAIL 915.1.1 - Where required Carbon monoxide detection shall be provided in Group I-1, 1-2, 1-4 and R occupancies and in classrooms in Group E occupancies in the locations specified in Section 915.2 where any of the conditions in Sections 9151.2 through 915.1.6 exist. Inspector: BARRY STRATTON - Comments: FAIL R2 - Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON - Comments: Furnace not working. Plumbing leak in walls. Floors wet and damage to drywall, carpet, and wood flooring. Printed on 03/26/2020� 10.i4 Page 1 of 3 STATUS CODE DESCRIPTION FAIL FAIL FAIL FAIL FAIL R3 -Unfit for Human Occupancy R6 -Interior Structure R6.A. -Interior Sbvcarre- Unsafe Conditions R6.B. -Residential Heating R6.C. -Mechanical Egiupmem REINSPECTION DATE 08/31/2020 Is the stiucture found to befit for human occupancy according to the code? (IPMC 108.1.3) Inspector: BARRY STRATTON - Comments: Units 102, 103, 104 are unfit to occupy. Eecause of the water leaks, and the degree to which the structure/apartments are in disrepair, lacks maintenance, is insanitary, vermin infested, contains filth, and contamination. Unit lacks ventilation and other essential equipment required by code to maintain humidity levels in apartments. These units are a hazard to the occupants. Has the interior of the structure and equipment inside been maintained in good repair, structm ally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON -Comments: Water damaged flooring carpet, walls, all need REMOVED & REPLACED. Mold growing on walls, closet doors, and all paint surfaces. Were any unsafe conditions noted dwing the interior inspection?(IPMC 305.1.1) Inspector; BARRY STRATTON -Comments: MOLD Are dvdellings provided with heating facilities capable of maintaining a room temperature of 68R (IPMC 602.2) Inspector: BARRY STRATTON -Comments: Have licensed contractor see why furnace is not functioning. Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: EARRY STRATTON -Comments: Plumbing leak somewhere in walls. Bathroom, 6ec600ms ,kitchen have water damage. Bath fan is missing and needs replaced. Open wires in wall where fan was. vrt�rEo 0o asrz�zozo � io rs Page 2 of 3 CONTACT SIGNATURE John Foley Signed on: 07/29/2020 @ 13:48 INS➢ECTOR SIGNATURE BARRY TON on: 07 Signed on: 07/29/2020 @ 73:48 QUESTIONS ABOUT YOUR INS➢ECTION7 BARRY STRATTON bar ry. stra tto n@waterloo-ia. org (319)231-9147 vn�.aa o� esrzwzum c- io.ia Page 3 of 3 WATERLOO FIRE RESCUE INSPECTION REPORT 205 ARGYLE ST. WATERLOO lA 50703 �eAE DETAILS Inspection Date: 07/29/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4630 1 Shift: N/A I Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS CODE DESCRIPTION FAIL 506.1 -Where required Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire -fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official. Inspector. BARRY STRATTON -Comments: Old TYacess Knox boxes still not removed from building. FAIL 907.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Smoke detectors needed in each bedroom and outside of the bedrooms. All cetectors need to be in working/functioning condition. FAIL R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON - Comments: MOLD and water clamage floors, carpet and walls. FAIL R3 -Unfit for Human Is the structure found to befit for human occupancy according to the code? (IPMC Occupancy 108,1.3) Inspector: BARRY STRATTON - Comments: Unit is unfit to occupy in current condition. MOLD and water clamage. Mice in unit. FAIL R6 -Interior Structure Has the interior of the suucture and equipment inside been maintained in good repair, structwally sound, and in a sanitary condition? (IPMC 305) e,��.- o�esrzwzozo�imis tl Page 1 of 3 STATUS CODE DESCRIPTION Inspector: BARRY STRATTON - Comments: Water damage on floors, walls, and carpet. Remove all water damaged material and replace Front door does not open and is catching on floor. Furnace cabinet is wet possible condensate line is backed up/plugged. Wall installed above sink is not fire rated material and wall needs replaced with drywall. Remove and replace all damaged carpet and wood flooring. FAIL R6.A. -Interior S[ruc[ure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1) Unsafe Conditions Inspector: BARRY STRATTON - Comments: MOLD FAIL R6.6. -Residential Heating Are dwellings provided with heating facilities capable of maintaining a room temperature of 68P (IPMC 602.2) Inspector: BARRY STRATTON - Conunen[s: Condensate line plugged. FAIL R6.C. -Mechanical Eyiupment Are mechanical appliances properly installed and maintained in good working condition? (R)MC 603,1) Inspector. EARRY STRATTON -Comments: Kitchen faucet needs replaced. Kitchen cabinets need replace what have water damage. REINSPECTION DATE 08/31/2020 CONTACT SIGNATURE Signed on: 07/29/2020 @ 14;00 INSPECTOR SIGNATURE BARRY STRATTON Signed on: 07/29/2020 @ 14:00 t Frtn[eU on OS/26/2J20= iG 19 Page 2 of 3 QUESTIONS ABOUT YOUR INSPECTION? EARRY STRATTON ba ny.st ratto n@wa to t I oo-ia. org (319)231-9147 v��, o�esrzerzoze� io:w �m Page 3 of 3 WATERLOO FIRE RESCUE00 INSPECTION REPORT 1012 W DRD Sr. WATERLOO IA 50701 M<.E DETAILS Inspection Date: 07/30/2020 1 Inspection Type: Rental inspection I Inspection Number: 4639 ShifC N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS CODE DESCRIPTION FAIL 1018.1 - General Aisles and aisle accessways serving as a portion of the exit access in the means of egress system shall comply with the requirements of this section. Aisles or aisle accessways shall be provided from all occupied portions of the exit access that contain seats, tables, furnishings, displays and similar fixtures or equipment. The minimum width of required capacity of aisles shall be unobstructed. Exception: Encroachments complying with Section 1005.7. Inspector. BARRY STRATTON -Comments: Obstructions in egress paths, storage of items in basement. FAIL 1031.7 -Emergency escape Required emergency escape and rescue openings shall be maintained in accordance and rescue openings with the code in effect at the time of construction, and the following: Required emergency escape and rescue openings shall be operational from the inside of the room without the use of keys or tools. Bars, grilles, grates or similar devices are allowed to be placed over emergency escape and rescue openings provided the minimum net clear opening size complies with the code that was in effect at the time of consu uction and such devices shall be releasable or removable from the inside without the use of a key, tool or force greater than that which is required for normal operation of the emergency escape and rescue opening. Inspector: BARRY STRATTON - Comments: Broken windows, windows not capable of opening. FAIL 315.3.2 - Means of egress Combustible materials shall not be stored in exits or encloswes for stairways and ramps. Inspector: BARRY STRATTON - Comments: Storage in basement and upper unit. All storage shall be maintained safe. Large accumulation of items in basement. FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions elecnical hazards in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Several extension cords in use and need removed. Electric switches hanging off walls, outlets missing covers. Elecu is panel in basement has cover not sn ewed on box. Need 3 IT clearance to electric panels. vnm.a o� esrzs+zozo �� +oay Page 1 of 4 STATUS CODE DESCRIPTION FAIL FAIL FAIL FAIL FAIL 906.1 - Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, P,, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of i-A: 10-B: C. 2. Within 30 feet (9144 nvn) of commercial cooking equipment. 3. In at where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1. 6. Special-hazarcl areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector. BARRY STRATTON -Comments: Need fire extinguishers in all units. 907.