HomeMy WebLinkAboutMidAmerican_Energy_-_Refundable_Advance_Electric_Service_-_4.21.25Docusign Envelope ID: 90C731A5-AC54-4CA4-95C6-727D3EC2FDB2
NIIDANIERICAN
ENERGYCOMPANY
Obsessively, RelendesslyAt Your Serri[e-
April 8, 2025
Waterloo Leisure Services
Attn: Travis Nichols
TRAVIS.NICHOLS @WATERLOO-IA.ORG
MidAmerican Energy
Attn: Brad Ballard
PO Box 657
Des Moines, IA 50306
Reference: Electric distribution to serve a reconstructed pool at 801 Campbell Ave. in
Waterloo, IA. MX: 3214451 Revision II
Dear Travis:
We are pleased to submit the Refundable Advance for Construction Underground
Electric Service Extension Proposal for the above project. This proposal is valid for 90
days and if MidAmerican Energy construction has not commenced within 12 months it
may be voided.
Please sign and return the proposal as soon as you are ready to commit to the work. You
may withhold payment until 30 days before MidAmerican Energy Company is ready to
schedule the work. In the meantime, please keep me informed of your schedule. After
we have received your payment, we will sign and return a copy of the proposal for your
records.
If you have any questions, please call me at 515-252-6707.
Sincerely,
MidAmerican Energy Company
12noyx?4,6,,A
Brad Ballard
Customer Project Coordinator II
Enclosures
Docusign Envelope ID: 90C731A5-AC54-4CA4-95C6-727D3EC2FDB2
NIIDANIERICAN
ENERGYCOMPANY
Obsessively, Relentlessly AI Yaur Servi[e-
MidAmerican Energy
Attn: Brad Ballard
PO Box 657
Des Moines, IA 50306
MIDAMERICAN ENERGY COMPANY
REFUNDABLE ADVANCE FOR CONSTRUCTION
UNDERGROUND ELECTRIC SERVICE EXTENSION PROPOSAL
MX: 3214451 Revision II
MidAmerican Energy Company ("MidAmerican"), an Iowa corporation and Waterloo
Leisure Services ("Applicant"), agree as follows:
1. MidAmerican will extend its electric lines underground to serve 3PHS, 277/480V
to a reconstructed pool at 801 Campbell Ave. in Waterloo, IA as shown on the
attached drawings.
2. MidAmerican will furnish the necessary labor and materials required to fulfill its
undertaking, as specified above. Such work will commence by MidAmerican as
soon as reasonable and practicable after the execution of this Proposal and receipt
of Applicant's Advance payment, defined below. MidAmerican will complete the
work with reasonable diligence.
3. In consideration of the receipt of a payment in the amount of $27,570.50 From
Applicant, which is an advance for construction subject to refund ("Advance"),
MidAmerican agrees to construct necessary electric facilities as set forth above.
Please submit the Advance payment with Applicant's signed acceptance of this
Proposal. If Applicant's acceptance and Advance payment is not received by July
7th, 2025, the amount may be subject to change.
4. The Advance shall be subject to refund by MidAmerican to Applicant based upon
the following terms and conditions:
a. Advances shall not accrue interest and shall be subject to refund from the
date of original advance payment. The refund will be based on twelve
months usage of the incremental difference between the current annual
metered electric service bill of the above Applicant, as described below, and
Applicant's future usage through the following annual period, which will
start after MidAmerican has completed the required work requested by the
customer. The Applicant's current usage is based on 47,320 billed kWh for
the twelve-month billing period starting September 22, 2023 through
August 22, 2024 for electric meter S64177261, CSS Acct 37930-12016,
resulting in the established annual billing of $5,290.58. The customer will
receive a one-time refund equal to three times the actual annual revenue,
less both fuel expenses and energy efficiency cost recovery charges, for the
first 12 months of metered electric service of the above Applicant, as
described below.
