COMMERCIAL INSPECTION - 3225 AIRPORT BLVD - 4-18-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 20,000
OCCUPANCY FEE
Total Price
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24359
05/21/2024
06/25/2024
2024-00000382
$100.00
Less Prepayment
Total Due —�
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
CAMP RUN A MUTT, 3225 AIRPORT BLVD AIRPORT BLVD, BLDG 3225 AIRPORT BLVD,
WATERLOO /A 50703
DETAILS
Inspection Date: 04/18/2024 I Inspection Type: Annual Inspection (1Yr) ! Inspection Number: 12926 ' Shift: N/A j Station: N/A
Unit: N/A Lead Inspector: JEREMIAH VANDYKE Other Inspectors: N/A Fee: $100.00
VIOLATIONS AND COM►LIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 46 I Violations: 6 I N/A Codes: 23
STATUS CODE DESCRIPTION
FAIL 509.1 - Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems, sprinkler risers and valves, or
other fire detection, suppression or control elements fire protection systems
shall be identified for the use of the fire department. Approved signs required to
identify fire protection system equipment and equipment location shall be
constructed of durable materials, permanently installed and readily visible.
Location: Room containing Main electrical, Sprinkler riser, and Fire alarm control
panel (FACP).
FAIL 509.2 - Equipment access. Approved access shall be provided and maintained for all fire protection system
equipment to permit immediate safe operation and maintenance of such
equipment. Storage, trash and other materials or objects shall not be placed or
kept in such a manner that would prevent such equipment from being readily
accessible.
Location: Room containing Main electrical, Sprinkler riser, and Fire alarm control
panel (FACP).
Original Comment: Storage in front of electrical panel, sprinkler riser, and fire
alarm needs 36 inch clearance.
Printed on 04/18/2024 @ 15:21
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 603.4.1 - Labeling. Doors into electrical control pan& rooms shall be marked with a plainly visible
and legible sign stating "ELECTRICAL ROOM" or similar approved wording. The
disconnecting means for each service, feeder or branch circuit originating on a
switchboard or panelboard shall be legibly and durably marked to indicate its
purpose unless such purpose is clearly evident. Where buildings or structures
are supplied by more than one power source, markings shall be provided at each
service equipment location and at all interconnected electric power production
sources identifying all electric power sources at the premises in accordance with
NFPA 70.
Location: Room containing Main electrical, Sprinkler riser, and Fire alarm control
panel (FACP).
Original Comment: Durable signage on door or next door stating, "Main
Electrical, Sprinkler Riser, and FACP"
FAIL 610.1.2 - Maintenance. The lint trap, mechanical and heating components, and the exhaust duct system
of a clothes dryer shall be maintained in accordance with the manufacturer's
operating instructions to prevent the accumulation of lint or debris that prevents
the exhaust of air and products of combustion.
FAI L
Location: Clothes dryer
Original Comment: Clothes Dryer Exhaust Duct system must be cleaned from the
dryer to the outside DOCUMENTED by who and when serviced.
Chapter 14 - Inspection, Fire alarm system tested at least annually by licensed contractor
testing, and maintenance
Location: Fire alarm panel.
Original Comment: Fire alarm needs to be inspected annually and report
uploaded to our Compliance engine by fire alarm contractor after inspection.
Printed on 04/18/2024 @ 15:21
Page 2 of 4
•
STATUS CODE DESCRIPTION
FAIL Chapter 14 - Inspection, Fire alarm system tested at least annually by licensed contractor
testing, and maintenance
Location: Jack and jilt bathroom in back.
Original Comment: Missing smoke alarm needs to be replaced by Fire alarm
contractor.
GENERAL NOTES
JEREMIAH VANDYKE - 04/18/2024 @ 15:03 Fire extinguishers serviced by Prosheild August 2023.
JEREMIAH VANDYKE - 04/18/2024 @ 15:04 02/28/2024 S - (Annual) Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC.
Reviewed Compliant
JEREMIAH VANDYKE - 04/18/2024 @ 15:04 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone # 319-291-2515.
JEREMIAH VANDYKE - 04/18/2024 @ 15:04 Re -inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections & re -inspections are Monday -
Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on
a weekend, the re -inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier
re -inspection. *****Re inspection fees may be assessed for subsequent re -
inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent
re-inspections.-
JEREMIAH VANDYKE - 04/18/2024 @ 15:04 Lt. Van Dyke-jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-
1615
JEREMIAH VANDYKE - 04/18/2024 @ 15:05 Inspection Fee = $100.00 (To be mailed out by City via snail mail.)
REINSPECTION DATE
05/18/2024
Printed on 04/18/2024 @ 15:21