COMMERCIAL INSPECTION - 2424 RANCHERO RD - 5-21-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price J
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
15371
06/06/2024
07/10/2024
2024-00000412
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
&D'1)
INSPECTION REPORT
CASEY'S GENERAL STORE #2867, 2424 RANCHERO RD, BLDG 2867 RANCHERO RD, WATERLOO
IA S0701
DETAILS
Inspection Date: 05/21/2024 I Inspection Type: Annual Inspection (1Yr) I Inspection Number: 10489-R1 i Shift: N/A ; Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 1 I Passed Codes: 0 I Violations: 3 I N/A Codes: 1
STATUS CODE DESCRIPTION
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: storage room by office
Original Comment: Remove storage in front of electrical panel. maintain a
minimum of 36" clearance at al times.
Additional Comment: Remove gasoline from building
Printed on 05/22/2024 @ 08:04
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
FAI L
GENERAL NOTES
904.13.5.2 - Extinguishing
system service.
Location: electrical room by kitchen.
Original Comment: remove storage from within 36" of electrical panel. Install
permanent signage on electrical panels stating " NO STORAGE MAINTAIN 36"
CLEARANCE" .REPEAT VIOLATION. re -inspection fees will apply if not corrected.
Additional Comment: Repeat violation
Automatic fire -extinguishing systems shall be serviced not less frequently than
every six months and after activation of the system. Inspection shall be by
qualified individuals, and a certificate of inspection shall be forwarded to the fire
code official upon completion.
Location: Not Provided
Original Comment: Provide current semi-annual kitchen hood fire suppression
inspection report with all discrepancies corrected. Currently 20 days past due.
Contractor must upload online to the compliance engine.
JEFF SIEBEL - 05/01/2024 @ 09:17 annual inspection fee $80
Printed on 05/22/2024 @ 08:04
Page 2 of 3
GENERAL NOTES
JEFF SIEBEL - 05/22/2024 @ 08:00 re -inspection fee $100. repeat offenses.
REINSPECTION DATE
06/11/2024
CONTACT SIGNATURE
Christine Crane 2023
Signed on: 05/22/2024 @ 08:00
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 05/22/2024 @ 08:01
QUESTIONS AMOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 05/22/2024 @ 08:04