COMMERCIAL INSPECTION - 1976 FRANKLIN ST - 5-28-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
22784
06/06/2024
07/10/2024
2024-00000403
$80.00
Less Prepayment
Total Due --*
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
YESWAY, 1976 FRANKLIN ST, DLD61976 FRANKLIN ST, WATERLOO IA S0703
DETAILS
Inspection Date: 05/28/2024 ; Inspection Type: Annual Inspection (1Yr) I Inspection Number: 10820 : Shift: N/A ; Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A i Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 28 I Violations: 5 I N/A Codes: 40
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
FAI L
Location: Not Provided
603.2 - Abatement of unsafe Identified electrical hazards shall be abated. Identified hazardous electrical
conditions and electrical conditions in permanent wiring shall be brought to the attention of the
hazards. responsible code official. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated not be used.
Location: walk in cooler
Original Comment: Improper bulbs in cooler lights. Install proper size and re-
install moisture proof covers.
Printed on 05/30/2024 @ 08:38
Page 1 of 4
STATUS CODE DESCRIPTION
FAI L
FAIL
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
603.4 - Working space and
clearancesclearance.
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: Electrical panel by cooler door.
Original Comment: replace missing breakers or install listed blank covers in open
slots. REPEAT OFFENSE
A working space of not Working space around electrical equipment shall be
provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: electrical panels and disconnects by back door
Original Comment: Remove obstructions, maintain a minimum of 36" clearance
at all times. REPEAT OFFENSE.
Printed on 05/30/2024 @ 08:38
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 904.13.5.2 - Extinguishing Automatic fire -extinguishing systems shall be serviced not less frequently than
system service. every six months and after activation of the system. Inspection shall be by
qualified individuals, and a certificate of inspection shall be forwarded to the fire
code official upon completion.
GENERAL NOTES
JEFF SIEBEL - 05/30/2024 @ 07:40
JEFF SIEBEL - 05/30/2024 @ 07:41
REINSPECTION DATE
06/24/2024
CONTACT SIGNATURE
Shelly Knott
Signed on: 05/30/2024 @ 07:41
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 05/30/2024 @ 07:41
Location: Auto Fry
Original Comment: provide current semi-annual kitchen hood fire suppression
inspection report with all discrepancies corrected. Currently 159 days past due.
Contractor must post online to the compliance engine.
annual inspection fee $80
Pump 1 Reg Plus OOS.
c'L�GIL
vq<
Printed on 05/30/2024 @ 08:38
Page 3 of 4
QUESTIONS AEOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 05/30/2024 @ 08:38
Page 4 of 4