HomeMy WebLinkAbout820 E DONALD STCustomer #: 9551
GATES PARK PRO SHOP
820 E DONALD ST
WATERLOO, IA 50703
INVOICE DATE
DUE DATE
INVOICE #
TOTAL DUE
05/21/2024
06/25/2024
2024-00000359
$80.00
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 820 E DONALD ST - 3-25-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
9551
05/21/2024
06/25/2024
2024-00000359
$80.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
GATES PARK GOLF PRO SHOP, 820 E DONALD ST, BLDG 820 E DONALD ST, WATERLOO IA
50703
DETAILS
Inspection Date: 03/25/2024 I Inspection Type: Annual Inspection (1 Yr) I Inspection Number: 10119 I Shift: N/A 1 Station: N/A I
Unit: N/A Lead Inspector: JEFF SIEBEL i Other Inspectors: N/A ( Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 31 I Violations: 5 ( N/A Codes: 38
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: SE Exit Door Pro Lounge
Original Comment: Repair exit/egress light.
FAIL 305.1 - Clearance from Clearance between ignition sources, such as luminaires, heaters, flame -
ignition sources. producing devices and combustible materials, shall be maintained in an
approved manner.
Location: AHU Room in basement
Original Comment: remove gasoline powered power washer from building.
Printed on 03/29/2024 @ 10:04
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 606.3.3.3 - Records. Records for inspections shall state the individual and company performing the
inspection, a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be completed after
each inspection or cleaning and maintained.
Location: Kitchen Hood Fire Suppression
Original Comment: Provide current semi-annual kitchen hood fire suppression
inspection report with all discrepancies corrected. Currently 197 days past due.
Contractor must upload online to the compliance engine.
FAIL 610.1.2 - Maintenance. The lint trap, mechanical and heating components, and the exhaust duct system
of a clothes dryer shall be maintained in accordance with the manufacturer's
operating instructions to prevent the accumulation of lint or debris that prevents
the exhaust of air and products of combustion.
FAIL
GENERAL NOTES
Location: basement
Original Comment: provide documentation of clothes dryer vent cleaning to the
outside of the building with signature and date. may be emailed
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: Basement Boiler room
Original Comment: Boiler room fire door must completely self -close and latch.
JEFF SIEBEL - 03/28/2024 @ 10:05 annual inspection fee $80
JEFF SIEBEL - 03/29/2024 @ 10:00 hood cleaning due 4/6/24
Printed on 03/29/2024 @ 10:04
Page 2 of 3
REINSPECTION DATE
04/18/2024
CONTACT SIGNATURE
James Bolger
Signed on: 03/29/2024 @ 10:03
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 03/29/2024 @ 10:03
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
V `crr cl..b
-/I-1J
Printed on 03/29/2024 @ 10:04
Page 3 of 3