COMMERCIAL FIRE INSPECTION - 2834 ANSBOROUGH AVE -
01 /22/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
REINSPECTION 1
$100.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
20752
01/27/2026
03/03/2026
2026-00000308
$100.00
Less Prepayment
Total Due —+
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Hy-Vee - 2834 Ansborough AVE, BLDG 2834 Ansborough Ave, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
01122/2026
Lead lnspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
16345
Shift Station Unit
N/A NIA N/A
SUMMARY OF INSPECTION
55 12 ® 9
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 01/23/2026 @ 13:57
$100 annual inspection fee
BRAD BALDWIN - 01/23/2026 @ 14:47
Reinspection Date
02/13/2026
Corrected during inspection: (1) Chained loose compressed gas tanks in mezzanine. (2) Repaired Club Room electric room fire door to self shut and
latch. (3) Removed obstructions to clear aisle space in back storage area, maintain minimum 36" in aisle width.
BRAD BALDWIN - 01/23/2026 @ 14:52
Generator test report
BRAD BALDWIN - 01/23/2026 @ 14:53
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
GENERATED ON 1/23/26, 2:59 PM 1 OF 6
BRAD BALDWIN - 01123/2026 @ 14:53
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 0112312026 @ 14:53
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature
No signature
Report completed post inspection
Inspector signature
CJ McBreen District Store Director 2026 Date: BRAD BALDWIN
CHECKLISTS
Means of Egress
Status Code Description
Fail
1104.16.5.1 - Examination.
Fire escape stairways and balconies shall be examined for
structural adequacy and safety in accordance with Section
1104.16.5 by a registered design professional or others
acceptable to the fire code official every 5 years, or as
required by the fire code official. An inspection report shall be
submitted to the fire code official after such examination.
Emergency Equipment
Status Code
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
01123/2026
Location: Fire escape (5 year inspection)
Comments: Provide inspection by design professional and report
including deficiencies corrected to compliance engine of fire escape.
Currently 268 days past due.
Description
Comments: Provide documentation of testing all emergency egress
lighting in building including repairs made to maintain working
properly, documentation shall include signature and date of
responsible person.
Comments: Provide documentation of testing all exit signs in
building including repairs made to maintain working properly,
documentation shall include signature and date of responsible
person.
GENERATED ON 1/23/26, 2:59 PM
2 OF 6
Additional Codes
Status Code
Fail
Fail
3207.3 - Pile dimension and height limitations.
Pile dimensions, the maximum permissible storage height
and pile volume shall be in accordance with Table 3206.2.
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
Description
Location: Back storage area
Comments: Remove storage below 15ft, refer to fire sprinkler riser
placard for allowed storage height.
Location: Back storage
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
GENERATED ON 1/23/26, 2:59 PM
3 OF 6
Electrical Safety
Status Code
Fail 603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Fail 603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Description
Location: Meat bunker
Comments: Outlet below missing cover.
Location: Near Customer Service counter
Comments: Remove extension cord behind video board.
GENERATED ON 1/23/26, 2:59 PM
4 OF 6
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
Status Code
Fail
606.3.3 - Cleaning.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
Fire Resistant Construction Maintenance
Status Code
Fail
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Portable Fire Extingusihers
Status Code
Location: Printer near customer service counter
Comments: Remove printer from extension cord. Extension cords
allowed for temporary use, appliance shall plug to wall outlet.
Description
Location: Kitchen exhaust hood
Comments: Provide corrections to deficiencies (6) noted in
Compliance Engine per Proshield Fire & Safety. Contractor shall
upload corrections report to Compliance Engine.
Description
Location: Club Room Elevator Room
Comments: Repair or replace door that failed to self shut and latch.
Description
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.1n Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Location: Club Room "Comms Room"
Comments: Provide annual service to extinguisher, currently past
due.
Fail
906.5 - Conspicuous location.
Portable fire extinguishers shall be located in conspicuous
locations where they will have ready access and be
immediately available for use. These locations shall be along
normal paths of travel, unless the fire code official determines
that the hazard posed indicates the need for placement away
from normal paths of travel.
Location: Back storage mezzanine
Comments: Relocate fire extinguisher behind refrigerant tanks to
maintain ready access for immediate use.