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Smoke detectors are needed in each bedroom, outside of the bedrooms and in basement. This is code for both units, 915,1 -General Carbon monoxide detection shall be installed in new buildings in accordance with Sections 915.1.1 through 915, 6. Carbon monoxide detection shall be installed in existing buildings in accordance with Section 1103.9. Inspector: EARRY STRATTON - Conunents: CO detectors are required to be installed in vicinity of bedrooms in both units. R7 -Unsafe Structures Is the suuchire found to be dangerous to the life, health, property or safety of either the public or occupants of the structure? (IPMC 108.1.1) Inspector: BARRY STRATTON - Comments: Storage, obsh actions in egress paths, electric issues throughout units/basement R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON - Comments: Stove has gas leak. Electric outlets hanging off wall by back door. Romex can not be used in this location. Wire needs to be in EMT, v.ora a� esrzsimm � rt. ra Page 2 of 4 STATUS CODE DESCRIPTION FAIL R3 - Unfit for I iuman Is the structure found to befit for human occupancy according to the code? (IPMC Occupancy 108.1.3) Inspector: BARRY STRATTON - Comments: Condition of building is unsafe for occupants. IPMC 108.5 Prohibited Occupancy: Any occupied su uciure condemned and placarded by the code official shall be vacated as ordered by the code official. Any person who shall occupy a placarded premises or shall operate placarded equipment, and any owner or any person responsible for the premises who shall let anyone occupy a placarced premises or operate placarded equipment shall be liable for the penalties provided by this code. Units shall be vacated until such time repairs can be made. Permits shall be obtained by licensed contractors and units will need inspected before anyone moves back in. PAIL R4 - Exterior Propel ty Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON - Comments: Debris all over property. FAIL RS -Exterior SUuctwe Is the exterior of the structure maintained in good repair, snucturally sound and sanitary state? (IPMC 304) Inspector: BARRY STRATTON - Comments: Roof, Soffit, & Gutters need attention. Missing soffit material, roof is rotten and leaking into units. FAIL R6 -Interior Structure flas the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON -Comments: Missing doa s, holes in walls need repaired, globes needed on all lights, handrails needed Io upstairs and to basement, bath floor needs replaced, shower faucet needs replaced, stove needs replaced holes in ceilings and walls, doorjambs need replaced, door hardware needs replaced. FAIL R6.A. - Interior Structwe- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1) Unsafe Conditions Inspector: BARRY STRATTON - Comments: Egress paths blocked and storage throughout units and basement. FAIL R6.6. -Residential Nearing Are dwellings provided with heating facilities capable of maintaining a room temperature of 68 F? (IPMC 602.2) Inspector: BARRY STRATTON -Comments: Need 3 ft clearance around water heater and boiler. v,�� a�esrzwzozoc iaia sEoPage 3 of 4 STATUS CODE DESCRIPTION FAIL R6.C. - Mechanical Egiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON - Comments Need 3 It clearance around water heater and boiler. FAIL R6.D. - Receptades Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grounding -type receptacle of a receptacle with a GFCI. Every bathroom shall contain not less than one receptacle. Any new bathroom receptacle shall have GFCI protection. All receptacles shall have the appropriate faceplate cover, (IPMC 605.2) Inspector. BARRY STRATTON - Comments: Licensed electrician needs to make corrections to electric system of rental units. Several unsafe outlets, electric extension cords all over basement and upper unit. Outlets not working. Globes needed on all light fixtures. RElNSPECTION DATE 08/31/2020 CONTACT SIGNATURE Stan Shaw Signed on: 07/30/2020 @ 10:4II M I INSPECTOR SIGNATURE BARRY STRATTON Signed on: 07/30/2020 @ 10:49 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON b a r ry. s [ra tto n @waterloo -i a. o rg (319) 231-9147 piincea on 6u'�2E/202� �� I G.IJ Page 4 of 4 WATERLOO FIRE RESCUE INSPECTION REPORT 2001 CITY VIEW ST, WATERLOO IA 50703 DETAILS Inspection Date: 07/30/2020 1 Inspection Type: Rental Inspection Inspection Number: 4496 Shift N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors N/A I Fee: $50.00 STATUS CODE DESCRIPTION FAIL 1031.7 -Emergency escape Required emergency escape and rescue openings shall be maintained in accordance and rescue openings with the code in effect at the time of construction, and the following: Required emergency escape and rescue openings shall be operational from the inside of the room without the use of keys or tools. Bars, grilles, grates or similar devices are allowed to be placed over emergency escape and rescue openings provided the minimum net clear opening size complies with the code that was in effect at the time of construction and such devices shall be releasable or removable from the inside without the use of a key, tool or force greater than that which is required for normal operation of the emergency escape and rescue opening. Inspector: BARRY STRATTON - Comments: Back door still blocked by items. Obstruction to get out of back door. Items on both sides of door. FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments Electric hazards in basement with flooding/backup. Electric outlet in bathroom and bedroom needs replaced. Exterior egress lights do not work. Exposed electric wires in basement. FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 nun) of commercial cooking equipment. 3, In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1. 6. Special -hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector: BARRY STRATTON - Comments: Need fire extinguisher in unit. frig. an OS/25/2020 c^^-10:11 ��Page 1 of 3 STATUS I m FAIL FAIL FAIL. FAIL FAIL FAIL CODE DESCRIPTION 907.2.11 - Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907,2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Smoke detectors needed in each bedroom, outside bedrooms, and in basement. 916.4-Carbon monoxide Carbon monoxide alarms shall comply with Sections 915.4.1 through 915.4.3. alarms Inspector: BARRY STRATTON - Comments: CO detector needs to be in working condition. RZ -Unsafe Equiprnent Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON - Comments: Basement flooded Appliances plugged in sitting in water. R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON -Comments: Debris around property, R6 -Interior Structwe Has the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 306) Inspector: BARRY STRATTON -Comments: Basement Flooded, front door needs replaced. Doorjamb and door plate are broken. Vent registers not staying in place. Mold in basement on walls caused by water in basement. Broken interior doors need eplaced. R6.6. -Residential Healing Are dwellings provided with heating facilities capable of maintaining a room temperatwe of 68F? (IPMC 602.2) Inspector: BARRY STRATTON -Comments: Registers/vent covers R6.C. -Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector. BARRY STRATTON -Comments: Water damage in basement may cause damage for water heater, furnace and other appliances to malfunction. v.;��:n oa esrzsrzoze ry io: w Page 2 of 3 STATUS CODE DESCRIPTION FAIL R6.D. - Receptacles Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grounding -type receptacle or a receptacle with a GECI. Every bathroom shall contain not less than one receptacle. Any new bathroom receptacle shall have GECI protection. All receptacles shall have the appropriate faceplate cover (IPMC 605.2) REINSPECTION DATE OS/31/2020 CONTACT SIGNATURE Dorothy Haugebak Signed on: 07/30/2020 @ 11:03 INSPECTOR SIGNATURE BARRY TON Signed on: on: 0707/30/2020 @ 11:03 QUESTIONS AROUT YOUR INSPECTION? BARRY STRATTON ba rry. Stratton @waterloo-ia. org (319)231-9147 Inspector: BARRY STRATTON -Comments: N L trine on Qa'/26ri020 _=1G'.IY f�Page 3 of 3 WATERLOO FIRE RESCUE INSPECTION REPORT 1649 CAMELOT DR, WATERLOO IA 50702 DETAILS Inspection Date: 08/07/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4677 1 Shift: N/A 1 Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS CODE DESCRIPTION y�A" FAIL 505.1 - Address identification New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall court ast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each chatacter shall be not less than 4 inches (102 mm) high with a minimum stroke width of 112 (12.7 min). Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address identification shall be maintained. Inspector: BARRY STRATTON - Comments: Addresses need to be legible frour street and all apartment building exterior doors and all interior cloors shall have identification on all apartment doors. FAIL 605.1 - Abatement of Identified elecvical hazards shall be abated. Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Light switches in both bedrooms need replaced Have all switches and outlet checked to ensure working acid safe. Water coming out of outlets and light fixtures. FAIL 703.2 -Opening protectives Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Where allowed by the fire code official, the application of field -applied labels associated with the maintenance of opening protectives shall follow the requirements of the approved third -party certification organization accredited for listing the opening protective. Fire doors and smoke barrier doors shall not be blocked or obstructed, or otherwise made inoperable. Fusible links shall be replaced promptly whenever fused or damaged. Fire door assemblies shall not be modified. Inspector: BARRY STRATTON - Comments: Doors in corridors shall be capable of closing and latching. Doots also shall fit reasonably in the doorjamb. FAIL 9DL6.1 -Standards Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed in Table . v,�ro 0o earzarzozo c io.w Page 1 of 3 STATUS CODE DESCRIPTION - FAIL FAIL FAIL FAIL FAIL Inspector: BARRY STRATTON - Comments: Will need records that the alarm in building has been in working condition and has had proper maintenance. 9D6.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E, F, H, I, M, R-12 R-21 R-4 and S occupancies. Exception: In Group R-2 occupancies, per fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 mm) of commercial cooking equipment. 3. In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1. 6. Special -hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector: BARRY STRATTON - Comments: 907.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON -Comments: All smoke detectors installed shall be in or condition, In hallway smoke detector is hanging from ceiling and appears to have water damage from a leak. R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON - Comments: Baseboard units. RS -Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and sanitary state? (IPMC 304) Inspector: BARRY STRATTON - Comments: Window screes missing on some windows and some screens damaged. R6 - Interior Suucture Has the interior of the struchre and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON -Comments: Water damage to walls and ceilings. Bathroom, living room, bedrooms have water damage flooring ceilings, &walls. Peeling and abraded paint will need corrected. Tub tiles coming off tub surround. Tiles have water damage and will need removed and replaced. Proper wall board shall be installed to ensure water will not damage surround. Carpets are water damaged and show signs of mold forming under carpet where carpet pad was removed. Kitchen floors shall be removed and replaced. All floors shall be maintained in a clean, sanitary, and good repair, Knockdown plaster is bubbling from water damage. Remove all water damage and replace. Mold mitigation is needed in unit. 0� CIS w„rtl zsrzozac 10a4 Page 2 of 3 STATUS CODE DESCRIPTION FAIL R6.A. - Interior Structtn e- Unsafe Conditions FAIL R6.6.-Residential Heating FAIL R6.C. -Mechanical Egiupment REINSPECTION DATF 09/14/2020 CONTACT SIGNATURE Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1) Inspector: BARRY STRATTON - Comments: Mold Are dwellings provided with heating facilities capable of maintaining a room temperature of 58R (IPMC 602.2) Inspector: BARRY STRATTON -Comments: Baseboard heating shall be checked and covers attached as manufactured. Debris is in heating element area and could cause potential fire hazard. Are mechanical appliances properly ins[alled and maintained in good waking condition? (IPMC 603.1) inspector: BARRY STRATTON -Comments: Baseboard heating and Air conditioner not installed correctly for unit. Window air installed in P-Tec box in wall. Towels holding AC n place. Paramark �/� I� Signed on: 08/07/2020 @ 10:37 / 1 j-\ INSPECTOR SIGNATURE BARRY STRATTON Signed on: OS/07/202.0 @ 10:38 QUESTIONS ABOUfi YOUR INSPECTIONT BARRY STRATTON b a r ry. s V a tto n @waterloo- i a. o rg (319)231-9147 wm�Ea o� oan_c�zozo e io: is Page 3 of 3 WATERLOO FIRE RESCUE INSPECTION REPORT 402112 WELLINGTON ST. WATERLOO IA 50701 DETAILS Inspection Date: 08/10/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4687 1 Shift: N/A ( Station: N/A I Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS CODE DESCRIPTION - FAIL 7010.1.9 - Uoor operations Except as specifically permitted by this section, egress doors shall be readily openable fiom the egress side without the use of a key or special knowledge or effort. Inspector. BARRY STRATTON -Comments: Doors need to be installed and be functional. Main entrance door to 402 112 is missing molding and not installed in opening. Screen door is broken and needs replaced. FAIL 7031.2 -Reliability Required exit accesses, exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire of other emergency where the building area served by the means of egress is occupied. An exit or exit passageway shall not be used for any purpose that interferes with a means of egress. Inspector: BARRY STRATTON - Comments: Rear doors are blocked by weeds and foliage. Egress path needs to be free h om obstructions. Need to replace rear stairs on both units. FAIL 505.1 -Address iden[ificatia� New and existing buildings shall be provided with approved adchess identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be At numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 4 inches (102 ram) high with a minimum stroke width of 1/2 (127 Mill). Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address identification shall be maintained. Inspector. BARRY STRATTON -Comments: Need numbers on all apartment doors. Need addresses on building. a,�o� o�esrzeaozc�m:�a Ea Page 7 of 4 STATUS CODE DESCRIPTION FAIL FAIL FAIL FAIL FAIL 605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible cocle official. Electrical wiring devices, appliances and other equipment that is modified or clamaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRA, MN - Comments: Extension cords need to be removed. All outlets & fixtures need to be in good condition. All lights need to work and have proper globes. 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E F, H, E M, R-1, R-2, R-4 and S occupancies, Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 10-13: C. 2, Within 30 feet (9144 mm) of commercial cooking equipment. 3. In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1.6. Special -hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector: BARRY STRATTON -Comments: Need f re extinguishers in all units. 907.2.11 -Single- and Listed single- and multiple -station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON -Comments: Need smoke detectors in each bedrooms, outside of the bedrooms, and in basemen[. 915.1.1 -Where required Cathon monoxide detection shall be provided in Group I-1, I-2, I-4 and R ocaipancies and in classrooms in Group E occupancies in the locations specified in Section 915.2 where any of the conditions in Sections 915.1.2 through 915.1.6 exist. Inspector: BARRY STRATTON - Comments: Need CO detectors in vicinity of bedrooms. Rt -Unsafe Struttures Is the structure fowld to be dangerous to the life, health, property or safety of either the public or occupants of the structure? (IPMC 108.1.1) Inspector: BARRY STRATTON -Comments: Need handrails installed on all stairs. v.