HomeMy WebLinkAbout2034 LA PORTE RDINVOICE DATE
DUE DATE
INVOICE #
TOTAL DUE
02/03/2026
03/09/2026
2026-00000323
$200.00
Customer #: 12855
HAMPTON INN
2034 LA PORTE RD
WATERLOO, IA 50702
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 2034 LA PORTE RD -
01 /30/2026
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 3
Total Price
$200.00
CUSTOMER #
12855
BILLING DATE
DUE DATE
INVOICE #
CHARGES
02/03/2026
03/09/2026
2026-00000323
$200.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
f(1-oo cP
Waterloo Fire Rescue
Inspection Report
425 E. 3rd Street
Hampton Inn & Suites - 2034 La Porte RD, BLDG 2034 La Porte Rd, Waterloo IA
50702
INSPECTION DETAILS
Inspection Date
01130/2026
Lead inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
REINSPECTION )
Other Inspectors
NIA
Inspection Number
13671-R14
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 0 U 8
Passed codes Failed codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
Reinspection Date
02/20I2026
BRAD BALDWIN - 01130/2026 @ 15:35
$200 re -inspection fee, failure to complete corrections 1130/26. Phone call with Mitch today, remaining violations corrections are still incomplete.
BRAD BALDWIN - 0110912026 @ 13:05
$200 re -inspection fee, failure to correct deficiencies as of 8/22/25.
BRAD BALDWIN - 01/09/2026 @ 13:05
$200 Re -inspection fee for failure to correct violations on 6/23/25
BRAD BALDWIN - 01/09/2026 @ 13:05
Provide corrections to avoid re -inspection fees
BRAD BALDWIN - 01/0912026 @ 13:05
Annual inspection $235
BRAD BALDWIN - 01/09/2026 @ 13:05
Provide corrections to avoid re -inspection fees.
BRAD BALDWIN - 01/09/2026 @ 13:05
Re -inspection fee $100
BRAD BALDWIN - 01109/2026 @ 13:05
Corrections not made on fire sprinkler, standpipe, or fire alarm and no date for completion of fire door certifications.
BRAD BALDWIN - 01/09/2026 @ 13:05
Re -inspection fee $150
BRAD BALDWIN - 01109/2026 @ 13:05
Called Mitch on 4117/25 and he stated no improvement.
GENERATED ON 1/30/26, 3:38 PM 1 OF 8
BRAD BALDWIN - 0110912026 @ 13:05
Re -inspection fee $200
BRAD BALDWIN - 01109/2026 @ 13:05
annual inspection S200
BRAD BALDWIN - 01109/2026 @ 13:05
We are recommending denial of alcohol license to the City Council because of lack of progress on required certification of guest room fire doors that
were altered during construction.
BRAD BALDWIN - 0110912026 @ 13:05
$200 Re -inspection fee, failure to complete corrections as of 7122/25
BRAD BALDWIN - 01/0912026 @ 13:05
$200 re -inspection fee, failure to correct deficiencies or provide plan to make corrections as of 10/3125.
BRAD BALDWIN - 0110912026 @ 13:05
Withholding re -inspection fee today due to progress made 10124/25
BRAD BALDWIN - 0110912026 @ 13:05
$200 re -inspection fee, failure to complete corrections as of 11124125. Discussion with Cayenne on site (11/20/25) regarding lack of fire doors re-
certification report.
BRAD BALDWIN - 01/0912026 @ 13:05
$200 re -inspection fee, failure to complete corrections. Have not received report verifying fire doors and hardware. No communication received from hotel
and its representatives.
BRAD BALDWIN - 0110912026 @ 13:05
$200 re -inspection fee, failure to complete corrections. Met with Mitch from maintenance today to discuss remaining corrections, no progress made.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Cayenne Adams - Manager (2025)
CHECKLISTS
Date: BRAD BALDWIN 01130/2026
GENERATED ON 1/30R6, 3:38 PM 2 OF 8
Reinspection
Status Code
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Entire buiding
Comments: Obtain permits and inspections for all work concerning
fire door repair, replacement smoke seals, all hardware replaced.
Please see original attached email with codes concerning information
requiered for fire door hardware. Please contact Building Official
Greg Ahlhelm with questions. 319-291-4319
Location: 1st floor west stair tower door
Comments: Fire rated door altered by cutting bottom of door as
shown in picture. Either replace door by obtaining permit and
inspection or obtain architect to review door, report from architect
shall be sent to inspector.
GENERATED ON 1/30/26, 3:38 PM
3 OF 8
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Stairway Fire Door by room 330
Comments: Repair fire door. There is a gap at bottom of door. Must
completely seal
GENERATED ON 1/30/26, 3:38 PM 4 OF 8
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Entire 4th Floor Fire Doors
Comments: Repair or replace fire doors that are improperly installed.
Doors must seal all sides including top and botom to prevent
smoke/fire from inflitrating fire rated coridoor.
GENERATED ON 1/30/26, 3:38 PM
5 OF 8
Fail 704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail 704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: obtain permit and inspections
Location: Entire Second Floor
Comments: verify all removed smoke seals have been replaced on
second floor. Also 4th floor and all other smoke sweeps added to
bottom of doors must be verified as listed for fire doors and
inspected.
GENERATED ON 1/30/26, 3:38 PM
6 OF 8
Fail
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: Entire second floor guest fire doors
Comments: Install approved smoke seal in all fire door openings that
has been removed including stair doors and utility areas. Check all
other floors
Location: 1st floor hallway men's bathroom
Comments: Door failed to shut and latch from full open position.
Bottom of door drags and sticks on ground.
GENERATED ON 1/30/26, 3:38 PM 7 OF 8
Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
N►A $200.00
Invoice Number
NIA
Check Number Transaction Number
NIA NIA
GENERATED ON 1/30/26, 3:38 PM
8 OF 8