Docusign Envelope ID: 90C731A5-AC54-4CA4-95C6-727D3EC2FDB2
NIIDANIERICAN
ENERGYCOMPANY
Obsessively, Relentlessly AI Yaur Servi[e-
MidAmerican Energy
Attn: Brad Ballard
PO Box 657
Des Moines, IA 50306
b. If additional single-phase customers are connected to the above described
line extension within 10 years of the original Advance payment, the above
Applicant shall receive refunds equal to three times estimated base revenue
for each additional new customer to the extent that such revenue exceeds
the additional distribution construction costs incurred by MidAmerican.
Base revenue shall be estimated annual revenue, less both fuel expenses and
energy efficiency cost recovery charges, based on similarly situated
customers.
c. Refunds shall be made annually on or about the anniversary date of the
original Advance payment.
d. Revenue for un-metered private lighting shall not be included in any refund.
e. No refunds shall be made for revenue associated with customers connecting
after 10 years from the date of the original Advance payment.
f. In no case shall the total amount refunded exceed the refundable portion of
the Advance payment stated above.
g. No refunds shall be made for customers served from a further extension of
the above described electric line extension.
The Applicant Agrees To:
1. Furnish and install the transformer pad including specified elbows and ducts,
according to the enclosed transformer pad drawings and minimum specifications.
A level graded, 10 foot minimum clearance is to be maintained from the front of
the pad to the nearest fixed structure.
2. Furnish and install an additional secondary duct for temporary service (if
required).
3. Furnish, install, own and maintain all 4-inch ducts as shown on attached prints.
All ducts shall be black w/red stripe or grey in color, PVC type schedule 40 or
schedule 40 HDPE coil -able. Applicant shall install the ducts a minimum of
forty-two (42) inches and a maximum of forty-eight (48) inches below finish
grade with capped and staked ends and equipped with pull wires. MidAmerican
Energy Company will provide marker balls for the duct ends. These are available
at MidAmerican Energy Company's storeroom. Applicant is responsible for
correct placement and depth of conduit. Note: No more than ten (10) conduits
allowed within the secondary compartment of the transformer pad.
Docusign Envelope ID: 90C731A5-AC54-4CA4-95C6-727D3EC2FDB2
NIIDANIERICAN
ENERGYCOMPANY
Obsessively, Relentlessly At Your Serri[e-
MidAmerican Energy
Attn: Brad Ballard
PO Box 657
Des Moines, IA 50306
4. All duct elbows shall be fiberglass, forty-eight (48) inches in radius, heavy wall,
with factory assembled plastic couplings on each end to mate with schedule 40
PVC duct.
5. Furnish and install barrier walls around the transformer that may be required by
the governing authorities' standards to shield windows, doors and other building
openings.
6. Furnish and install guard posts around the transformer (if needed).
7. Notify MidAmerican Energy Company 48 hours before pouring the concrete
transformer pad. Please contact me at 515-252-6707 to arrange for inspection.
8. Furnish, install, own, and maintain all secondary cable between the transformer
and the metering point.
9. Furnish easements to MidAmerican Energy Company without cost. (Furnish
survey drawing and/or legal description for easement preparation). If a 3rd party
easement is required any cost associated in obtaining the easement will be paid
by the applicant.
10. Pursuant to MidAmerican's tariff, the Applicant is required to pay actual permit
fees. Permit fees may not be offset by Revenue Credit and are to be paid
regardless of whether the applicant is required to pay a Refundable Advance or a
Nonrefundable Contribution.
11. Install metering instrument transformers sized and furnished by MidAmerican
Energy Company, and furnish and install the meter socket and test switch for all
instrument transformer services.
12. Bushing mounted current transformers (CT's) are only approved for services
above 1200 Amp and must be approved by our local meter shop department.
13. Furnish and install an electric meter setting for each tenant, applicable sockets,
conduit, cabinets and wiring according to MidAmerican Energy Company's
standards. Please contact your local customer project coordinator to complete the
service application to initiate new meter and service connection.
14. Furnish and install an oil containment structure (moat) around
MidAmerican Energy Company's transformer. Please note the required
specification for the oil containment structure is located on the design print
provided with this proposal and in MidAmerican Energy Company's
Electric Service Manual (curb style containment structure is not acceptable).