� - o�earzsimzc� i¢ia ��tlPage 2 of 4 STATUS CODE DESCRIPTION FAIL R2 - Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON - Comments: Stove plugged in with electric extension cords. Extension cot cis in use in all units and needs to be removed. Porch supports are rotten and do not support roof. Porch & supports will need removed and replaced. FAIL R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON - Comments: Need to replace roof. Roof is leaking. Front poach is weak and needs replaced. Front steps are unsafe and need replaced. FAIL R6 -Interior Structure Has the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON -Comments: Replace all broken windows, and picture windows that are broken. Repair all holes in walls. Basement is flooded by backed up drain. Sewer stack is leaking in basement. Toilet in upper unit is leaking at base of toilet. Bathroom window is not installed to code and is not safety glazed. Window in not approved for this location. FAIL R6.A. -Interior Structure- Were any unsafe caiditions noted during the interior- inspection?(IPMC 305.1.1) Unsafe Conditions Inspector: BARRY STRATTON -Comments: Ceiling collapsed in kitchen. Extension cords need removed. All electric outlets and fixtures need to be in function condition. FAIL R6.C. -Mechanical Egiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector. BARRY STRATTON -Comments: Water heater is missing cover. Dryer is not exhausting to thebutside. Dryer is exhausting in basement. Drain in basement is backed up. Sewer gas in basement. GENERAL NO iES BARRY STRATTON - O8/10/2020 @ 1443 9-7-4 9-7-5: Need all tenant information for ALL aparunents under your control turned into the City Clerk's Office. Prin[=tl on OS/25/2020� �G.iJ Page 3 of 4 REINSPECTION DATE 09/15/2020 CONTACT SIGNATURE LDN Properties LLC Signed on: 08/10/2020 @ 14:43 fNSPECTOR SIGNATURE BARRY STRATTON Signed on: 08/10/2020 @ 14:44 QUESTIONS ABOUT YOUR lNSPECTIONT BARRY STRATTON ba ny. strattoii@waterioo-ia.org (319)231-9147 `V- IL v���c mze�iu:w zo Page 4 of 4 WATERLOO FIRE RESCUE INSPECTION REPORT it 2141 LOGAN AVE, WATERLOO IA 50703 DETAILS Inspection Date: 08/10/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4546 1 Shift: N/A I Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A VIOLATIONS No Violations Found NEXT INSPECTION DATE 06/09/2023 CONTACT SIGNATURE Vieth Reality LLC Signed on: 08/10/2020 @ 10:13 INSPECTOR SIGNATURE BARRY n: 08/ON Signed oon: 8/10Q020 @ 10:13 QUESTIONS ABOUfi YOUR INSPECTION? BARRY STRATTON ba ny. Stratton @waterloo-ia. o rg (319) 231-9147 Frir. an OS/2E/3020 e10:15 rfaPage 1 of 1 WATERLOO ► RESCUE INSPECTION REPORT �a 656W11THST, WATERLOO IAS0701 DETAILS Inspection Date: 08/11/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4553 Shift: N/A Station: N/A Unit: N/A I Lead Inspector: BARRY SFRATTON I Other Inspectors: N/A I Fee: $50.00 STATUS -CODE DESCRIPTION FAIL 1070.19 -Door operations Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. hispector: BARRY STRATTON -Comments: Front doorjamb not seuned to house. Door still not corrected. Back cloor strike plates still not fixed. All doors shall fit reasonably in their openings and capable pf providing security and pet forming their intended function. FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock of fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Outlets not grounded in living room and kitchen still not repaired. FAIL R2 - Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON - Comments: Water heater needs discharge tube, No permits & inspections have been clone since 1 st inspection. Electric outlets have bad grounds. FAIL R4 - Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector. BARRY STRATTON -Comments: Drainage into basement. FAIL R6 -Interior Structure Has the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) v��, o"esrzwzomc roas �Ea Page 1 of 2 STATUS CODE DESCRIPTION - FAIL FAIL Inspector: BARRY STRATTON - Comments: Basement has mice and rodent feces in basement. Foundation walls are leaking and shall be maintained in good condition. Concrete shall be used to fill cracks not spray foam. Floor in basement has debris and water leaking up through Floor. Windows shall be capable of opening and dosing. bathroom window in not safety glazed. Kitchen cabinets have holes and holes in floors. Walls in basement stairwell need to be maintained free from cracks and holes. Strike plates and hardware need attention on all doors, R6.C. -Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON -Comments: Water heater no permits for installation and no inspections. R6. D. -Receptacles Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grouncling-type receptacle or a receptacle with a GFCI. Every bathroom shall contain not less than one receptacle. Any new bathroom receptacle shall have GFCI protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2) Inspector: BARRY STRATTON - Comments: Grounding, REiNSPECTION DATE 09/15/2020 CONTACT SIGNATURE Travis Davenport JVt A � Signed on: 08/11/2020 @ 13:27 ( \ f� fNSPECTOR SIGNATURE BARRY STRATTON Signed on: Oi3/11 /2020 @ 13:21 QUESTIONS ABOUT YOUR INSPECfilON7 BARRY STRATTON ba rry. Stratton@waterloo-i a. org (319) 231-9147 a�o- o�esearzoze �ioas ��oPage 2 of 2 WATERLOO FIRE RESC E INSPECTION REPORT 306JULIE CT, WATERLOO IA 50702 DETAILS Inspection Date: 08/13/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4702 1 Shift N/A I Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A I Fee: $50.00 STATUS CODE DESCRIPTION FAIL 906.1 - Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fine extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 10-13: C. 2. Within 30 feet (9144 torn) of commercial cooking equipment. 3. In at where flammable or combustible liquids are stored, used or dispensed. 4.On each floor Of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1.6. Special -hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector: BARRY STRATTON - Comments: Fire Extinguishers are needed in each bedroom. FAIL 907,2.11 - Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Smoke detectors are needed in each bedroom, outside of the bedrooms and in basement. FAIL 915.1 - General Carbon monoxide detection shall be installed in new buildings in accordance with Sections 915.1.1 through 915, 6. Carbon monoxide detection shall be installed in existing buildings in accordance with Section 1103.9. Inspector: BARRY STRATTON - Comments: CO detectors are needed in vicinity of the bedrooms. GENERAL NOTES BARRY STRATTON -08/13/2020 @ 0700 9-7-4 9-7-5: Landlad license and rental registration is needed for all rental units in Waterloo. Registration is required every year. e�,�e o�esrzsrzwo_ m.a <d Page 1 of 2 GENERAL NOTES BARRY STRATTON - 02/13/2020 @ 07:09 562A.19 Access: The landlord shall not abuse the right of access or use it to harass the tenant. Except in case of emergency or if it is impracticable to do so, the landlord shall give the tenant at least twenty-four hours' notice of the landlord's intent to enter and enter only at reasonable times. REINSPECfiION DAfiE 09/16/2020 CONTACTS/GNATURE Thomas8/1 [�L Signed onn::08/t'/2020 @ 07:13 INSPECTOR SIGNAfiURE BARRY STRATTON Signed on: 08/13/2020 @ 07:13 QUEST/ONS ABOUT YOUR INSPECTION? BARRY STRATTON ba rry. Stratton@waterloo-i a. o rg (319)231-9147 Pnn[e9 an 03125/3030 2 iG:15 Page 2 of 2 WATERLOO FIRE RESCUE INSPECTION REPORT 9625 MT CARMEL DR, WATERLOO /A 50703 DETAILS Inspection Date: 08/11/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4692 1 Shift: N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS CODE DESCRIPTION FAIL 605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Extension cords in use and need removed. FAIL R6 -Interior Structure Has the interior of the structwe and equipment inside peen maintained in good repair, suuctually sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON -Comments: Ceiling in living morn and dining room area are cracked and drywall is falling in. Replace all damaged drywall. Mice reported in At but @ time of inspection no noted mice found. Bugs reported in unit. Management on site notified of complaint. FAIL R6.C. -Mechanical Egiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON -Comments: Bathroom fan need repaired/replaced. Fan is very loud and is blowing out debris when turned on. REINSPECTION DATE 09/16/2020 CONTACT' SIGNATURE Waterloo Indelible Housing LLC �/ �� Signed on: 08/11/2020@ 14:00 (� v,mrea o0 osrzerzoze -�- iae s Page 1 of 2 INSPECTOR SIGNATURE BARRY STRATTON Signed on: 08/11/2020 @ 14:00 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON ba rty.stra tton@waterloo-ia. org (319) 231-9147 Prin[fa on 05126/E030 � 1015 Page 2 of 2 WATERLOO FIRE RESCUE INSPECTION REPORT 162S MT CARMEL DR, WATERLOO IA S0703 DETAILS Inspection Date: 08/11/2020 1 Inspection Type: Rental Inspection I inspection Number: 4692 1 Shift: N/A I Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS ` CODE DESCRIPTION - FAIL 605.1 -Abatement of Identified electrical hazards shall he abated. Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code official. Elecu ical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector. BARRY STRATTON - Comments: Extension cords in use and need removed. FAIL R6 - Interior Structure Has the interior of the structw e and equipment inside been maintained in good repair, Sit Mint sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON - Comments: Ceiling in living roorn and dining room area are packed and drywall is falling in. Replace all damaged drywall. Mice reported in unit but @ time of inspection no noted mice found. Bugs reported in unit. Management on site notified of complaint. FAIL R6.C. - Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON - Comments: Bathroom fan need repaired/replaced. Fan is very loud and is blowing out debris when turned on. REINSPECTION DATE 09/16/2020 CONTACT SIGNATURE -` Waterloo Indelible Housing LLC Signed on: OS/11/2020 @ 14:00 (� ` Prin(xd on GS/26/2020 ,�-- 10.)5 Page 1 of 2 INSPECTOR SIGNATURE BARRY STRATTON Signed on: 08/11/2020 @ 14:00 QUEST/ONS ABOUT YOUR INSPECTION? BARRY STRATTON bar y.stratton@waterloo-ia.org (319)231-9147 v��o zsrzozo cnuas �aPage 2 of 2 WATERLOO FIRE RESCUE INSPECTION REPORT 412 DANE ST, WATERLOO IA 50703 DETAILS nspection Date: 08/12/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4697 1 Shift: N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS -CODE DESCRIPTION - FAIL 1031.2 - Reliability Required exit accesses, exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency where the building area served by the means of egress is occupied. An exit or exit passageway shall not be used for any purpose that interferes with a means of egress. Inspector: BARRY STRATTON - Comments: Egress paths in unit are obstructecl. FAIL R4 - Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON - Comments: Garbage, debris, & weeds present. FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON - Comments: Closet has been torn up. Drywall removed & concrete floor removed. Replace drywall with rated wall board that is approved to retain firewall rating. Replace concrete floor. Possible looking for water leak and work being done to fix water leak done by an unlicensed contractor. REINSPECTION DATE 09/77/2020 CONTACT SIGNATURE John Poley E/ ' VT \� Signed on: 08/72/2020 @ 10:25 er�c<o o� osrzsizoze e- iooe Page 1 of 2 INSPECTOR SIGNATURE BARRY ON on: 081 Signed on: OS/12/2020 @ 10:25 QUES;IONS ABOUT YOUB iNSPEC;ION? BARRY STRATTON bany.sti atton@waterloo-ia.org (319)231-9147 Grn CSi2WT026 �0:16 �E Page 2 of 2 WATERLOO FIRE RESCUE INSPECTION REPORT 3719 W 9TN ST, WATERLOO IA 50702 DETAILS Inspection Date: 08/12/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4551 Shift: N/A I Station: N/A i Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A I Fee: $50.00 STATUS '.CODE DESCRIPTION - FAIL 1010.1.9 -Door operations Except as specifically pennit[ed by this secTion, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Inspector: BARRY STRATTON -Comments: Deadbolt still no[ replaced. Key access only on both sides of door not allowed. Need to install thumb turn style of deadbolt on or. Need to be done ASAP. PgIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E, F, H, I, M, R-11 R-21 R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 1043: C. 2. Within 30 feet (9144 turn) of commercial cooking equipment. 3. In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1. 6, Special -hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. Inspector: BARRY STRATTON - Comments: Fire extinguishers still not updated at listed address. 4/19/2019 Is date on extinguishers. FAIL R3 - Unfit for Human Is tie structure found to be fit for human occupancy according to the code? (IPMC Occupancy 108.1.3) Inspector: BARRY STRATTON - Comments: Mold. Moisture levels in units are high. FAIL R4- Exterior Property At Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON - Comments: Potential for mold to form with wet damaged ceilings and carpets. Moisture levels in units still reading high 96s.. Repair/replace damage affected at of drywall. v,�ro 0o esrzsrzozo c ivv Page 1 of 3 STATUS CODE DESCRIPTION - FAIL R5 - Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and sanitary state? (IPMC 304) Inspector. HARRY STRATTON - Comments: FAIL R6 -Interior Structure Has the interior 01 the stucture and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON -Comments: Water damage throughout unit # 6. Carpet damaged with water shall be removed and replaced. Ceilings in bathroom & living room/kitchen is damaged and needs replaced. Plaster damage from leak. Unit # 7 doorjamb is broken and trim to jamb is not attached at latch plate. Ceiling in unit # 7 kitchen/bath has water damage. FAIL R6,A. - Inrerior Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1) Unsafe Conditions Inspector: BARRY STRATTON - Comments: Mold FAIL R6.C. -Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON -Comments: AC unit in # 6 still does not have control knobs to operate AC. GENERAL NOTES HARRY STRATTON - OS/12/2020 @ 10:10 9-7-6 A (3): failure to correct deficiencies citations) will be issued to management company and/or landlord. REINSPECTION DATE 09/15/2020 CONTACT SIGNATURE R &) Kelly Trust Signed on: 08/12/2020 @ 10:11 E�1�/p �, �1� vn�.�Ea o� esrzsrozo c^^- io:v Page 2 of 3 INSPECTOR SIGNATURE BARRY STRAITON Signed on: 08/12/2020 @ 10:11 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON b a r iy, s t ra tto n@ wa to r l o o -i a. o rg (319)231-9147 a�mro 0o carzarzozc � m.n Page 3 of 3 WATERLOO FIRE RESCUE INSPECTION REPORT 428 OAKLAWN AVE, WATERLOO IA $0701 DETAILS Inspection Date: 08/24/2020 1 Inspection Type: Rental Inspection I Inspection Number. 456II Shift: N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: NIA I Fee: $50.00 STATUS CODE DESCRIPTION FAIL 1010.1.9 - Door operations Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. hispector: BARRY STRATTON -Comments: Bathroom door does not have suike plates. FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identifed hazardous electrical conditions electrical hazards in permanent wiring shall he brought to the attention of the responsible code official. Flecu-ical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Bathroom GFCI outlet has grounding issues. Electric system grounding. FAIL 907.2.11 - Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Need smoke detectors in each bedroom, outside of the bedrooms. and in basement. FAIL R2 - Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1 -2) Inspector: BARRY STRATTON - Comments: Windows, window frames, and casings damaged by water from leaking. Water heater is leaking from base of water heater. Water heater will need replaced. FAIL R4 - Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector. BARRY STRATTON - Comments: Gutters still leaking. w� o�osrzs�zozo c+o:n �foPage 1 of 2 STATUS CODE DESCRIPTION FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON - Comments: Peeling and abraded paint still needs corrected. Ceilings nad walls have water damage from roof leak. Need gripable handrails on basement stairs and back stairs. FAIL R6.C. -Mechanical Eqiuprnent Are mechanical appliances properly installed and maintained in good working condition? (IPMC 503.1) Inspector. BARRY STRATTON -Comments: Replace Water heater Toilet still has liter pop bottle in tank. FAIL R6.D. -Receptacles Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grounding -type receptacle or a receptacle with a GFCL Every bathroom shall contain not less than one receptacle. Any new bathroom receptacle shall have GFCI protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2) Inspector: BARRY STRATTON - Comments: RE/NSPECfi/ON DAfiE 09/24/2020 CONTACfi S/ONATURE