HomeMy WebLinkAboutK & W Electric - CO#2 - FY22 4th St Bridge and Dam Lighting, Cont No. 1054 - 11.21.2022CHANGE ORDER
® Kevin Martin, K&W Electric ❑
0 Jamie Knutson, City of Waterloo ❑
0 ❑
PROJECT: 411) Street Bridge Dann & Lighting CO No.: 02
OWNER: City of Waterloo, Contract 1054 DATE OF ISSUANCE: 10/24/22
TO: Kevin Martin FROM:
K&W Electric, Inc. RITLAND+KUIPER Landscape Architects
l 127 Lincoln Street 501 Sycamore Street, Mezzanine A
Cedar Falls, IA 50613 Waterloo, Iowa 50703
You are directed to stake the following changes in this Contract:
1. Added cost for labor, equipment, and materials to add security cameras to the 4`►' Street
Pedestrian bridge. Includes cameras, power supply, and control infrastructure. $44,950.00
TOTAL ADD TO CONTRACT $44,950.00
Attachments: PR-01
Not valid until signed by both the Owner and Architect.
Signature of the Contractor indicates his agreement herewith, including any adjustment in the Contract sum or Contract time.
The original Contract Sum was ... $749,772.30
Net change by previously authorized Change Orders ($102,300.00)
The Contract Sum prior to this Change Order was $647,472.30
The Contract Sum will be (increased) by this Change Order $44,950.00
The new Contract Sum including this Change Order will be $692,422.30
The Contract Time will be (extended) Thirty ( 30) Days
RITLAND+KUIPER
Landscape Architects
ARCHITECT
Signatur
Mark Kuiper, ASLA, LEED AP
K&W Electric, Inc. City of Waterloo
CON"(/RACTOR OWNER
414,
QuettEuz EN
Signature Signature
Kevin Martin Quentin Hart
PROPOSAL REQUEST 01
4th Street Bridge & Dam Lighting Project
City of Waterloo Contract No. 1054
From: David Jordan <djordan@a,modus-eng.com>
Sent: Wednesday, September 21, 2022 9:47 AM
To: Mark Kuiper <mark@ritlandkuiper.com>; Kevin Martin <kmartin@kwsign.com>
Cc: Ryan Vestal <rvestal(a,modus-eng.com>
Subject: 4th Street Bridge Camera PR
Please provide a price for the following work to get a camera network, power, and accessories added to
the 4th street bridge lighting project.
Cameras:
Mounted at the top of each of the ends of the walkway bridge, provide one (1) Axis #P3727-PLE per side
(total of two). Lenses shall be adjusted to cover the courtyard area and lighting towers in a 180-degree
fashion. The fourth lens shall cover pedestrians entering the bridge for facial recognition. On the opposite
side of these cameras looking back into the bridge viewing the interior of the bridge, provide one (1) Axis
#P1467-LE Bullet camera per end (total of two).
For the Middle Sections and bridge viewing platforms provide two (2) Axis #P3715-PLVE per platform
(total of 4). These shall also be mounted at the top and on opposite sides of the platform. The lenses shall
be adjusted so that one lens looks into the pedestrian walkway covering the interior of the bridge and the
other to cover the pedestrian platform. These shall be adjusted like described on both ends of the platform
and at both platform locations.
See attached image for further details of viewing angles and coverage. Provide 8 salient camera licenses
for these cameras to talk to salient. At the far end (southwest corner closest to the parking ramp) provided
two (2) wireless link Ubiquiti Nanobeam ac gen2. Model number NBE-5AC-Gen2. One wireless link is
located at the west most camera location and the other is located at the parking garage. Provide 120V
plug-in POE injector and associated receptacle at parking garage location.
Network Cabinets/Components:
Provide two (2) Nvent/Hoffman 24x24x12 Wall mounted, 3-point latch, Nema 4x stainless steel, and key
lockable enclosures for data network and camera equipment. Coordinate with lighting control cabinets
and exact locations prior to mounting. We will mount one (1) in each viewing platform. Provide all
mounting and accessories needed for a complete and working, protected installation. Provide 120v
unswitched power at each location. Mount one (1) 10 port, industrial, hardened, L2 Managed, POE, wall
or din rail mountable, switch equal to TRENDnet #TI-PG102i-M with proper 120v/24v power supplies.
