RENTAL FIRE INSPECTION -130 RAPIDS SQ - 02/04/2026
FIRE ALARM STILL DEFICIENT, FIRST NOTIFIED 11/24/2026.
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION FEE 1ST
Total Price
$50.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23806
02/04/2026
03/11/2026
2026-00000065
$50.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$50.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
BLDG 130 Rapids Sq -130 Rapids SQ, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
02104/2026
Lead inspector
JEFF SIEBEL
425 E. 3rd Street
Inspection Type Inspection Number
Residential Common Areas Inspection J REINSPECTION J 19070-R2
Other Inspectors
NIA
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 o
Passed codes
NEXT STEPS
0 2
Failed codes
Please direct questions about your Inspection to:
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org, 3199813973
GENERAL NOTES
JEFF SIEBEL - 02/0412026 @ 08:57
RE -INSPECTION FEE $50. Fire Alarm still deficient, first notified i1124125. Re -inspection fees increase each re -inspection date.
Reinspection Date
03111/2026
JEFF SIEBEL - 01/07/2026 @ 13:18
Re -inspection date is as posted on the inspection report. The rental unit's responsible personls shall contact prior to inspection date to set up time of re -
inspection. If all corrections are made before scheduled inspection, you can call to set up an earlier re -inspection. Please give the appropriate notices to
occupants of the unitls. Owner or owner's agent must be present during the re -inspections. Failure to schedule a time on the date given or failure to keep
the scheduled inspection will result in a $100.00 fee. Re -inspection fees may be assessed for re -inspections. Re -inspection fees start at $50, then $150,
and $250 for all subsequent re -inspections. All appropriate keys to gain entry to locked units shall be readily available during re -inspections.
JEFF SIEBEL - 01/07/2026 @ 13:18
Maintenance states new company coming on board and will issue corrections and post on the Compliance Engine
SIGNATURES
Contact signature
Inspector signature
Antrell Williams 02104/2026 JEFF SIEBEL
CHECKLISTS
02/04/2026
GENERATED ON 2/4/26, 9:04 AM 1 OF 3
Reinspection
Status Cod
Fail 5.2.1 - Annual sprinkler system inspection
Sprinklers shall be inspected at least annually by licensed
contractor
Fail 901.6 - Inspection, testing and maintenance.
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8 .
Description
Location: Fire sprinkler
Comments: Fire sprinkler inspection report dated 4/23125 list a
discrepancy of waterflow switch alarm sticking. Contractor must
upload corrections online to the compliance engine.
Location: Annual Fire Alarm
Comments: Provide documentation of corrections for deficiencies on
report dated 3/12/25. Horn strobes on second floor of buildinig 131
don't operate. Contractor must upload corrections online to the
compliance engine.