COMMERCIAL INSPECTION - 1825 E SAN MARNAN DR - 4-18-24
FOR BILLING INQUIRY: (319)291-4323
[ Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
15159
05/02/2024
06/10/2024
2024-00000346
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
CVS PHARMACY, 1825 E SAN MARNAN DR, BLDG 1825 E SAN MARNAN DR, WATERLOO IA
50702
DETAILS
Inspection Date: 04/18/2024 j Inspection Type: Annual Inspection (1Yr Inspecr on Number: 10397 ( Shift: N/A Station: N/A
Unit: N/A i Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 36 I Violations: 5 I N/A Codes: 32
STATUS CODE DESCRIPTION
FAI L
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
Location: back storage room above shelves by electrical panels
Original Comment: remove obstructions to egress light. Was not able to see or
test.
FAIL 505.1 - Address identification. New and existing buildings shall be provided with approved address
identification. The address identification shall be legible and placed in a position
that is visible from the street or road fronting the property. Address identification
characters shall contrast with their background. Address numbers shall be
Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each
character shall be not less than 4 inches (102 mm) high with a minimum stroke
width of 1/2 inch (12.7 mm). Where required by the fire code official, address
identification shall be provided in additional approved locations to facilitate
emergency response. Where access is by means of a private road and the
building cannot be viewed from the public way, a monument, pole or other sign
or means shall be used to identify the structure. Address identification shall be
maintained.
Location: front of building
Original Comment: replace peeling, missing address with same size and color
numbers.
Printed on 04/18/2024 @ 10:03
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 603.6 - Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: behind front counter
Original Comment: remove extension cord to fan .
FAIL 903.3.1 - Standards. Sprinkler systems shall be designed and installed in accordance with Section
903.3.1.1, unless otherwise permitted by Sections 903.3.1.2 and 903.3.1.3 and
other chapters of this code, as applicable.
FAI L
GENERAL NOTES
Location: sprinkler riser
Original Comment: Repair fire sprinkler riser backflow preventer. Currently
dripping, if fails flood is possible.
Chapter 14 - Inspection, Fire alarm system tested at least annually by licensed contractor
testing, and maintenance
Location: back room by FACP
Original Comment: Fire Alarm inspection report from JF Ahern Co 8/8/23 lists
discrepancies. (batteries). Contractor must upload corrections online to the
compliance engine.
JEFF SIEBEL - 04/18/2024 @ 10:00 annual inspection $80
REINSPECT/ON DATE
05/15/2024