COMMERCIAL INSPECTION - 209 W 5TH ST - 5-7-24
7'OR BILLING INQUIRY: (319)291-4323
[ Description
Total Price
INSPECTION 20,000
OCCUPANCY FE,E
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
4749
05/21/2024
06/25/2024
2024-00000381
$100.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
RUSSELL-LAMSON, 209 W STH ST, BLDG 209 W. STH ST, WATERLOO IA 50702
DETAILS
Inspection Date: 05/07/2024 I Inspection Type: Residential Common Areas Inspection I Inspection Number: 13208 j Shift: N/A
Station: N/A ; Unit: N/A :! Lead Inspector: JEREMIAH VANDYKE Other Inspectors: N/A I Fee: $100.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 29 I Violations: 7 I N/A Codes: 0
STATUS CODE DESCRIPTION
FAIL 109.1 - Maintenance of Where any device, equipment, system, condition, arrangement, level of
safeguards. protection, or any other feature is required for compliance with the provisions of
this code, or otherwise installed, such device, equipment, system, condition,
arrangement, level of protection, or other feature shall thereafter be
continuously maintained in accordance with this code and applicable referenced
standards.
Location: Boiler inspections.
Original Comment: Boilers need to inspected by license contractor or State of
Iowa inspectors. Need to provide paperwork of boiler inspections or certification
from the State.
FAIL 1203.4 - Maintenance. Emergency and standby power systems shall be maintained in accordance with
NFPA 110 and NFPA 111 such that the system is capable of supplying service
within the time specified for the type and duration required.
Location: Both Generators
Original Comment: Need service and maintenance records of curret working
genertor and will need paperwork of new generator being installed.
Printed on 05/07/2024 @ 11:37
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 1203.4.2 - Schedule. Inspection, testing and maintenance of emergency and standby power systems
shall be in accordance with an approved schedule established upon completion
and approval of the system installation.
Location: Both generators.
Original Comment: Need service and maintenance records of current working
genertor and will need paperwork of new generator being installed.
FAIL 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
FAI L
Location: Both Generators.
Original Comment: Records of hour usage needed. And service of generators by
licensed generator contractor.
1203.4.4 - Switch Emergency and standby power system transfer switches shall be included in the
maintenance. inspection, testing and maintenance schedule required by Section 1203.4.2.
Transfer switches shall be maintained free from accumulated dust and dirt.
Inspection shall include examination of the transfer switch contacts for evidence
of deterioration. When evidence of contact deterioration is detected, the
contacts shall be replaced in accordance with the transfer switch manufacturer's
instructions.
Location: Switch maintenance of both generators.
Original Comment: Need to log records of switch maintenance for both
generators. Ask genertor installers -contractors on maintenance.
Printed on 05/07/2024 @ 11:37
Page 2of4
STATUS CODE
DESCRIPTION
FAIL 2015 IFC - Fire alarm testing Is the fire alarm system powered, operational and displaying normal operation
and maintenance (no troubles, supervisory, or alarms)?
Location: Fire alarm inspection past due.
Original Comment: Scheduled for fire alarm inspection on 5/10/2024 and
contractor will upload report to compliance engine.
FAIL 99999 - Inspection Outcome
GENERAL NOTES
JEREMIAH VANDYKE
JEREMIAH VANDYKE
JEREMIAH VANDYKE
JEREMIAH VANDYKE - 05/07/2024 @ 11:34
JEREMIAH VANDYKE - 05/07/2024 @ 11:34
JEREMIAH VANDYKE - 05/07/2024 @ 11:35
Did the inspection pass or fail?
Location: Not Provided
- 05/07/2024 @ 11:17 Fire extinguisher serviced by Superior Sept. 2023.
- 05/07/2024 @ 11:18 Clothes dryers serviced in house and last cleaned April 30th 2024.
- 05/07/2024 @ 11:34 01/03/2024 S - (Quarterly) Fire Sprinkler CONTINENTAL FIRE SPRINKLER Reviewed
Compliant
07/25/2023 S - (Annual) Standpipe CONTINENTAL FIRE SPRINKLER Reviewed Compliant
07/25/2023 S - (Annual) Fire Pump CONTINENTAL FIRE SPRINKLER Reviewed Compliant
Re -inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections & re -inspections are Monday -
Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on
a weekend, the re -inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier
re -inspection. *****Re inspection fees may be assessed for subsequent re -
inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent
re -inspections. -
Printed an 05/07/2024 @ 11:37
Page 3 of 4
GENERAL NOTES
JEREMIAH VANDYKE - 05/07/2024 @ 11:35 Lt. Van Dyke-jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-
1615
JEREMIAH VANDYKE - 05/07/2024 @ 11:36 Inspection Fee = $100.00 (To be mailed out by City via snail mail.)
REINSPECTION DATE
06/06/2024
CONTACT SIGNATURE
Kathy Nelson Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 05/07/2024 @ 11:36