COMMERCIAL FIRE INSPECTION - 301 E 4TH ST - 01/16/2026 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE # CHARGES
14737 01/21/2026 02/25/2026 2026-00000301 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
14737 (6a
,,ER Waterloo Fire Rescue
D Inspection Report 425 E.3rd Street
El Patron-301 E 4th ST,BLDG 301 E 4th St,Waterloo IA 50703
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
01/1612026 Annual Inspection(1Yr) 16195
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
047 G6 024
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 0210612026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-01/16/2026 @ 15:07
$80 annual inspection fee
BRAD BALDWIN-01/16/2026 @ 15:30
Provide document verifying back room is not open to public,document shall be signed and dated,email document to inspector.
BRAD BALDWIN-01/1612026 @ 15:14
Fire extinguishers due annually serviced February 2026.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Migeul Palomares Date: BRAD BALDWIN 01/16/2026
CHECKLISTS
1 OF
GENERATED ON 1/16/26,3:35 PM
Additional Codes
Status Code Description
Fail 5303.5.3-Securing compressed gas containers,cylinders
Jand tanks. Location:Bar by beet taps
Compressed gas containers,cylinders and tanks shall be Comments:Secure compressed gas cylinders with chain to avoid tip
secured to prevent falling caused by contact,vibration or over.
seismic activity.Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers,cylinders and tanks to a fixed object
with one or more restraints.2.Securing containers,cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers,cylinders or tanks.
3.Nesting of compressed gas containers,cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if
dislodged,do not obstruct the required means of egress.
4.Securing of compressed gas containers,cylinders and
tanks to or within a rack,framework,cabinet or similar
assembly designed for such use.Exception:Compressed gas
containers,cylinders and tanks in the process of
examination,filling,transport or servicing.
Fail 603.1.1 Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment, Location:Kitchen(Panini maker)
wiring,devices and appliances shall be tested;and listed by
an approved agency and labeled;and installed,used and Comments:Remove panini maker from power strip,appliance shall
maintained in accordance with NFPA 70 and all instructions be plugged directly to wall outlet.
included as part of such listing.
Fail 603.1.1-Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment, Location:Kitchen(Oven)
wiring,devices and appliances shall be tested;and listed by
an approved agency and labeled;and installed,used and Comments:Remove oven plugged to power strip,appliance shall be
maintained in accordance with NFPA 70 and all instructions plugged directly to wall outlet.
included as part of such listing.
Fail 606.3.1-Ventilation system.
The ventilation system in connection with hoods shall be Location:Kitchen exhaust hood
operated at the required rate of air movement,and grease
filters listed and labeled in accordance with UL 3046 shall be Comments:Repair or replace damaged hood filters and close gaps in
filters,filters not in place cause more grease in ductwork and on in place where equipment under a kitchen grease hood is
used. cables for fire supression.
GENERATED ON 1/16/26,3:35 PM
2 OF 4
Electrical Safety
Status Code Description
Fail 603.5.2 - Application and usePower supply.
ORelocatable power taps and current taps shall be directly Location: Kitchen near dishwashing station
connected to a permanently installed receptacle. Exceptions: Comments: Power strip shall be plugged directly to wall outlet,
1. Where approved for use in a Group A occupancy or in a extension cord allowed for temporary use only, not everyday all day
meeting room in a Group B occupancy, not more than five
use.
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
lelliir-e i, _. _
s. 'Y f( ifa.
POOMKav ,;
ma
,t
- r . • .: i i*,4,......"-.i.-.,..w _
I
I
e i .4
Fail 603.5.3 - Installation.
ORelocatable power tap cords shall not extend through walls, Location: Kitchen next to oven
ceilings, floors, under doors or floor coverings, or be subject Comments: Properly support or mount power strip to wall, currently
to environmental or physical damage. hanging by wires.
I
GENERATED ON 1/16/26, 3:35 PM 3 OF 4