COMMERCIAL FIRE INSPECTION - 205 W 4TH ST - 01/15/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE # CHARGES
24382 01/21/2026 02/25/2026 2026-00000298 $80.00
Less Prepayment $0.00
Total Due —+ $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
ads sit
.„„0 Waterloo Fire Rescue
®� Inspection Report 425 E.3rd Street
Ariz Restaurant-205 W 4th ST,BLDG 205 W 4th St,Waterloo IA 50702
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
0111512026 Annual Inspection(1Yr) 19974
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 58 u 13 ® 10
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 0211112026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-01116/2026 @ 08:45
•$80 annual inspection fee
BRAD BALDWIN-01116/2026 @ 08:45
Fire extinguishers due annually serviced July 2026
BRAD BALDWIN-01116/2026 @ 09:23
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-01/16/2026 @ 09:23
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-0111612026 @ 09:23
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
-BO
Aurion Redding Date: _ BRAD BALDWIN 0111612026
CHECKLISTS
1oFa
GENERATED ON 1/16/26,9:26 AM
Additional Codes
Sta'.:i: Code Description
Fail 313.1-General.
Fueled equipment including,but not limited to,motorcycles, Location:Kitchen storage
mopeds,lawn-care equipment,portable generators and Comments:Remove motorcycle from building
portable cooking equipment,shall not be stored,operated or
repaired within a building.Exceptions:1.Buildings or rooms
constructed for such use in accordance with the International
Building Code.2.Where allowed by Section 314.3.Storage of
equipment utilized for maintenance purposes is allowed in
approved locations where the aggregate fuel capacity of the
stored equipment does not exceed 10 gallons(38 L)and the
building is equipped throughout with an automatic sprinkler
system installed in accordance with Section 903.3.1.1.
.sr11111111/1
r
•
\1
1
Fail 610.1.2-Maintenance.
The lint trap,mechanical and heating components,and the Location:Clothes dryer
exhaust duct system of a clothes dryer shall be maintained in
Comments:Provide documentation of dryer vent cleaning from
accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that appliance to exterior of building.
prevents the exhaust of air and products of combustion.
GENERATED ON 1/16/26.9:26 AM
2 OF 8
Fail 807.2-Combustible decorative materials.
In Groups A,B,E,I,M and R-1 and in dormitories in Group R- Location:By old pool exit
2,curtains,draperies,fabric hangings and other similar Comments:Provide documentation of proper fire rating of curtains
combustible decorative materials suspended from walls or hanging from Ceiling.
ceilings shall comply with Section 807.3 and shall not exceed
10 percent of the specific wall or ceiling area to which such
materials are attached.Fixed or movable walls and partitions,
paneling,wall pads and crash pads applied structurally or for
decoration,acoustical correction,surface insulation or other
purposes shall be considered to be interior finish,shall
comply with Section 803 and shall not be considered
decorative materials or furnishings.Exceptions:1.In
auditoriums in Group A,the permissible amount of curtains,
draperies,fabric hangings and similar combustible decorative
material suspended from walls or ceilings shall not exceed 75
percent of the aggregate wall area where the building is
equipped throughout with an approved automatic sprinkler
system in accordance with Section 903.3.1.1,and where the
material is installed in accordance with Section 803.15 of the
International Building Code.2.In Group R-2 dormitories,
within sleeping units and dwelling units,the permissible
amount of curtains,draperies,fabric hangings and similar
decorative materials suspended from walls or ceilings shall
not exceed 50 percent of the aggregate wall areas where the
building is equipped throughout with an approved automatic
sprinkler system installed in accordance with Section 903.3.1.
3.In Group B and M occupancies,the amount of combustible
fabric partitions suspended from the ceiling and not
supported by the floor shall comply with Section 807.3 and
shall not be limited.4.The 10-percent limit shall not apply to
curtains,draperies,fabric hangings and similar combustible
decorative materials used as window coverings.
Fail 807.2-Combustible decorative materials.
