COMMERCIAL FIRE INSPECTION - 626 SYCAMORE ST -
01 /27/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24658
01/30/2026
03/06/2026
2026-00000318
$80.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Pryme Tyme - 626 Sycamore ST, BLDG 626 Sycamore St, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
01/27/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
425 E. 3rd Street
Inspection Number
20185
Other Inspectors
N/A
Shift
NIA
Station
NIA
Unit
N/A
SUMMARY OF INSPECTION
� 41 ® 14 ® 24
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 01/28/2026 @ 14:56
• $80 annual inspection fee
BRAD BALDWIN - 01/28/2026 @ 14:56
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
02/1912026
BRAD BALDWIN - 01/28/2026 @ 14:57
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 01/28/2026 @ 14:57
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Rodney Lewis
CHECKLISTS
No signature
Report completed post inspection
Date: BRAD BALDWIN 01/28/2026
GENERATED ON 1/28/26, 2:59 PM OF 9
Means of Egress
Status Code
Description
Fail
1010.2.5 - Bolt locks.
Manually operated flush bolts or surface bolts are not
permitted. Exceptions: 1.On doors not required for egress in
individual dwelling units or sleeping units. 2.Where a pair of
doors serves a storage or equipment room, manually
operated edge- or surface -mounted bolts are permitted on the
inactive leaf. 3.Where a pair of doors serves an occupant load
of less than 50 persons in a Group B, F or S occupancy,
manually operated edge- or surface -mounted bolts are
permitted on the inactive leaf. The inactive leaf shall not
contain doorknobs, panic bars or similar operating hardware.
4.Where a pair of doors serves a Group B, F or S occupancy,
manually operated edge- or surface -mounted bolts are
permitted on the inactive leaf provided that such inactive leaf
is not needed to meet egress capacity requirements and the
building is equipped throughout with an automatic sprinkler
system in accordance with Section 903.3.1.1. The inactive leaf
shall not contain doorknobs, panic bars or similar operating
hardware. 5.Where a pair of doors serves patient care rooms
in Group 1-2 occupancies, self -latching edge- or surface -
mounted bolts are permitted on the inactive leaf provided that
the inactive leaf is not needed to meet egress capacity
requirements and the inactive leaf shall not contain
doorknobs, panic bars or similar operating hardware.
Location: Door to bathroom hallway
Comments: Remove slide bolt lock from door.
GENERATED ON 1/28/26, 2:59 PM
2 OF 9
Additional Codes
sinus Code
Fail
Fail
Fail
1013.1- Where required.
Exits and exit access doors shall be marked by an approved
exit sign readily visible from any direction of egress travel.
The path of egress travel to exits and within exits shall be
marked by readily visible exit signs to dearly indicate the
direction of egress travel in cases where the exit or the path
of egress travel is not immediately visible to the occupants.
Intervening means of egress doors within exits shall be
marked by exit signs. Exit sign placement shall be such that
any point in an exit access corridor or exit passageway is
within 100 feet (30 480 mm) or the listed viewing distance of
the sign, whichever is less, from the nearest visible exit sign.
Exceptions: 1.Exit signs are not required in rooms or areas
that require only one exit or exit access. 2.Main exterior exit
doors or gates that are obviously and clearly identifiable as
exits need not have exit signs where approved by the fire
code official. 3.Exit signs are not required in occupancies in
Group U and individual sleeping units or dwelling units in
Group R-1, R-2 or R-3. 4.Exit signs are not required in
dayrooms, sleeping rooms or dormitories in occupancies in
Group 1-3. 5.In occupancies in Groups A-4 and A-5, exit signs
are not required on the seating side of vomitories or openings
into seating areas where exit signs are provided in the
concourse that are readily apparent from the vomitories.
Egress lighting is provided to identify each vomitory or
opening within the seating area in an emergency.
605.1.4 - Access.
The installation of fuel -fired equipment shall be provided with
access to equipment for cleaning hot surfaces; removing
burners; replacing motors, controls, air filters, chimney and
vent connectors, draft regulators and other working parts;
and for adjusting, cleaning and lubricating parts.
605.6.1- Guard against contact.
The heating element or combustion chamber shall be
permanently guarded so as to prevent accidental contact by
persons or material.
Description
Location: Near bathrooms
Comments: Exit sign shall be turned 90 degrees to direct egress
towards alley exit between bathrooms.
Location: Basement furnace
Comments: Create clear 36" path of access to furnace from stairs.
Location: Basement (east of stairs)
Comments: Furnace cover off today, cover shall be installed and
maintained as manufactured.
GENERATED ON 1/28/26, 2:59 PM 3 OF 9
Fail 701.5 - Maintaining protection.
Materials, systems and devices used to repair or protect
breaches and openings in fire -resistance -rated construction
and construction installed to resist the passage of smoke
shall be maintained in accordance with Sections 703 through
707.
Fail 901.4.6 - Appearance of equipment.
Any device that has the physical appearance of life safety or
fire protection equipment but that does not perform that life
safety or fire protection function shall be prohibited.
Emergency Equipment
Status Code
Fail 1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Location: Bathroom hallway
Comments: Obtain permit and inspection to install rated fire door to
neighboring space, currently plywood covering door opening.
Location: Smoke detectors
Comments: All smoke detectors in building shall be maintained as
working properly. Noted detectors beeping and covers off today
1/27/26.
Description
Location: High bay egress lights
Comments: Provide documentation of testing lights including repairs
made if necessary confirming working properly. Document shall
include address, date and signed, email to inspector.
GENERATED ON 1/28/26, 2:59 PM
4 OF 9
Electrical Safety
Status Code
Fail
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.4.1- Labeling.
Doors into electrical control panel rooms shall be marked
with a plainly visible and legible sign stating "ELECTRICAL
ROOM" or similar approved wording. The disconnecting
means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident. Where buildings or structures are supplied by more
than one power source, markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or Tess for the purpose of testing the
performance of such devices.
Description
Location: Basement (west of stairs)
Comments: Install cover on box
Location: Electric panel near back entrance
Comments: Permanent signage shall installed on panel covering or
covering shall be removed. Signage shall be red with white lettering,
minimum lettering height of flinches. Laminated paper will not be
accepted.
Location: Slot machines.
Comments: Power strip shall plug directly to wall outlet, remove from
extension cord.
GENERATED ON 1/28/26, 2:59 PM 5 OF 9
Fail
Fail
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Bar
Comments: Power strip plugged to another power strip at front of bar
shall be corrected. All power strips shall plug directly to wall outlets
for Tight duty electric only.
Location: Near slot machines
Comments: Extension cord shall not be used as permanent wiring,
remove extension cord.
GENERATED ON 1/28/26, 2:59 PM
6 OF 9
Fire Resistant Construction Maintenance
Status Code
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Ceiling
Comments: Obtain permit and inspection and repair hole in ceiling.
GENERATED ON 1/28/26, 2:59 PM
7 OF 9
Portable Fire Extingusihers
Status Co!'
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.1n Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Smoke detectors (2)
Comments: Provide annual service to both extinguishers in space,
last recorded service completed December 2024.