Hawthorne Rentals Signed on: 08/24/2020 @ 14:41 INSPECTOR SIGNATURE BARRY STRATTON Signed on: 08/24/2020 @ 14:41 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON b a rrystra tton @waterloo-i a. o rg (319)231-9147 Ginn (''ol2fi/3020C 10:1> ��Page 2 of 2 WATERLOO (FIRE RECOJ INSPECT/ON REPORT 5548 SUMMERLAND OR, WATERLOO IA 50701 DETAILS Inspection Date: 08/04/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4587 1 Shift: N/A I Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A VIOLATIONS No Violations Found NEXT INSPECTION DATE - 07/22/2023 CONTACT SIGNAfiURE Troy Luck Signed on: 08/04/2020 @ 10:45 1NSP£CTOR SIONAfiURE BARRY ON Signed on: on: 08/08/04/2020 @ 10:45 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON ba nystratton @waterloo-ia.o rg (319)231-9147 Pnn[ on 03I26i2020� iG:i) E�Page i of 1 WATERLOO FIRE RESCUE INSPECTION REPORT 5548 SUMMERLAND DR, WATERLOO /A 50701 DETAILS Inspection Date: 08f04/2020 I Inspection Type: Rental Inspection Inspection Number: 4587 Shift: N/A Station: N/A Unit: N/A Lead Inspector: BARRY StRATTON I Other Inspectors: N/A VIOLATIONS No Violations Found NEXT INSPECTION DATE - - 07/22/2023 CONfiACfi SIGNATURE Troy Luck Signed on: 08/04/2020 @ 10:45 INSPECTOR SIGNATURE - - BARRY STRATTON Signed on: 08/04/2020 @ 10:45 QUESfi1ONS ABOUT YOVR INSPECfilON7 BARRY STRATTON b a rry. Stratton @water to o-ia.o rg (319)231-9147 vr��.ra o� oarzdzom � m.n Page 1 of 1 WATERLOO FIRE RESCUE INSPECTION REPORT 314E ARLINGTON ST, WATERLOO IA 50703 DETAILS Inspection Date: 08/20/2020 1 Inspection Type: Rental inspection I Inspection Number: 4585 Shift N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A STATUS -CODE DESCRIPTION FAIL 605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: 2 open boxes in basement on ceiling need covers. No electricity supplied to house at time of re -inspection so grounding could not be checked. FAIL 9D7211.2 -Groups R-Z, R-3, Single or nnultiple-station smoke alarms shall be installed and maintained in Groups R-4 and 1-1 R-20 R-31 R-4 and 1-1 regardless of occupant load at all of the following locations: 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. 2. In each room used for sleeping purposes. 3. In each story within a dwelling unit, including basements but not including ciawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. Inspector: BARRY STRATTON - Comments: Smoke detector is needed in basement. FAIL R4 - Exterior Property At Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON - Comments: Garbage all over yard from snowing FAIL R6 - Interior Structure Has the interior of the structure and equipment inside been maintained in good repair, shvcturally sound and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON - Comments: Handrails to basement are mounted to close to wall. Handrail height need to he between 34-38 inches and shall be at least 1 112 inches away from wall. Hand ails ends shall return or terminate back to wall, Floor at rear door is still soft and wood under is rotten and needs replaced. FAIL R6.C. - Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) wTnt<o on esrzeizoxo Timis Pa9e 1 of 2 STATUS .CODE DESCRIPTION Inspectot: BARRY STRATTON - Comments: Water heater installation still does not have proper permits & inspections. Inspections required by Plumbing Inspector. FAIL R6,D. -Receptacles Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grounding -type receptacle or a receptacle with a GFCI. Every bathroom shall contain not less than one receptacle, Any new bathroom receptacle shall have GFCI protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2) Inspector: BARRY STRATTON - Comments: No power supplied to house to check grounding of outlets. REINSPECTION DATE 09/21/2020 CONTACT SIGNATURE CNC Investments ,(p Signed on: 0II/20202020 @ 10:30 C� 11 / � `t /NSP£CTOR SIGNATURE BARRYSTRATTON Signed on: 08/20/2020 @ 10:30 QUESTIONS ABOUT YOUR /NSPECTION? BARRY STRATTON b a r ry. stra tto n@ w a [e r l o o -i a. o rg (319) 231-9147 an�.cEa on esrzerzoxo e- w:�s Page 2 of 2 WATERLOO FIRE RESC E INSPECTION REPORT 412 DANE ST. WATERLOO IA 50703 DETAILS Inspection Date: 08/19/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4723 1 Shift N/A 1 Station: N/A I Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors N/A STATUS 'CODE DESCRIPTION FAIL 1010.L9 -Door operations Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Inspector: BARRY STRATTON -Comments: Patio door does not lock. Building security: Doors shall be provided with devices designed to provide security to occupants and property within. Front door is broken at latch and hardware is not secured in door. out door will need replaced. FAIL 9072.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Smoke detectors are needed to be in working condition. FAIL 915.1 -General Carbon monoxide detection shall be installed in new buildings in accordance with Sections 915.1.1 through 915. 6. Carbon monoxide detection shall be installed in existing buildings in accordance with Section 1103.9. Inspector: BARRY STRATTON - Comments: CO detectors need to be in working condition. FAIL R1 -Unsafe Sttuctures Is the structure found to be dangerous to the life, health, property or safety of either the public or occupants of the structure? (IPMC 108.1.1) Inspector: BARRY STRATTON - Comments: Mold FAIL R2 -Unsafe Equipment Was [he presence of mtsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON - Comments: Kitchen cabinets have fallen off wall. Kitchen cabinets missing drawer fronts. Kitchen sink base has water damage and mold forming in cabinet. Water heater pipe penetrations are not fire caulked. No open penetrations allowed in walls. Prinrxd on OS/26/2020 �^ iP'.19 Page 1 of 2 STATUS .-.CODE DESCRIPTION FAIL R3 - Unfit for Human Occupancy FAIL R6 -Interior Structure FAIL R6.C. -Mechanical EGiupment REINSPECTION DATE 09/17/2020 CONTACT SIGNATURE )ohn Foley Signed on: OS/19/2020 @ 14:49 INSPEC►OR SIGNATURE BARRY STRATTON Signed on: 08/19/2020 @ 14:49 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON b a ny. s tra tto n@ wa to r l o o- i a, o rg (319)231-9147 Is the structure found to befit for human occupancy according to the code? (IPMC 108.1.3) Inspector: BARRY STRATTON - Comments: No carpet in living room. Carpet needs removed in dining room and stairs. Carpet needs removed and replaced in areas that have been water damaged. Walls that have been water damaged will need removed and replaced. Mold will need mitigated. Has [he interior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON -Comments: No carpet in living room. Carpet in dining room damage and needs removed and replaced. Kitchen cabinets need replaced. Drawer fronts missing on cabinets. Carpet is not sanitary. Mold mitigation is needed. Closet doors need installed in closets that doors have fallen off. Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON -Comments: Need fire caulk on water heater heater peneu-ations in mechanical closet. v���� o�esaerzozo�iooz ftlPage 2 of 2 WATERLOO FIRE RESCUE INSPECTION REPORT 1211 LANGLEY RD, WATERLOO IA 50702 DETAILS Inspection Date: 08/19/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4579 1 Shift N/A (Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A I Fee: $50.00 STATUS CODE DESCRIPTION FAIL 1018.1 -General Aisles and aisle accessways serving as a potion of the exit access in the means of egress system shall comply with the requirements of this section. Aisles or aisle accessways shall be provided from all occupied For of the exit access that contain seats, tables, furnishings, displays and similar fixtures or equipment. The minimum width or required capacity of aisles shall be unobstructed. Exception: Encroachments complying with Section 1005.7. Inspector: BARRY STRATTON - Comments: Egress path still unsafe from rear of building. FAIL 90L6 -Inspection, testing and Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust maintenance systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected tested and maintained or removed. Inspector: BARRY STRATTON -Comments: Still no records for alarm system in building. FAIL 907.2.1 L2 -Groups R-2, R-3, Single ormultiple-station smoke alarms shall be installed and maintained in Groups R-4 and I-1 R-2, R-3, R-4 and I-1 regardless of occupant load at all of the following locations: 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. 