KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 2225 E SHAULIS RD - 4-11-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000 HH
OCCUPANCY FEE
Total Price ]
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
10030
05/02/2024
06/10/2024
2024-00000348
$100.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
LOST ISLAND WATERPARI( 2225 E SHAULIS RD, BLDG 2225 E SHAULIS RD, WATERLOO IA
50702
DETAILS
Inspection Date: 04/11/2024 I Inspection Type: Annual Inspection (1Yr nspecti n Number: 10227 I Shift: N/A I Station: N/A
Unit: N/A j Lead Inspector: JEFF SIEBEL Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 1 Passed Codes: 38 j Violations: 3 N/A Codes: 33
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: souvenir storage
Original Comment: repair exit egress light.
FAIL 5704.2.3.2 - Label or placard. Tanks more than 100 gallons (379 L) in capacity, which are permanently installed
or mounted and used for the storage of Class I, II or III liquids, shall bear a label
and placard identifying the material therein. Placards shall be in accordance with
NFPA 704. Exceptions: 1.Tanks of 300-gallon (1136 L) capacity or less located on
private property and used for heating and cooking fuels in single-family dwellings.
2.Tanks located underground.
Location: Wave Pool Equipment room
Original Comment: replace missing and faded 704 placard signage on all tanks.
Printed on 04/16/2024 @ 10:04
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 904.13.5.2 - Extinguishing Automatic fire -extinguishing systems shall be serviced not less frequently than
system service. every six months and after activation of the system. Inspection shall be by
qualified individuals, and a certificate of inspection shall be forwarded to the fire
code official upon completion.
GENERAL NOTES
JEFF SIEBEL - 04/16/2024 @ 09:27
JEFF SIEBEL - 04/16/2024 @ 09:57
JEFF SIEBEL - 04/16/2024 @ 09:58
REINSPECTION DATE
05/16/2024
CONTACT SIGNATURE
Jesse Henry
Signed on: 04/16/2024 @ 10:00
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 04/16/2024 @ 10:00
Location: All food venures
Original Comment: provide current semi-annual kitchen hood fire suppression
inspection reports with all discrepancies corrected. Currently 12 days past due.
Contractor must upload online to the compliance engine.
Annual inspection $100
private fire hydrant testing due 5/1/24
fire extinguishers due now.