COMMERCIAL INSPECTION - 3720 VILLAGE PLACE - 5-21-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
REINSPECTION 1
Total Price j
$100.00
CUSTOMER #
23028
BILLING DATE
06/06/2024
DUE DATE
07/10/2024
INVOICE #
2024-00000415
CHARGES
$100.00
Less Prepayment
Total Due —*
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
FRIENDSHIP VILLAGE, 3720 VILLAGE PL, BLDG 3720 VILLAGE PL, WATERLOO IA 50702
DETAILS
Inspection Date: 05/21/2024 j Inspection Type: Residential Common Areas Inspection I Inspection Number: 10338 { Shift: N/A I
Station: N/A '. Unit: N/A Lead Inspector: JEREMIAH VANDYKE I Other Inspectors: N/A I Fee: $100.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 26 I Violations: 3 I N/A Codes: 2
STATUS CODE DESCRIPTION
FAIL 703.1 - Maintaining Materials and firestop systems used to protect membrane and through
protection. penetrations in fire -resistance -rated construction and construction installed to
resist the passage of smoke shall be maintained. The materials and firestop
systems shall be securely attached to or bonded to the construction being
penetrated with no openings visible through or into the cavity of the
construction. Where the system design number is known, the system shall be
inspected to the listing criteria and manufacturer's installation instructions.
FAIL
Location: Cove 1st floor mechanical room.
Original Comment: Hole in wall needs repaired.
705.2.4 - Door operation. Swinging fire doors shall dose from the full -open position and latch
automatically.
Location: Near room 5312.
Original Comment: Hallway fire doors did not properly dose.
Printed on 05/21 /2024 @ 16:02
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 901.6 - Inspection, testing and Fire detection and alarm systems, emergency alarm systems, gas detection
maintenance. systems, fire -extinguishing systems, mechanical smoke exhaust systems and
smoke and heat vents protection and life safety systems shall be maintained in
an operative condition at all times, and shall be replaced or repaired where
defective. Nonrequired fire protection and life safety systems and equipment
shall be inspected, tested and maintained or removed in accordance with Section
901.8 .
Location: Hood suppression report.
Original Comment: Hood suppression inspection past due 11 days. Contact
licensed contractor and have report uploaded to compliance engine by
contractor.
GENERAL NOTES
JEREMIAH VANDYKE - 05/21/2024 @ 15:55 Cummins generator service report and loadbank testing completed 8/8/2024.
JEREMIAH VANDYKE - 05/21/2024 @ 15:54 Monthly generator hours recorded April 2024.
JEREMIAH VANDYKE - 05/21/2024 @ 16:00 05/25/2023 L - (Annual) Kitchen Exhaust HARRIS CLEANING SERVICE AND AH Reviewed
Compliant
JEREMIAH VANDYKE - 05/21/2024 @ 16:01
Re -inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections & re -inspections are Monday -
Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on
a weekend, the re -inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier
re -inspection. *****Re inspection fees may be assessed for subsequent re -
inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent
re-inspections.-
JEREMIAH VANDYKE - 05/21/2024 @ 16:01 Lt. Van Dyke-jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-
1615
JEREMIAH VANDYKE - 05/21/2024 @ 15:52 Clothes dryers cleaned by Harris Cleaning 10/11/2023.
JEREMIAH VANDYKE - 05/21/2024 @ 15:53 Weekley Generator Test last recorded 5/17/2024.
Printed on 05/21/2024 @ 16:02
Page2of3
GENERAL NOTES
JEREMIAH VANDYKE - 05/21/2024 @ 15:55 Fire extinguishers serviced by Superior Fire October 2023.
JEREMIAH VANDYKE - 05/21/2024 @ 15:56 Water heater scheduled for inspection by Hartford steam boiler 5/22/2024.
JEREMIAH VANDYKE - 05/21/2024 @ 16:00 0/19/2023 S - (Annual) Fire Alarm HAWKEYE ALARM Reviewed Compliant
JEREMIAH VANDYKE - 05/21/2024 @ 16:00 07/27/2023 S - (Annual) Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC.
Reviewed
JEREMIAH VANDYKE - 05/21/2024 @ 16:00 07/27/2023 S - (Annual) Standpipe BLACKHAWK AUTOMATIC SPRINKLERS, INC. Reviewed
JEREMIAH VANDYKE - 05/21/2024 @ 16:01 Inspection Fee = $100.00 (To be mailed out by City via snail mail.)
REINSPECTION DATE
06/20/2024
CONTACT SIGNATURE
Chad Wagner Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 05/21/2024 @ 16:02