2. In each room used for sleeping purposes. 3. In each stay within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level. Inspector: BARRY STRATTON -Comments: FAIL R2 -Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, elearical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON -Comments: Rear stairs, landings, & no handrails on rear of building. PriP. on OSl26/2020 (^10:19 �Ea Pege 1 of 3 STATUS CODE DESCRIPTION FAIL R4- Extetlor Property At FAIL RS -Exterior Structure GENERAL NOTES BARRY STRATTON - 08/19/2020 @ 10:26 BARRY sTRATTON - OII/19/2020 @ 10:26 REINSPECT/ON DATE 09/16/2020 CONTACT SIGNATURE Equity Ves[ors LLC Signed on; 08/19/2020 @ 10:27 INSPECTOR SIGNATURE BARRY STRATTON Signed on; 08/19/2020 @ 10:27 Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON -Comments: Rear stairs to 12 plex Is the exterior of the structure maintained in good repair, structurally sound and sanitary state? (IPMC 304) Inspector: BARRY STRATTON -Comments: Every exterior stairway, deck, porch, and baIrony, and all appurtenances attached thereto, shall be maintained structurally sound, in good repair, with proper anchorage and capable of supporting the imposed loads. Property was notified back in May 20"LO about stairs and on today's date stairs are still unsafe. Double fee for rental registration has yet to be received by the Clerk's Office. 9-7-6 A(3): Failure to correct deficiencies shall result in municipal citations) being ssued. ec��cm o� esrzsizozc �-loos Page 2 of 3 QUESTIONS ABOUT YOUR INSPECTION? BARRY STRATTON bat ty.st ra tton @waterloo-ia. org (319)231-9147 Prnre o0 oaiu zozu e- ioa9 Page 3 of 3 WATERLOO FIRE RESCUE INSPECTION REPORT 713112 RANDOLPH ST. WATERLOO IA 50702 DETAILS Inspection Date: 08/20/2020 1 Inspection Type: Rental Inspection I Inspection Number; 4729 Shift: N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors N/A STATUS (CODE DESCRIPTION FAIL 505.1 -Address identification New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road ft on[ing the property. Address identification characters shall contrast with their background. Address numbers shall be At numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 4 inches (102 nun) high with a minimum stroke width of 112 (12.7 mm). Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. Address identification shall be maintained. Inspector: BARRY STRATTON -Comments: Address is required for rear apartment. FAIL 605.1 - Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions electrical hazards in permanent witing shall be brought to the attention of the responsible code official. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or file hazard shall not he used. Inspector: BARRY STRATTON - Comments: Need light replaced outside back door with approved outdoor fixture. Outlet above dryer is not grounded. Open lightfixture in basement with exposed wires X 2 (in ceiling above washer). Electric panel has open slots and needs approved slugs. Extension coed running from window AC to outlet act oss room. Window AC will need direct connection to an outlet. FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E, F, N, I, M, R-1, R-$ R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 10-B: C. 2. Within 30 feet (9144 mm) of commercial cooking equipment. 3. In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1. 6. Special -hazard areas, including but not limited to laboratories, computer rooms and generates rooms, where required by the fit code official. Inspector: BARRY STRATTON - Comments: Need fire extinguishers in units. Prin(ee on 4o'/2W302J C 1G'.19 Page 1 of 3 STATUS CODE DESCRIPTION FAIL FAIL FAIL FAIL FAIL FAIL FAIL 907.2.11 - Single- and Listed single- and multiple- station smoke alarms complying with UL 217 shall be multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Need smoke detectors installed in bedrooms, outside bedrooms, and in basement. 915.1 -General Carbon monoxide detection shall be installed in new buildings in accordance with Sections 915.1.1 through 915. 6. Carbon monoxide detection shall be installed in existing buildings in accordance with Section 1103.9. Inspector: HARRY STRATTON -Comments CO deteRor is needed in vicinity of the bedrooms. R2 -Unsafe Equipment Was [he presence of unsafe equipment noted during the inspection? Equipment may include boilers, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON -Comments: Rear deck, landing, &stairs need replaced. Water heater flue has no seal at chimney and installed without permits and inspections. PVC sewer stack installed in between case without any permits and inspections. R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON -Comments: Weed obstruction at rear stairs. Rear deck, landing &stairs need replaced. RS -Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and sanitary state? (IPMC 304) Inspector: BARRY STRATTON -Comments: Roof needs replaced. Several areas has exposed underlayment, (tar paper). R6 -Interior Structure Has the interior of the structure and equipment inside been maintained in good repair, structwally soun$ and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON -Comments: Peeling paint needs corrected in upper unit in several areas. Closet has water damage with peeling &abraded paint. R6.A. - Interim -Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1) Unsafe Conditions Inspector: HARRY STRATTON -Comments: Extension cords and water heater venting. F/lrce0 on 03/25/2020 3 1019 Page 2 of 3 STATUS CODE DESCRIPTION FAIL R6.C. - Mechanical Equipment Are mechanical appliances properly installed and maintained in good working conclition? (IPMC 603.1) Inspector: BARRY STRATTON -Comments: Water heater in stalled in 2019 did not have permits & inspections. Water heater flue is not installed in chimney correctly and is missing seal. PVC pipe installed in between cast pipe. FAIL R6.D. -Receptacles Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grounding -type receptacle or a receptacle with a GECL Every bathroom shall contain not less than one receptacle. Any new bathroom receptacle shall have GECI protection. All receptacles shall have the appropriate faceplate cover. (IPMC 60S.2) tnspector: BARRY STRATTON -Comments: Grounding required for all outlets. REINSPFCTION DATE 09/22/2020 CONTACT SIGNATURE Hagedom Housing LLC Signed on: 08/20/2020 @ 12:07 INSPECTOR SIGNATURE BARRY STRATTON Signed on: 08/20/2020 @ 12:07 QUESTIONS ABOUT YOUR INSPECTION? - PARRY STRATTON ba rry. s[ratton @wa to rloo-i a. o rg (319)231-9147 v�mao o�carzrzozo� was Page 3 of 3 WATERLOO FIRE RESCUE � INSPECTION REPORT M<.E 520 ANKENY ST, WATERLOO fA 50703 DETAILS Inspection Date: 08/24/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4592 1 Shift N/A I Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A I Fee: $50.00 STATUS '.CODE - DESCRIPTION..` - FAIL 1010.1.9.4 - 60l[ locks Manually operated flush bolts a surface bolls are not permitted. Exceptions: 1.On doors not required for egress in individual dwelling units or sleeping units. 2. Where a pair of doors serves a storage or equipment roost, manually operated edge- or surface -mounted bolts are permitted on the inactive leaf. 3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F or S occupancy, manually operated edge- or surface -mounted bolts are per on the inactive leaf. The inactive leaf shall not contain doorknobs, panic bars or similar operating hardware. 4. Where a pair of doors serves a Group B, F or S occupancy, manually operated edge- or surface -mounted bolts are permitted on the inactive leaf provided such inactive leaf is not needed to meet egress capacity requirements and the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The inactive leaf shall not contain doorknobs, panic bars or similar operating hardware. 