HomeMy WebLinkAbout1615 BISHOP O W A PF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
430 01/14/2026 02/18/2026 2026-00000288 $80.00
•
.......
S Ivi7N�
Customer#: 24892 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
IOWA CONVENIENCE AND PETRO LLC 715 Mulberry St
1615 BISHOP AVE WATERLOO, IA 50703
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION- 1615 BISHOP - 01/07/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24892 01/14/2026 02/18/2026 2026-00000288 $80.00
Less Prepayment $0.00
Total Due-p $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
aatortz, ' •• ire Rescue � ///� }r
Inspection Report t • Y/v �;5�0 /1V6 425 E.3rd street
UNI Mart-1615 Bishop AVE,BLDG 1615 Bishop Ave,Waterloo IA 50707 70 3
rt
INSPECTION DETAILS / `' ?("1.
Inspection Date Inspection Type Inspection Numbcr
01107/2026 Annual Inspection(1Yr) 16354
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
� 44 08 025
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 01130/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-01/09/2026 @ 14:34
Gas pump 91 out of service today 119/26.
BRAD BALDWIN-01109/2026 @ 14:37
•$80 annual inspection fee
BRAD BALDWIN-01/09/2026 @ 14:37
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(OS)-Cell:319-230-1224
BRAD BALDWIN-01109/2026 @ 14:37
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-0110912026 @ 14:37
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 am.-4:00 p.m."•`••Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature p
Report completed post inspection
Muhammad Samar Date: BRAD BALDWIN 0110912026
CHECKLISTS
GENERATED ON 1/926,2:40 PM 1 OF 7
Additional Codes
Status Code Description
Fail 102.4- Application of building code.
OThe design and construction of new structures shall comply Location: Back storage above walk-in cooler
with the International Building Code , and any alterations, Comments: Licensed plumbing contractor shall obtain permit and
additions, changes in use or changes in structures required inspection of water heater installed.
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
1
4j ..opr-.«..........:,
•
• w.1 �'k
•
• r
d t
4
Fail 5003.5 - Hazard identification signs.
Unless otherwise exempted by the fire code official, visible Location: Outdoor propane cabinet
hazard identification signs as specified in NFPA 704 for the Comments: Replace missing hazard identification signage.
specific material contained shall be placed on stationary
containers and above-ground tanks and at entrances to
locations where hazardous materials are stored, dispensed,
used or handled in quantities requiring a permit and at
specific entrances and locations designated by the fire code
official.
GENERATED ON 1/9/26, 2:40 PM 2 OF 7
Electrical Safety
S;d!b"' Code Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Cabinet outlet under microwave
Identified electrical hazards shall be abated.Identified Comments:Replace damaged outlet.
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
44 It
GENERATED ON 1/9/26,2:40 PM 3 OF 7
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Kitchen,below food openings
Identified electrical hazards shall be abated.Identified Comments:Remove(2)cord ground prongs broke off in outlet.
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
•
GENERATED ON 1/9/26,2:40 PM 4 OF 7
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Back storage room
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or Comments:Remove storage from within 36"in front of electric
less,and Section 110.33 of NFPA 70 for electrical equipment panels,maintain clearance at all times.
rated over 1,000 volts,The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
•
dItEri
iigi+
ij
F 1,
ti.
GENERATED ON 1/9/26,2:40 PM 5 OF 7
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Storage behind kitchen
for permanent wiring and shall be listed and labeled in Comments:Remove black cord from above concealed area(drop
accordance with UL 817.Extension cords and flexible ceiling).
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
•
. 1'.
e
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Kitchen
for permanent wiring and shall be listed and labeled in Comments:Remove white multi-plug cord to TV,would approve to
accordance with UL 817.Extension cords and flexible replace with properly mounted power strip with manual reset.
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Portable Fire Extingusihers
5 vus cc.4, Description
Fail 906.7-Hangers and brackets.
Hand-held portable fire extinguishers,not housed in cabinets, Location:Kitchen
shall be installed on the hangers or brackets supplied. Comments:Class K extinguisher shall be properly mounted on wall
Hangers or brackets shall be securely anchored to the bracket,currently sitting on ground.
mounting surface in accordance with the manufacturer's
installation instructions.
GENERATED ON 1/9/26,2:40 PM 6 OF 7
r'o Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
7OF7
GENERATED ON 1/9R6,2:40 PM