COMMERCIAL INSPECTION - 127 JEFFERSON ST - 4-19-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23091
05/02/2024
06/10/2024
2024-00000334
$80.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
HAS PETROLEUM,127JEPFERSON ST, BLDG 127JEPPERSON ST, WATERLOO IA S0702
DETAILS
Inspection Date: 04/19/2024 Inspection Type: Annual Inspection (1 Y,
Unit: N/A Lead Inspector: JEFF SIEBEL Other Inspectors: N/A
VIOLATIONS AND COM►LIANCES
umber: 10667 Shift: N/A Station: N/A
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 ( Passed Codes: 24 Violations: 6 l N/A Codes: 43
STATUS CODE DESCRIPTION
FAIL 1010.2.9 - Panic and fire exit Swinging doors serving a Group H occupancy and swinging doors serving rooms
hardware. or spaces with an occupant load of 50 or more in a Group A or E occupancy shall
not be provided with a latch or lock other than panic hardware or fire exit
hardware. Exceptions: 1.A main exit of a Group A occupancy shall be permitted to
have locking devices in accordance with Section 1010.2.4, Item 2 3. 2.Doors
provided with panic hardware or fire exit hardware and serving a Group A or E
occupancy shall be permitted to be electrically locked in accordance with Section
1010.2.12 or 1010.2.11. 3. Exit access doors serving occupied exterior areas shall
be permitted to be locked in accordance with Section 1010.2.4, Item 8.
4.Courtrooms shall be permitted to be locked in accordance with Section
1010.2.13, Item 3. Electrical rooms with equipment rated 1,200 amperes or more
and over 6 feet (1829 mm) wide, and that contain overcurrent devices, switching
devices or control devices with exit or exit access doors, shall be equipped with
panic hardware or fire exit hardware. The doors shall swing in the direction of
egress travel.
Location: back exit to restrooms
Original Comment: remove thumb turn lock from exit door. REPEAT OFFENSE
FAIL 1032.2 - Reliability. Required exit accesses, exits and exit discharges shall be continuously
maintained free from obstructions or impediments to full instant use in the case
of fire or other emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be used for any purpose
that interferes with a means of egress.
Location: Rear exit to bathrooms
Original Comment: Remove all items blocking exit egress path to restrooms.
Maintain clear path at all times.
Printed on 04/22/2024 @ 09:32
Page 1 of 4
STATUS
FAI L
FAIL
CODE
DESCRIPTION
603.2 - Abatement of unsafe Identified electrical hazards shall be abated. Identified hazardous electrical
conditions and electrical conditions in permanent wiring shall be brought to the attention of the
hazards. responsible code official. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated not be used.
603.5 - Relocatable power
taps and current
taps.Multiplug adapters.
Location: C4 Energy Cooler by back door
Original Comment: Power cord stretched to the max, end pulling off. Repair
Multiplug adapters, such as cube adapters, unfused plug strips or any other
device not complying with NFPA 70 shall be prohibited. The construction and use
of current taps and relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Bait cooler front of store by front counter and door.
Original Comment: Remove cooler from power strip. Cooler must plug directly
into wall outlet. Mount power strip REPEAT OFFENSE
Printed an 04/22/2024 @ 09:32
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
FAI L
Location: entire building
Original Comment: provide annual service for all fire extingishers
Chapter 14 - Inspection, Fire alarm system tested at least annually by licensed contractor
testing, and maintenance
GENERAL NOTES
JEFF SIEBEL - 04/22/2024 @ 09:28
JEFF SIEBEL - 04/22/2024 @ 09:29
JEFF SIEBEL - 04/22/2024 @ 09:30
Location: Fire Alarm for Building including notification for convenience store and
restrooms
Original Comment: Provide annual service for fire alarm. Currently 192 days past
due. Contractor must upload online to the compliance engine.
annual inspection
Repeat offenses will automatically be billed for re -inspection fees beginning at $100.
correct all violations to avoid progressive re -inspection fees beginning at $100.
Printed on 04/22/2024 @ 09:32
Page 3of4
REINSPECTION DATE
05/20/2024
CONTACT SIGNATURE
Mohammad Bhatti
Signed on: 04/22/2024 @ 09:24
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 04/22/2024 @ 09:24