COMMERCIAL INSPECTION FEE-250 ANSBOROUGH- 01/12/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 50,000 $225.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24040 01/14/2026 02/18/2026 2026-00000293 $235.00
Less Prepayment $0.00
Total Due--► $235.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
425 E.3rd Street
Hippodrome Auditorium-250 Ansborough AVE,BLDG 257 Ansborough Ave,
Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
0111212026 Annual Inspection(1Yr) 16658
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
� 54 �; 18 ® 10
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
02/0612026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-01113/2026 @ 11:36
$325 annual inspection fee
BRAD BALDWIN-01/13/2026 @ 12:12
Inspector not granted access to managers office,ticket office,and cash room today.
BRAD BALDWIN-01113/2026 @ 12:31
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-01113/2026 @ 12:31
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-01113/2026 @ 12:31
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-01114/2026 @ 08:50
•Request of specific time on scheduled inspection date or change of inspection date shall be made by business representative prior to scheduled
inspection date.Failure to request time or change of date will result in failed inspection.
SIGNATURES
Contact signature Inspector signature
No signature
Report completedeelpost stinspection
GENERATED ON 1/14/26,8:53 AM 1 OF 10
Mark Little-2025 Date: BRAD BALDWIN 01/14/2026
CHECKLISTS
Means of Egress
Status Code Description
Fail 1010.1.3-Door opening force Forces to unlatch and open
doors. Location:NE green exit doors(2nd from left door)
The force for pushing or pulling open interior swinging Comments:Repair or replace door that failed to open today(top latch
egress doors,other than fire doors,shall not exceed 5 not operating).
pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
Fail 1032.2-Reliability.
Required exit accesses,exits and exit discharges shall be Location:East box office
continuously maintained free from obstructions or Comments:Remove furniture from egress path of exit.
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
IY
rr
tii tii a
GENERATED ON 1/14/26,8:53 AM 2 OF 10
Emergency Equipment
Stat`s Code Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:High bay emergency egress lights
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Provide documentation of testing and repairs completed
if necessary of all high bay egress lights in building.Report shall be
signed and dated and emailed to inspector.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:NW men's bathroom
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress light that failed to illuminate
during test.
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Exit signs
in Section 1013.6.3.The system shall be capable of powering Comments:Provide documentation of testing and repairs completed
the required load for a duration of not less than 90 minutes. if necessary of all high bay exit lights in building.Report shall be
signed and dated and emailed to inspector.
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Lobby men's bathroom
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign that failed to illuminate during
the required load for a duration of not less than 90 minutes. test.
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Main lobby exit(south)doors
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign that failed to illuminate during
the required load for a duration of not less than 90 minutes. test.
GENERATED ON 1/14/26,8:53 AM 3 OF 10
Fire Sprinkler System
Sta':s, Cede Description
Fail 4.9-Support of nonsprinkler system components
Sprinkler system components shall not be used to support Location:Dressing rooms 3&4
non-sprinkler system components unless expressly permitted Comments:Remove wiring used for curtains in shower from
by NFPA 13. sprinkler piping.
•
Fail 4.9-Support of nonsprinkler system components
Sprinkler system components shall not be used to support Location:Dressing room 5&6
non-sprinkler system components unless expressly permitted Comments:Remove light and cord supported by sprinkler pipe.
by NFPA 13.
•
Fail 4.9-Support of nonsprinkler system components
Sprinkler system components shall not be used to support Location:Dressing rooms 5&6
non-sprinkler system components unless expressly permitted Comments:Remove wiring used for curtains in shower from
by NFPA 13.
sprinkler piping.
4 OF 10
GENERATED ON 1/14/26,8:53 AM
Fail 903.3.3-Obstructed locations.
Automatic sprinklers shall be installed with regard to Location:Woo store
obstructions that will delay activation or obstruct the water Comments:Remove tape from escutcheon ring.
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
({-
3
GENERATED ON 1/14/26,8:53 AM 5 OF 10
Electrical Safety
Code Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Woo Store(SE wall)
Identified electrical hazards shall be abated.Identified Comments:Replace damaged outlet
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
GENERATED ON 1/14/26,8:53 AM 6 OF 10
Fail 603.2•Abatement of unsafe conditions and electrical
hazards. Location:West concession
Identified electrical hazards shall be abated.Identified Comments:Replace damaged outlet below counter
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
V. �.
•
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Exterior outlet above"arcade area"entrance
Identified electrical hazards shall be abated.Identified Comments:Replace damaged outlet.
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
GENERATED ON 1/14/26,8:53 AM 7 OF 10
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Woo store(SE wall)
prohibited.Approved covers shall be provided for all switch Comments:Replace missing outlet cover
and electrical outlet boxes.
14
.g tq
1i
r
•
GENERATED ON 1/14/26,8:53 AM 8 OF 10
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Hawkers storage
equipment shall be provided in accordance with Section Comments:Remove storage from within 36"in front of panel,
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or maintain clear access to panel at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
-
_.
, t-
l 'ta.
_ y
!'l J.
4
Fail 603.9.4-Prohibited areas.
Portable,electric space heaters shall not be operated within 3 Location:Maintenance area
feet(914 mm)of any combustible materials.Portable,electric Comments:Provide documentation of proper commercial listing and
space heaters shall be operated only in locations for which label of heater or remove from usage.
they are listed.
Additional Codes
Status Code Description
Fail 912.7-Inspection,testing and maintenance.
L�
Fire department connections shall be periodically inspected, Location:Private hydrants
tested and maintained in accordance with NFPA 25.Records Comments:Provide report of inspection with any deficiencies
of inspection,testing and maintenance shall be maintained. corrected of all private hydrants on property.Contractor shall upload
reports to Compliance Engine,currently 251 days past due as of
1113126.
GENERATED ON 1/14/26,8:53 AM 9 OF 10