Docusign Envelope ID: 90C731A5-AC54-4CA4-95C6-727D3EC2FDB2
NIIDANIERICAN
ENERGYCOMPANY
Obsessively, RelendesslyAt Your Serri[e-
MidAmerican Energy
Attn: Brad Ballard
PO Box 657
Des Moines, IA 50306
15. Locate all underground facilities such as storm and sanitary sewer, septic lines,
underground electric cable, communication cable, irrigation systems and water
lines that are not located by members of One Call. MidAmerican Energy
Company assumes no liability for private facilities not located.
16. Be responsible for complying with all aspects of compliance as required by any
local, state, or federal permit or plan associated with storm water pollution
prevention or erosion control. It is specifically understood and agreed that
MidAmerican Energy Company is providing the service requested by the
Applicant solely for the Applicant. MidAmerican Energy Company will not
become or agree to become a co-permittee or operator for the purpose of
applicants' compliance with any local, state or federal permit or plan associated
with storm water pollution prevention or erosion control.
17. Stake all necessary lot lines, corners and buildings before installation of the
primary cable.
All meter and related metering equipment locations shall be approved by the
company. Unless Company approval of an exception is given, all meters and related
meter equipment must be installed outside and securely attached to permanent
structure.
MidAmerican Energy Company will not hook up permanent electric service until the
oil containment structure is installed around the transformer.
If a change is made to your facility that requires oil containment around any existing
transformers, you will be responsible for the cost to install the containment structure/s.
If MidAmerican Energy Company is required to start construction of underground electric
facilities during the winter season, the work will be subject to an additional winter
construction charge.
Proposed this 8th day of April, 2025
MIDAMERICAN ENERGY COMPANY
By:
Title: Supervisor, Customer Project Support
yilA, (ka
Do52Mayo r9...
Title:
Docusign Envelope ID: 90C731A5-AC54-4CA4-95C6-727D3EC2FDB2
Byrnes Park Extention
1009643
101
11M1•MEM•=NM•••=1.•
93-4-590
1nn4
TOP STLT POLE
0001J096
Qo
Lam•
J P
C
•
•
•
r
•
•
amma'' — • ® 0001009 8
001552161E nr sR I /0 ACSR 6/1
40T REMOVE TEMP TRANSFORMER BANK
REMOVE OH WIRE.
EXISTING POLE IN WAY OF SIDEWALK
z-5-3 WOOD
2u5F05948
9
932
928
922
1
916
•-•4M=
910
• 0001009660
801-901
INSTALL 45' POLE
INTALL CR8M106 FRAME
INSTALL GGC523 GUY
INSTALL RPC302 RISER
25T FUSE LABEL: 05F05948
HOFFMAN BORE IN APPROX 90' OF 4" CONDUIT
.a PULL IN APPROX 400' OF 1/0 PARA
RBT04772
C PHS 150 KVA
480/277
CUSTOMER TO
INSTALL 4" CONDUIT TO ROW
INSTALL MEDIUM TRANSFOMER PAD
INSTALL 150KVA 480/277 XFMR
INSTALL (4) TCC202'S
LABEL 05T04772
MIDAMERICAN
ENlERCYCOMPANY.
Crew HQ:WAT
Gust: Waterloo Leisure Services
Addr: 801 801 CAMPBELL AVE AVE
City: WATERLOO
X = 1945197 Y = 907061
WMS_REV:3214451-1
Date: 8/8/2024
Scale: 1 IN = X FT
Designer:ROBERT D HOLM
Job Desc: BYRNES PARK POOL
DISCLAIMER OF LIABILITY
NOTE: This drawing reflects facilities in place at the time of its preparation and is subject to change at any time. For current facility information, please contact MidAmerican Energy
Company. Further, MidAmerican Energy Company disclaims all liability and responsibility for all claims and damages including but not limited to, personal injury, death and
property damage, resulting from any authorized or unauthorized use of, or reliance upon, this drawing for any purpose.