COMMERCIAL INSPECTION FEE- 300 W 4TH ST- 01/08/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
9011 01/14/2026 02/18/2026 2026-00000290 $80.00
Less Prepayment $0.00
Total Due—► $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
�,Ew,, Waterloo Fire Rescue
o
t.
,'k Inspection Report 425 E.3rd Street
Doughy Joey's-300 W 4th ST,BLDG 300 W 4th St,Waterloo 50701 Q✓ Pt)
INSPECTION DETAILS
fib!
Inspection Da:a Inspection Type Inspection Number
0110812026 Annual Inspection(1Yr) 16953
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 51 13 ® 11
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 0112912026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-0110812026 @ 12:58
•$80 annual inspection fee
BRAD BALDWIN-01/0812026 @ 15:01
Noted during 118/26 inspection-Employee coats hanging from above kitchen electric panel.Maintain panels easily accessible and visible for fire fighters
access in case of emergency.
BRAD BALDWIN-01/08/2026 @ 15:06
Corrected during 118126 inspection:(1)Removed obstruction blocking access to fire extinguisher in dishwashing area.(2)Removed storage within 18"
below sprinkler head in upper level storage closet.(3)Removed bar mini fridge from extension cord,plugged to wall outlet.
BRAD BALDWIN-01/08/2026 @ 15:14
Christmas lights throughout building approved for temporary(90 days)usage.
BRAD BALDWIN-01/08/2026 @ 15:18
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-01/0812026 @ 15:18
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-01/0812026 @ 15:18
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.****"Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
GENERATED ON 1/8R6,3:32 PM 1 OF 10
No signature
Report completed post inspection
Andrew Howe Date:
CHECKLISTS
Fire Alarm System
Code Description
Fail Chapter 14-Inspection,testing,and maintenance
Fire alarm system tested at least annually by licensed Location:Fire alarm
contractor Comments:Fire alarm inspection due 1128/26.Contractor shall
upload report to Compliance Engine with any deficiencies corrected.
Fire Sprinkler System
Status cd- Description
Fail 903.3.3-Obstructed locations.
OAutomatic sprinklers shall be installed with regard to Location:Near dishwasher
obstructions that will delay activation or obstruct the water Comments:Remove dust build-up an sprinkler heads and guards.
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
GENERATED ON 1/8/26,3:32 PM 2 OF 10
Fire Service Features
st_u< Code, Description
Fail 509.2-Equipment access.
Approved access shall be provided and maintained for all fire Location:Sprinkler riser room
protection system equipment to permit immediate safe Comments:Remove all storage from room,maintain clear access to
operation and maintenance of such equipment.Storage,trash fire protection services at all times.
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
�11
F
1t �-
3 OF 10
GENERATED ON 1/8/26,3:32 PM
Additional Codes
s_.-.. c.cde Description
Fail 5303.5.3-Securing compressed gas containers,cylinders
and tanks. Location:Kitchen tanks near electric panel
Compressed gas containers,cylinders and tanks shall be Comments:Secure compressed gas cylinders with chain to avoid tip
secured to prevent falling caused by contact,vibration or over.
seismic activity.Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers,cylinders and tanks to a fixed object
with one or more restraints.2.Securing containers,cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers,cylinders or tanks.
3.Nesting of compressed gas containers,cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if
dislodged,do not obstruct the required means of egress.
4.Securing of compressed gas containers,cylinders and
tanks to or within a rack,framework,cabinet or similar
assembly designed for such use.Exception:Compressed gas
containers,cylinders and tanks in the process of
examination,filling,transport or servicing.
-,-
1
i
„.„,,....-V„...„,
', mks
i , 4.
GENERATED ON 1/8/26.3:32 PM 4 OF 10
Fail 606.1-General.
Commercial kitchen exhaust hoods shall comply with the Location:Kitchen fryers
requirements of the International Mechanical Code.
Comments:Move fryers to be 6 inches inside of outer edge of hood
exhaust system to avoid flame roll out.
•
44
lc
J:
GENERATED ON 1/8/26,3:32 PM 5 OF 10
Electrical Safety
Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Kitchen microwave
Identified electrical hazards shall be abated.Identified Comments:Replace appliance or cord damaged exposing wires.
hazardous electrical conditions in permanent wiring shall be Replacing cord shall be provided by licensed electrician,retain copy
brought to the attention of the responsible code official. of receipt of work completed.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
1
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Main level bathroom hallway.
prohibited.Approved covers shall be provided for all switch Comments:Provide missing outlet covers(2).
and electrical outlet boxes.
GENERATED ON 1/8/26,3:32 PM 6 OF 10
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Sprinkler riser room
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or Comments:Remove all storage from room,maintain clear access to
less,and Section 110.33 of NFPA 70 for electrical equipment panels at all times.
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
\......)f )\ l'' ', i'
'A
, 1;000f,rr4..ev:0021_
1
— �' E
.,
, , ,a,.. -1
, ik,, il
yv 3
Y4 yK L
V.\ \ \ ;
-S , J I
3, B
• t' w. .,
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Upper level office
for permanent wiring and shall be listed and labeled in Comments:Remove POS system flexible cord from above drop
accordance with UL 817.Extension cords and flexible ceiling.
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 1/8/26,3:32 PM 7 OF 10
Commercial Cooking Hood Suppression System
Sa-,, Des,J .,-,,
Fail 606.3.3-Cleaning.
Hoods,grease-removal devices,fans,ducts and other Location:Kitchen hood exhaust
appurtenances shall be cleaned at intervals as required by Comments:Exhaust cleaning due 1128/26.Provide cleaning and
Sections 606.3.3.1 through 606.3.3.3. report to be uploaded to Compliance Engine with any deficiencies
corrected.
Fail 606.3.3.2-Grease accumulation.
If during the inspection it is found that hoods,grease-removal Location:Kitchen fryers cabinet,cooktop,floor under cooking
devices,fans,ducts or other appurtenances have an equipment,wall and gas lines behind equipment.
accumulation of grease,such components shall be cleaned in Comments:Clean build-up of grease,hood exhaust not engineered to
accordance with ANSIIIKECA C1O. provide coverage of grease accumulation.
re __ , Mr-11111111r7, • ', ; '
°^ k
F
,-- tom:.
, , I , V:____ ___
t
c
,
GENERATED ON 1/8/26,3:32 PM 8 OF 10
Fi'e'Resistant Construction Maintenance
Status Curie Description
Fail 704.1-Maintaining protection.
U Where required when the building was originally constructed, Location:Main level hallway near Sprinkler Riser Room
materials and systems used to protect joints and voids in the Comments:Replace missing ceiling tile.
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail 705.2.4-Door operation.
USwinging fire doors shall close from the full-open position Location:Sprinkler riser room
and latch automatically. Comments:Remove items holding door open.Fire rated door shall
self close and latch.
f],i
itil
1 1
y
s�. l t',
11
F
t V
sik
�r
/w'
s ort `�'-- `y
GENERATED ON 1/8/26,3:32 PM 9 OF 10