In Groups A,B,E,I,M and R-1 and in dormitories in Group R- Location:By pool table
2,curtains,draperies,fabric hangings and other similar Comments:Provide documentation of proper fire rating of curtains
combustible decorative materials suspended from walls or hanging from ceiling.
ceilings shall comply with Section 807.3 and shall not exceed
10 percent of the specific wall or ceiling area to which such
materials are attached.Fixed or movable walls and partitions,
paneling,wall pads and crash pads applied structurally or for
decoration,acoustical correction,surface insulation or other
purposes shall be considered to be interior finish,shall
comply with Section 803 and shall not be considered
decorative materials or furnishings.Exceptions:1.In
auditoriums in Group A,the permissible amount of curtains,
draperies,fabric hangings and similar combustible decorative
material suspended from walls or ceilings shall not exceed 75
percent of the aggregate wall area where the building is
equipped throughout with an approved automatic sprinkler
system in accordance with Section 903.3.1.1,and where the
material is installed in accordance with Section 803.15 of the
International Building Code.2.In Group R-2 dormitories,
within sleeping units and dwelling units,the permissible
amount of curtains,draperies,fabric hangings and similar
decorative materials suspended from walls or ceilings shall
not exceed 50 percent of the aggregate wall areas where the
building is equipped throughout with an approved automatic
sprinkler system installed in accordance with Section 903.3.1.
3.In Group B and M occupancies,the amount of combustible
fabric partitions suspended from the ceiling and not
supported by the floor shall comply with Section 807.3 and
shall not be limited.4.The 10-percent limit shall not apply to
curtains,draperies,fabric hangings and similar combustible
decorative materials used as window coverings.
TOES
GENERATED ON 1/1626.9:26 AM
Fire Service Features
States Code Description
Fail 509.2 - Equipment access.
OApproved access shall be provided and maintained for all fire Location: Near office
protection system equipment to permit immediate safe Comments: Remove items blocking access to fire alarm pull station
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
• 11111
VIONIMINIIIIII
-, _-r-
I _ _
64114
r -
*it,. k . ,j,,
y }L
EI .
Iffif 'IIti 4 - Z 1
b ; i .\
t1 114 --''
IA
i .
GENERATED ON 1/16/26, 9:26 AM
4 OF 8
Electrical Safety
slat Cade Description
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Electric panel by laundry appliances
equipment shall be provided in accordance with Section Comments:Remove storage below electric panels,maintain 36"
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or clearance at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
Fail 603.5-Relocatable power taps and current taps.Multiplug
adapters. Location:Between two bars by"Grand Marnier"neon sign
Multiplug adapters,such as cube adapters,unfused plug Comments:Remove multi-plug adapter,would approve use of
strips or any other device not complying with NFPA 70 shall properly mounted power strip with manual reset for light duty electric
be prohibited.The construction and use of current taps and only.
relocatable taps shall be in accordance with NFPA 70 and this
code.
3:43 ..d
tiNI mac..
i
i rn
I fill'��dt�.
41a a
-3 fi
79..011
5 OF 8
GENERATED ON 1/16/26,9:26 AM
Fail 603.5-Relocatable power taps and current taps.Multiplug
adapters. Location:Kitchen near smoker
Multiplug adapters,such as cube adapters,unfused plug Comments:Remove multi-plug adapter,would approve properly
strips or any other device not complying with NFPA 70 shall mounted power strip with manual reset for light duty electric only.
be prohibited.The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
•
-i
4,
t ; '* :
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:North side window"Open"sign by bar
for permanent wiring and shall be listed and labeled in
Comments:Remove multi-plug extension cord to sign,would
accordance with UL 817.Extension cords and flexible approve sign plugged to properly mountedpower stripwith manual
cordsshall not be affixed to structures,extended through pPp gg p p y
reset.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:By"Pure Leaf"beverage fridge
for permanent wiring and shall be listed and labeled in Comments:Remove green multi-plug extension cord.
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Fireplace
for permanent wiring and shall be listed and labeled in Comments:Remove fireplace from extension cord,appliance shall
accordance with UL 817.Extension cords and flexible plug directly to wall outlet.
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 1/16/26,9:26 AM 6 OF 8
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Kitchen small chest freezer
for permanent wiring and shall be listed and labeled in Comments:Remove freezer from extension cord,freezer shall plug
accordance with UL 817.Extension cords and flexible directly to wall outlet
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
Status Code Deseripticn
Fail 606.3.3-Cleaning.
OHoods,grease-removal devices,fans,ducts and other Location:Kitchen hood exhaust
appurtenances shall be cleaned at intervals as required by Comments:Exhaust system cleaning 146 days past due as of 1116126.
Sections 606.3.3.1 through 606.3.3.3. Provide cleaning and report to be uploaded to Compliance Engine
with any deficiencies corrected.
GENERATED ON 1/16/26,9:26 AM 7 OF 8