COMMERCIAL FIRE INSPECTION - 210 E TOWER PARK DR -
01 /21 /2026
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 100,000
Total Price
$600.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
10758
01/27/2026
03/03/2026
2026-00000312
$600.00
Less Prepayment
Total Due —+
City of Waterloo
$0.00
$600.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
bto l 015t
Waterloo Fire Rescue
Inspection Report
Sam's Club - 210 E Tower Park DR, BLDG 210 E Tower Park Dr, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
01/21/2026
Inspection Type
Annual Inspection (1Yr)
425 E. 3rd Street
Inspection Number
18892
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A NIA N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
058
Passed codes
NEXT STEPS
0 14
Failed codes
7
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 01/2112026 @ 15:37
$600 annual inspection fee
BRAD BALDWIN - 01/22/2026 @ 08:02
Fire extinguishers due annually serviced in March 2026
BRAD BALDWIN - 01/22/2026 @ 08:26
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 01/22/2026 @ 08:26
Reinspection Date
02112/2026
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 01/22/2026 @ 08:26
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 01122/2026 @ 08:27
• Request of specific time on scheduled inspection date or change of inspection date shall be made by business representative prior to scheduled
inspection date. Failure to request time or change of date will result in failed inspection.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 1/22/26, 8:29 AM 1 OF 8
Mike Ahmann - Fresh Manager (2026) Date: BRAD BALDWIN 01/22/2026
CHECKLISTS
Means of Egress
Status Cods
Fail
1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Emergency Equipment
Status Code
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Front maintenance closet
Comments: Exit door to exterior failed to open today. Repair or
replace door, replacing door requires obtaining permit and
inspections.
Description
Location: Emergency egress lighting
Comments: Provide documentation of testing all egress lighting in
building including repairs made to maintain working properly,
documentation shall include signature and date of responsible
person.
Location: Exit signs
Comments: Provide documentation of testing all exit signs in
building including repairs made to maintain working properly,
documentation shall include signature and date of responsible
person.
GENERATED ON 1/22/26, 8:29 AM 2 OF 8
Fire Sprinkler System
Status Code
Fail
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
Description
Location: Demo Room
Comments: Sprinkler escutcheon shall be tight to ceiling.
GENERATED ON 1/22/26, 8:29 AM 3 OF 8
Fire Service Features
Status Code
Fail
Fail
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Description
Location: Tire center "Sprinkler Riser Room"
Comments: Remove storage from riser room. No storage shall be
kept in room.
Location: Tire center
Comments: Remove obstructions (carts) blocking access to Fire
Hose Connection, maintain clear access at all times.
GENERATED ON 1/22/26, 8:29 AM
4 OF 8
Fail
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Additional Codes
Status Code
Fail
Fail
603.1- General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
913.5 - Testing and maintenance.
Fire pumps shall be inspected, tested and maintained in
accordance with the requirements of this section and NFPA
25. Records of inspection, testing and maintenance shall be
maintained.
Electrical Safety
Status Code
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Receiving back hallway
Comments: Remove obstructions (storage) blocking access to Fire
Hose Connection, maintain clear access at all times.
Description
Location: HMS kitchen
Comments: Remove rice cooker from power strip. Appliance shall
plug directly to permanent wall receptacle.
Location: Fire pump
Comments: Provide corrections regarding report #8398157 on
Compliance Engine. Report of corrections made shall be uploaded to
Compliance Engine.
s®
Description
Location: "Fresh Office"
Comments: Replace missing outlet cover behind fridge.
GENERATED ON 1/22/26, 8:29 AM 5 OF 8
Fire Resistant Construction Maintenance
Status Code
Fail
Fail
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
705.2.6 - Testing.
Horizontal and vertical sliding and rolling fire doors shall be
inspected and tested annually to confirm proper operation
and full closure. Records of inspections and testing shall be
maintained.
Description
Location: Cash room door
Comments: Carefully remove tape and/or paint covering fire rating
tags without altering tag information.
Location: IT Room
Comments: Carefully remove tape and/or paint covering fire rating
tags without altering tag information.
Location: Tire center
Comments: Provide documentation of annual inspection of fire door
drop testing.
GENERATED ON 1/22/26, 8:29 AM 6 OF 8
Portable Fire Extingusihers
Status Code
Fail
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Description
Location: Tire center
Comments: Annually serviced fire extinguisher shall be hung on wall
bracket. Currently sitting in shopping cart.