COMMERCIAL FIRE INSPECTION - 422 COMMERCIAL ST -
01 /20/2026
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 20,000
OCCUPANCY FEE
Total Price
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
10504
01/27/2026
03/03/2026
2026-00000313
$100.00
Less Prepayment
Total Due -�
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
\co/ io501-k
Waterloo Fire Rescue
Inspection Report
Community Bank & Trust - 422 Commercial ST, BLDG 422 Commercial St, Waterloo
IA 50701-1318
INSPECTION DETAILS
Inspection Date
0112012026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
1307
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
0 50 0 26
Passed codes Failed codes
NEXT STEPS
0 14
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 01120/2026 @ 13:14
$100 annual inspection fee
BRAD BALDWIN - 01120/2026 @ 14:49
Main floor vault - Space heater noted unplugged. Heater shall be properly listed and labeled for commercial use.
BRAD BALDWIN - 01/21/2026 @ 07:27
Fire alarm inspection due 2/5/26. Contractor shall upload report with deficiencies corrected to Compliance Engine.
BRAD BALDWIN - 01121/2026 @ 12:44
Reinspection Date
02/20/2026
Emergency egress lights and exit signs: Per occupancy, non occupied basement used as storage allows exit sign and egress lights removed as not
required. Recommend retaining and maintaining exit signs above exit doors for safety of persons in basement in time of Toss of power and lights or
emergency to find exits.
BRAD BALDWIN - 01121/2026 @ 12:44
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 01121/2026 @ 12:45
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 1/21/26, 12:48 PM 1 OF 9
Brian Riek (2025) Date: BRAD BALDWIN 01/2112026
CHECKLISTS
GENERATED ON 1/21/26, 12:48 PM 2 OF 9
Emergency Equipment
Status Code
Fail
Fail
Fail
Fail
Fail
Fail
Fail
Fail
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Main stairwell (high bay) egress lights
Comments: Provide documentation of testing emergency egress
lights including repairs made to maintain working properly,
documentation shall include signature and date of responsible
person.
Location: Main stairwell - Main floor landing
Comments: Repair or replace egress lights that failed to illuminate
during test
Location: Back stairwell - 2nd to 3rd floor landing
Comments: Repair or replace egress lighting that failed to illuminate
during test.
Location: Back stairwell - 1st to 2nd floor landing
Comments: Repair or replace egress lighting that failed to illuminate
during test.
Location: Back entrance from drive-thru
Comments: Repair or replace egress lighting that failed to illuminate
during test.
Location: 3rd floor elevator room
Comments: Repair or replace egress light that failed to illuminate
during test.
Location: Back entrance stairwell basement landing
Comments: Repair or replace egress light that failed to illuminate
during test.
Location: Basement
Comments: All emergency egress lights shall be repaired or replaced
to remain illuminated during test. Refer to notes for further details.
Location: 2nd floor training room
Comments: Repair or replace (north wall) exit sign and egress lights
that failed to illuminate during test.
Location: Main exit vestibule
Comments: Repair or replace exit signs (2) that failed to illuminate
during test.
GENERATED ON 1/21/26, 12:48 PM 3 OF 9
Fail
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required Toad for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
General Housekeeping
Status Code
Fail
315.3.1- Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
Fire Sprinkler System
Status Code
Fail
5.2.1 - Annual sprinkler system inspection
Sprinklers shall be inspected at least annually by licensed
contractor
Location: Main stairwell - Main floor landing
Comments: Repair or replace exit sign that failed to illuminate during
test
Location: Basement
Comments: All exit signs shall be repaired or replaced to remain
illuminated during test. Refer to notes for further details.
Description
Location: Basement marketing storage room
Comments: Remove storage within 24" of ceiling not including along
walls.
Description
Comments: Provide annual inspection report with any deficiencies
corrected, contractor must upload report to Compliance Engine.
Currently 6 days past due as of 1/20/26.
GENERATED ON 1/21/26, 12:48 PM 4 OF 9
Electrical Safety
Status Code
Fail
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Exterior room south of drive-thru
Comments: Replace missing outlet cover
Location: Basement men's bathroom closet
Comments: Provide cover for open junction box exposing wire
connections
Location: Basement storage room
Comments: Provide cover for open junction box exposing wire
connections above shelving
GENERATED ON 1/21/26, 12:48 PM
5 OF 9
Fail 603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Fail 603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Fail
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Fail 603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Location: Basement furnace storage area
Comments: Provide cover for open junction box exposing wire
connections
Location: Main lobby electric panels near tellers counter
Comments: Remove paintings covering panels, maintain clear access
at all times.
Location: Unoccupied office near Sheena (2nd floor)
Comments: Properly support or mount power strip to avoid hanging
by wires.
Location: Lobby TV
Comments: Properly mount power strip to avoid hanging by wires.
GENERATED ON 1/21/26, 12:48 PM
6 OF 9
Fail
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Fire Resistant Construction Maintenance
Status Code
Fail
Fail
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: Teller's counter
Comments: Properly support or mount power strip to avoid hanging
by wires
Description
Location: Double fire doors near Tina Hummels office
Comments: Repair or replace doors that failed to self shut and latch
today.
Location: Back stairwell - 3rd floor landing
Comments: Repair or replace door that failed to self latch today.
GENERATED ON 1/21/26, 12:48 PM
7 OF 9
Portable Fire Extingusihers
Status Code
Fail 906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Additional Codes
Status Code
Fail 912.7 - Inspection, testing and maintenance.
Fire department connections shall be periodically inspected,
tested and maintained in accordance with NFPA 25. Records
of inspection, testing and maintenance shall be maintained.
Description
Location: All of building
Comments: Provide annual service to all fire extinguishers, currently
past due.
Description
Location: South of drive thru (Park Ave) side
Comments: Replace missing FDC cap
GENERATED ON 1/21/26, 12:48 PM