COMMERCIAL FIRE INSPECTION - 617 SYCAMORE- 01/15/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
8735 01/21/2026 02/25/2026 2026-00000297 $80.00
Less Prepayment $0.00
Total Due -- $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
j,�� Inspection Report C6t)
425 E.3rd Street
Sycamore Convienence Store-617 Sycamore ST,BLDG 617 Sycamore St-STE 619
Sycamore,Waterloo IA 50703
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
01/15/2026 Annual Inspection(1Yr) 16140
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
N/A
SUMMARY OF INSPECTION
C 32 8 ® 36
Passed codes c.oci_:s Ni
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 02106/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-01115/2026 @ 15:32
$80 annual inspection fee
BRAD BALDWIN-0111512026 @ 15:32
Fire extinguishers due annually serviced March 2025
BRAD BALDWIN-01/1612026 @ 08:16
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-01116/2026 @ 08:16
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-01/16/2026 @ 08:16
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature 1 �
Report completed post inspection
(Sarah)2025
Date: BRAD BALDWIN 01116/2026
CHECKLISTS
1 OF 6
GENERATED ON 1/16/26,8:18 AM
General Housekeeping
Li,-:, Descript,en
Fail 305.1-Clearance from ignition sources.
Clearance between ignition sources,such as luminaires, Location:Basement water heater
heaters,flame-producing devices and combustible materials, Comments:Remove storage from within 36"of water heater,maintain
shall be maintained in an approved manner. clearance at all times.
\ \
tc
f
i ¢ ' 1� =� `
i
6
Additional Codes
� Descrii;=yen
Fail 5303.5.3-Securing compressed gas containers,cylinders
and tanks. Location:Basement
Compressed gas containers,cylinders and tanks shall be Comments:All tanks,empty or full shall be chained up to avoid tip
secured to prevent falling caused by contact,vibration or over
seismic activity.Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers,cylinders and tanks to a fixed object
with one or more restraints.2.Securing containers,cylinders 1
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers,cylinders or tanks.
3.Nesting of compressed gas containers,cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if
dislodged,do not obstruct the required means of egress.
4.Securing of compressed gas containers,cylinders and
tanks to or within a rack,framework,cabinet or similar
assembly designed for such use.Exception:Compressed gas
containers,cylinders and tanks in the process of
examination,filling,transport or servicing.
Fail 603.9.1-Listed and labeled.
Only listed and labeled portable,electric space heaters shall Location:Behind both liquor and tobacco side register counters.
be used.
Comments:Provide documentation of listing and labeling of heater
for use in commercial space or remove from building.
GENERATED ON 1/16/26,8:18 AM
2 OF 6
Electrical Safety
i Description
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Liquor side(back storage)
prohibited.Approved covers shall be provided for all switch Comments:Install bulb in open light socket to avoid shock hazard
and electrical outlet boxes.
l;
f
I'
({
\ J.:."14411111111111'.' R'e:al34-'''..-' °-:'2'
ti i rN�i`o ,,eax `O`
,
I
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Tobacco side(back storage)
prohibited.Approved covers shall be provided for all switch Comments:Provide plug for opening in box
and electrical outlet boxes.
1Y
• I v 14. y1+'.
,' N m.- \. ' '
e `
r
c
\ . \ „ti- j:-.
30F6
GENERATED ON 1/16/26,8:18 AM
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Basement
equipment shall be provided in accordance with Section Comments:Storage shall be removed within 36"in front of and 30"in
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or width of electrical equipment(both sides of stairs).Clear storage in
less,and Section 110.33 of NFPA 70 for electrical equipment direct path of access to electric equipment for firefighters.
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
'ti I
i J;
vg kii
/ .
•
:4T
s # .
,. V jr'-
* ii'
......,
V
` �, t . �' '
GENERATED ON 1/16/26,8:18 AM
4 OF 6
Fail 603.5.2-Application and usePower supply.
Relocatable power taps and current taps shall be directly Location:Tobacco side(behind display shelf)
connected to a permanently installed receptacle.Exceptions: Comments:Power strip shall be plugged directly to wall outlet,
1.Where approved for use in a Group A occupancy or in a currentlyplugged to brown extension cord.Extension cord shall not
meeting room in a Group B occupancy,not more than five p gg
be used as permanent wiring.
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2.Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
POP
o
r
Portable Fire Extingusihers
Description
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:Liquor side near back storage room
maintained in accordance with this section and NFPA 10. Comments:Class K extinguisher for old kitchen shall be serviced or
Exceptions:1.The distance of travel to reach an extinguisher removed from building.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
SOF6