5. Where a pair of doors serves patient care rooms in Group 1-2 occupancies, self -latching edge- or surface -mounted bolts are permitted on the inactive leaf provided that the inactive leaf is not needed to meet egress capacity requirements and the inactive leaf shall not contain doorknobs, panic bars or similar operating hardware. Inspector: BARRY STRATTON - Car nments: Latch locks on doors need removed. Doors now blocked by 2 X 4's on exterior of doors. FAIL 1031.7 -Emergency escape Required emergency escape and rescue openings shall be maintained in accordance and rescue openings with the code in effect at the time of construction, and the following: Required emergency escape and rescue openings shall be operational front the inside of the room without the use of keys or tools. Bars, grilles, grates or similar devices are allowed to be placed over emergency escape and rescue openings provided the minimum net clear opening size complies with the code that was in effect at the time of construction and such devices shall be releasable or removable fi ont the inside Without the use of a key, tool or for greater than that which is required for normal operation of the emergency escape and rescue opening. Inspector: BARRY STRATTON - Comments: latch locks & doors blocked with 2 X 4's. vr�ra o�esrzerzozo c-ioaz Page 1 of 4 STATUS CODE DESCRIPTION - - FAIL FAIL FAIL FAIL FAIL FAIL 605.1 -Abatement of Identified electrical hazards shall be abated Identified hazardous electrical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring, devices, appliances and other equipment that is modified of damaged and constitutes an electrical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Outlets in house do not have grounds. Some outlets have the hot/neutral reversed. Exposed wire still exist on exterior light at front door. 906.1 -Where required Parable fire extinguishers shall be installed in all of the following locations: 1. In new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 1-A: 10-13: C. 2. Within 30 feet (9144 nun) of commercial cooking equipment. 3. In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under cons0uction, except Group R-3 occupancies, in accordance with Section 3315.1. 5. Where required by the sections indicated in Table 906.1. 6. Special -hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. InspeRor: BARRY STRATTON -Comments: Need updated fire extinguisher in unit. 907.2.11 -Single- and Listed single- and multiple- station smoke alarms complying with UL 277 shall he multiple -station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector: BARRY STRATTON - Comments: Need smoke detectors in each bedroom, outside bedrooms, and in basement. 915.4 -Carbon monoxide Carbon monoxide alarms shall comply with Sections 915.4.1 through 915.43. alarms Inspector: BARRY STRATTON -Comments: CO detector is needed in vicinity of the bedrooms. R4 -Exterior Property Areas Is the exterior property area maintained in a clean, safe, and sanitary condition? This includes grading and drainage, sidewalks and driveways, weeds, and pest infestations. (IPMC 302) Inspector: BARRY STRATTON -Comments: Windows sills and framing rotten. Roof leaking and gutters need repaired. Broken windows and windows not capable of opening. Several tubes of roof tar all over property. Several tubes of caulk around property where window is boarded up. RS -Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and sanitary state? (IPMC 304) vrinzE On eaaarzazo�ioae Page 2 of 4 STATUS CODE DESCAIPTION - - htspector: BARRY STRATTON - Comments: Windows, gutters, doors. FAIL R6 - Interior Structure Has the intetior of the structure and equipment inside been maintained in good repair, structurally sound, and in a sanitary condition? (IPMC 305) Inspector: BARRY STRATTON - Comments: Ceiling has collapsed in bedroom, kitchen, and back entryway that has still not been repaired/ replaced. Front porch floor is unstable. Windows are not functional. Doorjambs and hardware to front door needs replaced The condition of the front door need attention. Bathroom cabinets missing drawer fronts. Handrail is needed to meet code to basement. Kitchen floor needs replaced Any wet drywall from ceilings needs removed and replaced Door trim and jamb to bathroom needs replaced Latch locks need removed. Bedroom doors broken and need replaced. FAIL R6.A. - Interior Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1) Unsafe Conditions Inspector: BARRY STRATTON - Comments: Cellulose from attic all over house,. Electric issues, peeling paint, windows, doors, water heater. FAIL R6.13. - Residential Heating Ate dwellings provicled with heating facilities capable of maintaining a room temperahire of 68P (IPMC 602.2) Inspector: BARRY STRATTON - Comments: Furnace filter FAIL R6.C. - Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON - Comments: Water heater missing cover and stove is not in working condition. FAIL R6.D. - Receptacles Every habitable space in a dwelling shall contain not less than two separate and remote receptacle outlets. Every laundry area shall contain not less than one grounding -type receptacle or a receptacle with a GFCL Every bathroom shall contain not less than one receptacle. Any new bathroom receptacle shall have GFCI protection. All receptacles shall have the appropriate faceplate cover. (IPMC 605.2) Inspector: BARRY STRATTON - Comments: Grounding issues, and wiring issues. AEINSPECTION DATE 09/22/2020 v,��.ra o� esrzsrzozo e ioae Page 3 of A CONTACT SIGNATURE LDN Properties LLC Signed on: 08/24/2020 @ 10:15 INSPECTOR SIGNAfiUFE 6ARRY STRATTON Signed on: 0812412020 @ 10:15 QUESTIONS ABOUfi YOUR 1NSPECTION7 BARRY STRATTON b a oy.stra tton@waterloo-i a. o rg (319) 231-9147 w,� o�esrzsrzomc ioae E Page 4 of 4 WATERLOO FIRE RES UE INSPECTION REPORT 725 W STH ST. WATERLOO ►A 50702 DETAILS Inspection Date: 08/24/2020 1 Inspection Type: Rental Inspection I Inspection Number: 4597 Shift: N/A Station: N/A Unit: N/A I Lead Inspector: BARRY STRATTON I Other Inspectors: N/A I Fee: $50.00 STATUS -CODE DESCRIPTION FAIL 1010.L9 -Door operations Except as specifically permitted by this section, egress doors shall he readily operable from the egress side without the use of a key or special knowledge or effort. Inspector: BARRY STRATTON -Comments: Rear egress door is now boarded up. Need alI egress doors to be accessible and capable of being used. FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous elecUical conditions electrical hazards in permanent wiring shall be brought to the attention of the responsible code official. Electrical wiring devices, appliances and other equipment that is modified or damaged and constitutes an elect ical shock or fire hazard shall not be used. Inspector: BARRY STRATTON - Comments: Need service in building to be grounded to code. FAIL R2 - Unsafe Equipment Was the presence of unsafe equipment noted during the inspection? Equipment may include ballets, heating equipment, elevator, moving stairways, electrical wiring, and flammable liquid containers. (IPMC 108.1.2) Inspector: BARRY STRATTON - Comments: Water heater draft flue need to be changed. Draft hood need to be installed to code and have a continuous rise in discharge. Need to install discharge tube on water heater. FAIL R5 - Exterior Structure Is the exterior of the structure maintained in good repair, structurally sound and sanitary state? (IPMC 304) Inspector: BARRY STRATTON - Comments: Need gripable handrails to run the full length of the stairs. Install handrails at a height of between 34"-38" inches. Handrails need to be turned back and top and bottom of handrails. FAIL R6.A. - Interior Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1) Unsafe Conditions Inspector: BARRY STRATTON - Comments: Electric Pr�n. on OSI2fi/2020 G'C iO:'20 «o Page 1 of 2 STATUS CODE DESCRIPTION FAIL R6.C. - Mechanical Ecliupment Are mechanical appliances properly installed and maintained in good working condition? (IPMC 603.1) Inspector: BARRY STRATTON - Comments: Water heater need flue changed to meet code and install a discharge tube. REINSPECTION OAfiE D9124/2.020 CONTACT SIONATURE Randy Schmidt Signed on: 08/24/2020 @ 14:28 \ INSPECTOR SIGNATURE BARRY n: 08/2 / Signed oon: 8/24/2020 @ 14:28 Q UEST/ONS ABOUT YOUR INSPECTION? BARRY STRATTON b a r ry. stra tto n @waterloo - i a. o rg (319)231-9147 cn�. a�osrzsrzozo e-+¢zo f��Page 2 of 2