COMMERCIAL INSPECTION FEE- 310 W CONGER- 01/12/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
12078 01/14/2026 02/18/2026 2026-00000294 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
425 E.3rd Street
Electric Park Ballroom-310 W Conger ST,BLDG 310 W Conger St,Waterloo IA
50701 Et �
INSPECTION DETAILS ld078 ��
Inspection Date Inspection Type Inspection Number
01/12/2026 Annual Inspection(1Yr) 16445
Lead Inspector Station Unit
BRAD BALDWIN N/A NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
061 ® 5 010
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
02/0612026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-0111312026 @ 12:35
•$80 annual inspection fee
BRAD BALDWIN-01/14/2026 @ 08:48
Basement sprinkler piping noted with leak today,necessary repairs shall be made by licensed sprinkler contractor.Last inspected 5/27/25,passed
inspection by Blackhawk Sprinklers.
BRAD BALDWIN-01/14/2026 @ 08:46
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-0 1114/2 0 2 6 @ 08:46
GENERATED ON 1/14/26,8:54 AM 1 OF 6
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-0111412026 @ 08:46
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-01114/2026 @ 08:50
•Request of specific time on scheduled inspection date or change of inspection date shall be made by business representative prior to scheduled
inspection date.Failure to request time or change of date will result in failed inspection.
SIGNATURES
Contact signature Inspector signature
No signature -RE-REReport completed post inspection
Mark Little 2025 Date:_ BRAD BALDWIN 0111412026
CHECKLISTS
i
GENERATED ON 1/14/26,8:54 AM 2 OF 6
Emergency Equipment
s ati,s Code Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:South ballroom egress light by ticket counter
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress light that failed to illuminate
during test
1 , ,�5
,,;
1
f/rs_
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Egress lights above steps from bar to ballroom
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress light that failed to illuminate
during test
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:High bay egress lights
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Provide document of testing all high reach egress lights
including repairs made if necessary.Sign and date document,email
to inspector.
GENERATED ON 1/14/26,8:54 AM 3 OF 6
Fire Resistant Construction Maintenance
Status Code Description
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Bar seating area
materials and systems used to protect joints and voids in the Comments:Replace damaged ceiling by obtaining city building
following locations shall be maintained.The materials and permit and inspection.
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floorlceiling assemblies and roof or
rooficeiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer&N039;s installation instructions.
1111111
..,,c. _ *...4.,. ,
f
3
GENERATED ON 1/14R6.8:54 AM 4 OF 6
Fail 704.1 - Maintaining protection.
Where required when the building was originally constructed, Location: Next to bar
materials and systems used to protect joints and voids in the Comments: Replace damaged ceiling by obtaining city building
following locations shall be maintained. The materials and
permit and inspection.
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire-resistance-rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.