COMMERCIAL INSPECTION - 325 E PARK AVE - 5-9-24
FOR BILLING INQUIRY: (319)291-4323
[ Description
REINSPECTION 1
Total Price ]
$100.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
10426
05/21/2024
06/25/2024
2024-00000375
$100.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
BLDG MASONIC TEMPLE LOFTS, 325 E PARK AVE, WATERLOO IA 50703
DETAILS
Inspection Date: 05/09/2024 Inspection Type: Residential Common Areas Inspection Inspection Number: 13263 Shift: N/A
Station: N/A j Unit: N/A j Lead Inspector: JEREMIAH VANDYKE Other Inspectors: N/A j Fee: $100.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 1 Passed Codes: 20 1 Violations: 13 N/A Codes: 6
STATUS CODE DESCRIPTION
FAIL
FAIL
1204.6 - Cords and wiring. Extension cords and temporary wiring used to connect portable generators shall
be in accordance with Section 604 and shall be provided with GFCI protection.
Location: Ballroom
Original Comment: Christmas lights are to be removed.
2015 IFC - Fire alarm testing Is the fire alarm system powered, operational and displaying normal operation
and maintenance (no troubles, supervisory, or alarms)?
Location: Fire alarm
Original Comment: Fire alarm in trouble mode. Contact Fire alarm contractor to
address.
FAIL 5303.5 - Security. Compressed gas containers, cylinders, tanks and systems shall be secured
against accidental dislodgement and against access by unauthorized personnel
in accordance with Sections 5303.5.1 through 5303.5.3.
Location: Basement "Out of Order" women's restroom.
Original Comment: Compressed tank found and either needs to be removed
from building or secured from falling over.
Printed on 05/09/2024 @ 16:52
Page 1 of 8
STATUS CODE DESCRIPTION
FAI L
FAI L
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
603.6 - Extension cords.
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: Basement electrical room
Original Comment: Electrical panel cover is off and needs to be installed back on.
Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: Youth art office.
Original Comment: Extension cord being used as permanent wiring. Discussed
installing differant outlet with 3 prong closer to desk.
FAIL 610.1.2 - Maintenance. The lint trap, mechanical and heating components, and the exhaust duct system
of a clothes dryer shall be maintained in accordance with the manufacturer's
operating instructions to prevent the accumulation of lint or debris that prevents
the exhaust of air and products of combustion.
Location: All clothes dryers in building.
Original Comment: Clothes Dryer Exhaust Duct system must be cleaned from the
dryer to the outside DOCUMENTED by who and when serviced.
Printed on 05/09/2024 @ 16:52
Page 2 of 8
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Outside of Exercise room.
Original Comment: Hole in wall needs to be repaired.
Printed on 05/09/2024 @ 16:52
Page 3of8
STATUS CODE DESCRIPTION
FAIL 704,1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Exercise room
Original Comment: Ceiling tile needs replaced.
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Entire basement.
Original Comment: Missing ceiling tiles missing that need to be replaced.
Printed on 05/09/2024 @ 16:52
Page 4 of 8
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
FAI L
Location: Ballroom
Original Comment: Ceiling tile needs replaced.
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: Laundry rooms on 3rd and 4th floor.
Original Comment: Doors are fire rated and must be self closing or have fire
alarm contractor install maglocks to hold open unless fire alarm is set off.
FAIL 901.1 - Scope. The provisions of this chapter shall specify where fire protection and life safety
systems are required and shall apply to the design, installation, inspection,
operation, testing and maintenance of all fire protection and life safety systems.
Location: 4th floor above existing concrete stairs in common area.
Original Comment: Sprinkler head pipe wrapped in a blanket that needs to b
removed.
Printed on 05/09/2024 @ 16:52
Page 5 of 8
STATUS
FAIL
!UNREAL NOTES
CODE
906.1 - Where required.
DESCRIPTION
Portable fire extinguishers shall be installed in all of the following locations: 1.In
new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies.
Exceptions: 1.In Group R-2 occupancies, portable fire extinguishers shall be
required only in locations specified in Items 2 through 6 where each dwelling unit
is provided with a portable fire extinguisher having a minimum rating of 1-A:10-
B:C. 2.In Group E occupancies, portable fire extinguishers shall be required only
in locations specified in Items 2 through 6 where each classroom is provided with
a portable fire extinguisher having a minimum rating of 2-A:20-B:C. 3. In storage
areas of Group S occupancies where forklift, powered industrial truck or powered
cart operators are the primary occupants, fixed extinguishers, as specified in
NFPA 10, shall not be required where in accordance with all of the following: 3.1.
Use of vehicle -mounted extinguishers shall be approved by the fire code official.
3.2. Each vehicle shall be equipped with a 10-pound, 40A:80B:C extinguisher
affixed to the vehicle using a mounting bracket approved by the extinguisher
manufacturer or the fire code official for vehicular use. 3.3. Not less than two
spare extinguishers of equal or greater rating shall be available on -site to replace
a discharged extinguisher. 3.4. Vehicle operators shall be trained in the proper
operation, use and inspection of extinguishers. 3.5. Inspections of vehicle -
mounted extinguishers shall be performed daily. 2.Within 30 feet (9144 mm)
distance of travel from commercial cooking equipment and from domestic
cooking equipment in Group 1-1; 1-2, Condition 1; and R-2 college dormitory
occupancies. 3.In areas where flammable or combustible liquids are stored, used
or dispensed. 4.On each floor of structures under construction, except Group R-3
occupancies, in accordance with Section 3316.1. 5.Where required by the sections
indicated in Table 906.1. 6.Special-hazard areas, including but not limited to
laboratories, computer rooms and generator rooms, where required by the fire
code official. Exception: Portable fire extinguishers are not required at normally
unmanned Group U occupancy buildings or structures where a portable fire
extinguisher suitable to the hazard of the location is provided on the vehicle of
visiting personnel.
Location: Entire building.
Original Comment: Fire extinguishers are past due and need to be serviced and
re tagged.
Printed on 05/09/2024 @ 16:52
Page 6 of 8
JEREMIAH VANDYKE - 05/09/2024 @ 16:35 03/15/2024 S - (Annual) Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC.
Reviewed Compliant
JEREMIAH VANDYKE - 05/09/2024 @ 16:35 03/15/2024 S - (Annual) Standpipe BLACKHAWK AUTOMATIC SPRINKLERS, INC. Reviewed
Compliant
JEREMIAH VANDYKE - 05/09/2024 @ 16:35 05/18/2023 S - (Annual) Fire Alarm HAWKEYE ALARM Reviewed Compliant
JEREMIAH VANDYKE - 05/09/2024 @ 16:36 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone # 319-291-2515.
JEREMIAH VANDYKE - 05/09/2024 @ 16:36
Re -inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections & re -inspections are Monday -
Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on
a weekend, the re -inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier
re -inspection. *****Re inspection fees may be assessed for subsequent re -
inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent
re-inspections.-
JEREMIAH VANDYKE - 05/09/2024 @ 16:36 Lt. Van Dyke-jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-
1615
JEREMIAH VANDYKE - 05/09/2024 @ 16:36 Inspection Fee = $100.00 (To be mailed out by City via snail mail.)
REINSPECTION DATE
06/08/2024
CONTACT SIGNATURE
Andrea Stallman Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 05/09/2024 @ 16:37
Printed on 05/09/2024 @ 16:52
Page 7 of 8