COMMERCIAL INSPECTION - 728 COMMERCIAL ST - 5-1-24
FOR BILLING INQUIRY: (319)291-4323
[ Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
6422
05/02/2024
06/10/2024
2024-00000326
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
AMERICAN LEGION POST 138, 728 COMMERCIAL ST, BLDG 728 COMMERCIAL ST, WATERLOO
IA 50702
DETAILS
Inspection Date: 05/01/2024 I Inspection Type: Annual Inspection (1Yr nsp'ction Number: 10513 I Shift: N/A I Station: N/A I
Unit: N/A I Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 36 1 Violations: 3 1 N/A Codes: 34
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
FAI L
Location: North Exit Kitchen Area
Original Comment: repair exit/egress light.
705.2.4 - Door operation. Swinging fire doors shall close from the full -open position and latch
automatically.
Location: Fire door to kitchen
Original Comment: Fire door to kitchen must remain closed at all times. Re -install
door closure . Door must completely self -close and latch.
Printed on 05/02/2024 @ 09:59
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
GENERAL NOTES
JEFF SIEBEL - 05/02/2024 @ 09:56
JEFF SIEBEL - 05/02/2024 @ 09:56
REINSPECTION DATE
05/22/2024
CONTACT SIGNATURE
Sarah Hoffman
Signed on: 05/02/2024 @ 09:57
Location: Not Provided
Original Comment: provide annual service for fire extinguishers.
annual inspection $80
Kitchen hood fire suppression system due for service 5/21/24
Printed an 05/02/2024 @ 09:59
Page 2of3
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 05/02/2024 @ 09:57