Cable and Pathway
Provide mid -grade Category 6 cabling from each cabinet and switch to serve POE powered cameras. (One
drop/run per camera (8 total), one to connect the two cabinets/switches together, and one for the radio
(wireless uplink)). Coordinate routing with electrical contractor and bridge structure. Electrician shall run
1" conduit to match lighting conduit (3/4 acceptable in bridge path if 1" doesn't fit) for all data cabling.
Connect the two cabinets with one pathway. Cat 6 cabling can be flown in bridge structure to get to
cameras.
Electrical
Provide new 20A-1P circuit of unswitched power to serve network cabinets. Refer to attached drawing for
more information.
2022 RITLAND+KUIPER LANDSCAPE ARCHITECTS
COPYRIGHT
N
CBX100
RGB
(TYP. OF 5)
ICO
PATHWAY LIGHTING PLAN
POWER TO
POE SWITCH
EXISTING CANOPY LIGHTING
RACEWAY IS LOCATED ON
NORTHWEST SIDE OF BRIDGE.
RGB
(TYP. OF 5)
CBX 100
REFER TO CONDUCTOR AND
CONDUIT CHART FOR MORE
INFORMATION
O
1" = 30'-0"
GENERAL NOTES:
A. ALL CONDUITS SERVING CIRCUITS ON THE BRIDGE SHALL BE SURFACE
MOUNTED TO BRIDGE EXTERIOR WALL OR SUSPENDED BELOW THE
BRIDGE. JUNCTION BOXES SHALL BE INSTALLED IN ACCESSIBLE
LOCATIONS. COORDINATE WITH DESIGN TEAM AS NECESSARY.
B. CONTRACTOR SHALL PROVIDE ACCESS TO BELOW THE BRIDGE DURING
CONSTRUCTION - CONTRACTOR SHALL BE RESPONSIBLE FOR ALL RIGGING,
SCAFFOLDING, ETC, REQUIRED FOR CONSTRUCTION.
C. LOCATIONS OF ALL NEW AND EXISTING EQUIPMENT, LIGHT
FIXTURES, AND CONDUIT ROUTING ARE INTENDED TO BE SHOWN
SCHEMATICALLY AND SHALL BE COORDINATED WITH THE DESIGN
TEAM DURING CONSTRUCTION.
D. ALL CONDUITS, JUNCTION BOXES AND FITTINGS SHALL BE WET LOCATION,
RATED,WATERTIGHT AND SEALED. REFER TO SPECIFICATIONS FOR MORE
INFORMATION.
REFERENCED NOTES: 0
(NOT ALL NOTES MAY BE APPLICABLE TO THIS SHEET)
1. ELECTRICAL CONTRACTOR SHALL REMOVE EXISTING CANOPY LIGHT AND
EXISTING JUNCTION BOX. WIRE NEW FIXTURES TO EXISTING CANOPY
LIGHTING CIRCUIT(S). REUSE EXISTING CONDUCTORS AND RACEWAY.
REFER TO FIGURE 1 FOR MORE INFORMATION ON DEMOLITION SCOPE.
2. WIRE FIXTURES TO EXISTING TIMECLOCK CONTROLS LOCATED IN SAME
NEMA 3R ENCLOSURE AS PANEL 1C.
3. MOUNT RGB POINT LIGHT FIXTURES TO WALKWAY NODE EXTERIOR
CONCRETE WALL. COORDINATE EXACT MOUNTING HEIGHT AND LOCATION
WITH DESIGN TEAM PRIOR TO INSTALLATION.
4. REMOVE TWO (2) AREA LIGHTS AND ASSOCIATED JUNCTION BOXES
INSTALLED IN NODES. EXISTING CONDUCTORS AND RACEWAY TO REMAIN
PROVIDE NEW SPLICE BOXES TO MAINTAIN CIRCUITRY TO OTHER
FIXTURES.
5. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ONE (1) CATSE
CABLE EQUAL TO BELDEN #7921A ROUTED IN A 1" CONDUIT FROM THE
MAIN CONTROLLER LOCATION TO EACH OF THE CBX BOXES AND WIRELESS
TRANSCEIVERS. ROUTE CONDUIT SURFACE MOUNT ON OUTSIDE OF
BRIDGE.
6. REFER TO SHEET E-3.0 FOR MORE INFORMATION OF MOUNTING OF
CASCADES LIGHTING. COORDINATE INSTALLATION WITH ALUMINUM TRUSS
MANUFACTURER.
7. RUNS OF LOG LUMINAIRES ARE DAISY CHAINED VIA MANUFACTURER
SUPPLIED JUMPER CABLES. FROM CBX CONTROL BOXES.
FIGURE 1: EXISTING CANOPY LIGHT TO BE REMOVED.
IGHT AND JUNCTION BOX TO BE
REMOVED. RACEWAY AND CONDUCTORS
0 REMAIN. TYPICAL OF 24 LOCATIONS.
NOTE:
UTILITIES SHOWN ARE INDICATED SCHEMATICALLY.
CONTRACTORS SHALL VERIFY ALL DEPTHS AND ALL
LOCATIONS/DIMENSIONS PRIOR TO EXCAVATING.
ALL UTILITIES MAY NOT BE SHOWN.
River
Lights
F.Y. 2022
4th Street Bridge
& Dam Lighting
Waterloo, Iowa
Project Leader/Landscape Architect:
RITLAND+KUIPER
Landscape Architects
501 Sycamore Street, Mezz. A
Waterloo, Iowa 50703
Phone: 319-233-8090
Electrical & Lighting Engineer:
MODUS Engineering
214 East 4th Street
Waterloo, Iowa 50703
Phone: 319-235-0650
Lighting Designer:
Shakespeare Lighting Design
1806 East Thornton Drive
Bloomington, Indiana 47401
Phone: 812-320-2796
Civil Engineer/Surveyor:
AECOM, Inc.
501 Sycamore Street, Suite #222
Waterloo, Iowa 50703
Phone: 319-232-6531
Architect:
INVISION Architecture
501 Sycamore Street, #101
Waterloo, Iowa 50703
Phone: 319-233-8419
Geotechnical Engineer:
Terracon Consulting Engineers
6612 Chancellor Drive, Suite #102
Cedar Falls, Iowa 50613
Phone: 319-277-4016
Issued
No.
Date Description
Issue Date :
06/20/22
Designed By :
Drawn By :
Reviewed By :
Sheet Title
PATHWAY
LIGHTING
PLAN
Category Sheet
E-2.1
City of Waterloo Contract No. 1054
21-086 WATERLOO RIVER LIGHTING
,ICTIR1C9 LIM0m
100% Employee Owned
Date:
Company:
Attention:
RE:
10.08.22
Modus
David
4th Street camera's
Nick Steinkamp
CEO
Kevin Martin
President — Civil Operations
Brian DeVries
President— Commercial Operations
We are pleased to provide you the following quote. This quote includes all need
labor, equipment, and materials to complete. The one exception to the RFQ is
that we will be running the cat 6 cable in the cable tray that is be hide fascia
board and below the new LOG light fixtures.
We are also asking for a completion date schedule extension so we can receive
the needed materials.
LUMP SUM $44,950.00
If you have any question, please feel free to call me at the office or at 319-240-
1119.
Kevin Martin
1127 Lincoln St.
PO Box 967
Cedar Falls, IA 50613
PH: 319.277.0415
F: 319.277.1418
1004 Main St.
PO Box 426
Emmetsburg, IA 50536
PH: 712.852.9077
F: 712.852.8061
1Bc
ANGS
Email: kwe ink-wetectric.com
Visit our website at www.k-weleciric.com