COMMERCIAL INSPECTION - 1600 OLYMPIC DR 3-11-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 20.000
OCCUPANCY FEEE
Total Price
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
3311
03/18/2024
04/20/2024
2024-00000306
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
SUNNYSIDE COUNTRY CLUB, 1600 OLYMPIC DR, BLD6 1600 OLYMPIC DR, WATERLOO /A
S0701
DETAILS
Inspection Date: 03/11/2024 I Inspection Type: Annual Inspection (1Yr) I Inspection Number: 10419 Shift: N/A j Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL Other Inspectors: N/A
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 46 ( Violations: 13 I N/A Codes: 19
STATUS CODE DESCRIPTION
FAIL 1010.1 - Doors. Means Doors in the means of egress shall comply with the requirements of
Sections 1010.1.1 through 1010.3.4. Exterior exit doors shall meet also comply
with the requirements of this section. Doors serving a Section 1022.2. Gates in
the means of egress shall comply with the requirements of Sections 1010.4
and 1010.4.1. Turnstiles in the means of egress system shall meet comply with
the requirements of this section and Section 1022.2. Doors Sections 1010.5
through 1010.5.4. Doors, gates and turnstiles provided for egress purposes in
numbers greater than required by this code shall meet comply with the
requirements of this section. Doors in the Means means of egress doors shall be
readily distinguishable from the adjacent construction and finishes such that the
doors are easily recognizable as doors. Mirrors or similar reflecting materials
shall not be used on means of egress doors. Means of egress doors shall not be
concealed by curtains, drapes, decorations or similar materials.
Location: Golf simulator room
Original Comment: Remove curtains and other obstructions to exit doors. Not
allowed to disguise exit doors with curtains.
Printed on 03/12/2024 @ 10:21
Page 1 of 7
STATUS CODE DESCRIPTION
FAIL 1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
FAI L
FAIL
Location: Above parson's trail picture in mezzanine entry
Original Comment: repair egress light.
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
Location: upper floor by elevator
Original Comment: repair egress light
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
llumination. accordance with Sections 1008.3 and 1104.5.1.
Location: Vestibule of Men's locker room exit to long hallway
Original Comment: repair egress light
FAIL '1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: in hallway outside employees breakroom
Original Comment: repair exit light
Printed on 03/12/2024 @ 10:21
Page 2of7
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Pro Shop main door
Original Comment: repair exit/egress light
FAIL 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
FAIL
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
Location: entire building including lights listed in violations
Original Comment: Provide documentation of testing and repair of all emergency
egress and exit lights with signature and date.
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: Basement walk in cooler
Original Comment: replace missing moisture proof cover on light fixture.
Printed on 03/12/2024 @ 10:21
Page 3 of 7
STATUS CODE DESCRIPTION
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
FAIL
603.6 - Extension cords.
Location: golf cart shed
Original Comment: Remove obstructions to electrical panel. maintain a minimum
of 36" to and around electrical panels.
Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: To lamp on piano in foyer
Original Comment: remove extension cord
Printed on 03/12/2024 @ 10:21
Page 4 of 7
STATUS
FAI L
CODE
603.6 - Extension cords.
DESCRIPTION
Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: Kitchen office
Original Comment: remove extension cord to second desk. Install permanent
power with permits and inspections or utilize power tap with reset plugged
directly into wall and properly mounted.
Printed on 03/12/2024 @ 10:21
Page 5of7
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1 Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: by employees break room in basement
Original Comment: replace missing ceiling tiles to enable fire sprinkler to function
properly.
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: clubhouse, pro shop, cart shed, maintenance building
Original Comment: provide annual service. fire extinguishers month overdue.
GENERAL NOTES
Printed on 03/12/2024 @ 10:21
Page 6 of 7
JEFF SIEBEL - 03/11 /2024 @ 15:28 Annual inspectio
REINSPECT/ON DATE
04/01/2024
CONTACT SIGNATURE
Seth Henricks
Signed on: 03/12/2024 @ 10:19
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 03/12/2024 @ 10:19
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 03/12/2024 @ 10:21