COMMERCIAL FIRE INSPECTION - 2127 LA PORTE RD -
02/02/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 20,000
OCCUPANCY FEE
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
7995
02/03/2026
03/09/2026
2026-00000322
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Holiday Inn Express - 2127 La Porte RD, BLDG 2127 La Porte Rd, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
02/02/2026
Lead lnspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other inspectors
NATE BEUSELING
425 E. 3rd Street
Inspection Number
6754
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 41
Passed codes
NEXT STEPS
38
Failed codes
17
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 0210212026 @ 12:39
$100 annual inspection fee
BRAD BALDWIN - 02102/2026 @ 15:11
Reinspection Date
03/04/2026
Properly listed power strips shall be mounted or supported to avoid hanging by wires. Power strips are approved for light duty electric only, appliances
shall be powered as directed per manufacturers guidelines.
BRAD BALDWIN - 02/03/2026 @ 08:13
Appliance cords shall be plugged to outlets with proper allowance from furniture to avoid excessive stress to cord and plug.
BRAD BALDWIN - 02/03/2026 @ 08:36
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 02/03/2026 @ 08:36
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 02/03/2026 @ 08:36
• Request of specific time on scheduled inspection date or change of inspection date shall be made by business representative prior to scheduled
inspection date. Failure to request time or change of date will result in failed inspection.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 2/3/26, 8:43 AM 1 OF 15
Sarah Everett 2026 Date: BRAD BALDWIN 02/03/2026
CHECKLISTS
GENERATED ON 2/3/26, 8:43 AM 2 OF 15
Additional Codes
Status Code
Fail
Fail
Fail
Fail
1023.9.1- Signage requirements.
Stairway identification signs shall comply with all of the
following requirements: 1.The signs shall be a minimum size
of 18 inches (457 mm) by 12 inches (305 mm). 2.The letters
designating the identification of the interior exit stairway and
ramp shall be not less than 1112 inches (38 mm) in height.
3.The number designating the floor level shall be not less
than 5 inches (127 mm) in height and located in the center of
the sign. 4.Other lettering and numbers shall be not less than
1 inch (25 mm) in height. 5.Characters and their background
shall have a nonglare finish. Characters shall contrast with
their background, with either Tight characters on a dark
background or dark characters on a light background.
6.Where signs required by Section 1023.9 are installed in the
interior exit stairways and ramps of buildings subject to
Section 1025, the signs shall be made of the same materials
as required by Section 1025.4.
2015 IPMC 704.1.1 - Automatic sprinkler systems
Inspection, testing and maintenance of automatic sprinkler
systems shall be in accordance with NFPA 25.
315.3.3 - Equipment rooms.
Combustible material shall not be stored in boiler rooms,
mechanical rooms, electrical equipment rooms or in fire
command centers as specified in Section 508.1.5.
603.1- General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
Description
Location: Roof access
Comments: Install permanent sign in stairwell (4th floor landing)
leading to roof access. Refer to code "102.9.1.1" for signage
requirements.
Location: Sprinkler system (5 year inspection)
Comments: Provide contractor inspection report including
deficiencies corrected to Compliance Engine, currently 413 days past
due.
Location: 4th floor storage room labeled "Mechanical Room"
Comments: Remove "Mechanical Room" sign outside storage room
by #403 that does not contain mechanical equipment.
Location: Rooms including (but not limited to): 127, 204, 208, 305,
318, 319, 401
Comments: Remove microwaves and mini fridges from power strips,
appliances shall plug directly to wall outlets. Further details in notes.
GENERATED ON 2/3/26, 8:43 AM 3 OF 15
Fail
Fail
Fail
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.9.1 - Listed and labeled.
Only listed and labeled portable, electric space heaters shall
be used.
Location: "NTONPOWER" Multi -plug adapters in rooms.
Comments: Provide documentation of appliance listing. Non -listed
equipment shall be removed from use.
Location: Rooms including (but not limited to): 307, 308, 322, 400,
407, 408, 417, 426
Comments: Provide documentation of appliance listing. Non -listed
equipment shall be removed from use.
Location: Manager's Office
Comments: Provide documentation of proper listing and labeling of
commercially approved heater or remove from building.
GENERATED ON 2/3/26, 8:43 AM
4 OF 15
Fail
610.1.2 - Maintenance.
The lint trap, mechanical and heating components, and the
exhaust duct system of a clothes dryer shall be maintained in
accordance with the manufacturer&##039;s operating
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
Emergency Equipment
Status Cede
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Location: Guest and House laundry dryers
Comments: Provide documentation of cleaning of dryer vent from
appliance to the outside of the building with signature and date.
Email documentation to fire inspector.
Description
Comments: Provide documentation of testing all emergency egress
lighting in building including repairs made to maintain working
properly, documentation shall include signature and date of
responsible person.
Comments: Provide documentation of testing all exit signs in
building including repairs made to maintain working properly,
documentation shall include signature and date of responsible
person.
GENERATED ON 2/3/26, 8:43 AM 5 OF 15
General Housekeeping
Status Code
Fail
Fail
315.3.1- Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
315.3.3 - Equipment rooms.
Combustible material shall not be stored in boiler rooms,
mechanical rooms, electrical equipment rooms or in fire
command centers as specified in Section 508.1.5.
Description
Location: 3rd floor Conference Room Storage Room
Comments: Remove storage within 18 inches of sprinkler heads not
including storage along walls.
Location: Main floor "Panel Room" behind check -in counter
Comments: Remove storage from room.
GENERATED ON 2/3/26, 8:43 AM
6 OF 15
Fail
Fail
315.3.3 - Equipment rooms.
Combustible material shall not be stored in boiler rooms,
mechanical rooms, electrical equipment rooms or in fire
command centers as specified in Section 508.1.5.
315.3.3 - Equipment rooms.
Combustible material shall not be stored in boiler rooms,
mechanical rooms, electrical equipment rooms or in fire
command centers as specified in Section 508.1.5.
Location: 2nd floor "Panel Room" by elevator
Comments: Remove storage from room and remove storage outside
room obstructing clear path of access to "Panel Room"
Location: 3rd floor "Panel Room"
Comments: Remove combustible storage out of room.
GENERATED ON 2/3/26, 8:43 AM
7 OF 15
Fire Sprinkler System
Status Code
Fail 903.3.3 - Obstructed locations.
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not less
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
Fail 903.3.3 - Obstructed locations.
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not less
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
Fire Service Features
Status Code
Fail 506.2 - Key box maintenance.
The operator of the building shall immediately notify the fire
code official and provide the new key where a lock is changed
or rekeyed. The key to such lock shall be secured in the key
box.
Description
Location: Room #307
Comments: Remove paint from sprinkler head and escutcheon ring.
Location: Roof access top landing
Comments: Remove paint from sprinkler head.
Description
Location: Roof access lock
Comments: Notify Fire Department and provide key to lock to Roof
Access door for the Knox Box.
GENERATED ON 2/3/26, 8:43 AM
8 OF 15
Electrical Safety
Status Code
Fail
Fail
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Description
Location: Room #409
Comments: TV Cabinet tight to wall forcing stress to appliance cords
at outlet shall be corrected. Further details in notes.
Location: Lobby dining room
Comments: Properly mount power strip behind microwave to avoid
hanging by wires.
Location: Employee area
Comments: Remove brown multi -plug extension cord.
GENERATED ON 2/3/26, 8:43 AM
9 OF 15
Fire Resistant Construction Maintenance
Status Code
Fail 705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
Fail 705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Description
Location: Pool Equipment Room
Comments: Replace missing fire rated door seal.
Location: Room #422
Comments: Replace door by obtaining proper permit and inspection
or obtain re -certification and labeling of current door. Fire rating label
has been removed.
Location: 1st floor storage room by laundry
Comments: Repair or replace door that failed to self shut and latch.
Replacing door requires obtaining proper permit and inspection.
Location: 1st floor Elevator Room by elevator
Comments: Repair or replace door that failed to self shut and latch.
Replacing door requires obtaining proper permit and inspection.
GENERATED ON 2/3726, 8:43 AM
10 OF 15
Fail
Fail
Fail
Fail
Fail
Fail
Fail
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: Pool Equipment Room
Comments: Repair or replace door that failed to self shut and latch.
Replacing door requires obtaining proper permit and inspection.
Location: Pool Equipment Room (inner door)
Comments: Remove obstructions holding door open.
Location: 2nd floor double fire doors by elevator
Comments: Repair or replace door that failed to self shut and latch.
Replacing door requires obtaining proper permit and inspection.
Location: 2nd floor "Panel Room" by elevator
Comments: Repair or replace door that failed to self shut and latch.
Replacing door requires obtaining proper permit and inspection.
Location: 3rd floor "Ice Vending Room" by elevator
Comments: Repair or replace door that failed to self shut and latch.
Replacing door requires obtaining proper permit and inspection.
Location: Room #312
Comments: Repair or replace door that failed to self shut and latch,
drags on carpet when fully open. Replacing door requires obtaining
proper permit and inspection.
Location: 3rd floor Housekeeping (inner door)
Comments: Remove foot wedge from door.
GENERATED ON 2/3/26, 8:43 AM
11 OF 15
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: 4th floor double fire doors at elevator
Comments: Repair or replace door that failed to self shut and latch.
Replacing door requires obtaining proper permit and inspection.
Location: Employee area behind check -in counter
Comments: Remove foot wedge holding door open.
GENERATED ON 2/3/26, 8:43 AM
12 OF 15
Portable Fire Extingusihers
status Lots
Fail
Fail
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.6 - Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or
obscured from view. In rooms or areas in which visual
obstruction cannot be completely avoided, means shall be
provided to indicate the locations of extinguishers.
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Description
Location: All extinguishers
Comments: Provide annual service to all extinguishers in building,
last service recorded in October 2024.
Location: Employee break room
Comments: Remove table obstructing ready access to extinguisher.
Location: Kitchen
Comments: Extinguisher shall be properly mounted on wall bracket,
currently sitting on floor.
GENERATED ON 2/3/26, 8:43 AM
13 OF 15
Fail 906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Fail 906.8 - Cabinets.
Cabinets used to house portable fire extinguishers shall not
be locked. Exceptions: 1.Where portable fire extinguishers
subject to malicious use or damage are provided with a
means of ready access. 2.In Group 1-3 occupancies and in
mental health areas in Group 1-2 occupancies, access to
portable fire extinguishers shall be permitted to be locked or
to be located in staff locations provided that the staff has
keys.
Location: Pool Equipment Room
Comments: Extinguisher shall be properly mounted on wall bracket.
Location: Pool
Comments: Replace missing glass to cabinet.