COMMERCIAL INSPECTION - 926 LINN ST - 3-13-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FE,E
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
22283
03/18/2024
04/20/2024
2024-00000305
$80.00
Less Prepayment
Total Due —+
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
SPEEDY MART,. 926 LINN ST, BLDG 926 LINN ST, WATERLOO IA 50703
DETAILS
Inspection Date: 03/13/2024 j Inspection Type: Annual Inspection (1Yr) I Inspection Number: 9913 j Shift: N/A ( Station: N/A
Unit: N/A j Leacl Inspector: JEFF SIEBEL Other Inspectors: N/A I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 18 I Violations: 7 I N/A Codes: 49
STATUS CODE DESCRIPTION
FAI L
FAIL
603.2 - Abatement of unsafe Identified electrical hazards shall be abated. Identified hazardous electrical
conditions and electrical conditions in permanent wiring shall be brought to the attention of the
hazards. responsible code official. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated not be used.
Location: Kitchen area
Original Comment: properly contain electrical wires in light fixture with listed
cover.
603.2 - Abatement of unsafe Identified electrical hazards shall be abated. Identified hazardous electrical
conditions and electrical conditions in permanent wiring shall be brought to the attention of the
hazards. responsible code official. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated not be used.
Location: back wall behind counter
Original Comment: remove light fixture leaning on wall and plugged into outlet.
Not installed as listed for use.
Printed on 03/15/2024 @ 10:40
Page 1 of 5
STATUS
FAI L
FAIL
CODE
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
603.5.3 - Installation.
DESCRIPTION
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: on front of building
Original Comment: Replace missing moisture proof outlet covers on front of
building. If something is permanently plugged in, cover must close and
accomdate cord.
Relocatable power tap cords shall not extend through walls, ceilings, floors,
under doors or floor coverings, or be subject to environmental or physical
damage.
Location: Behind
Original Comment: properly mount power strip behind freezers and coolers .
Freezers and coolers not allowed to plug into power strip, must plug directly into
permanent wall outlet. Install permanent power with permits and inspections.
Printed on 03/15/2024 @ 10:40
Page 2 of 5
STATUS
FAIL
CODE
603.6 - Extension cords.
DESCRIPTION
Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: behind counter
Original Comment: remove 2 extension cords from behind counter. Properly
install power strips plugged directly into wall and supported or mounted may be
utilized for computer equipment only.
Printed on 03/15/2024 @ 10:40
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10.3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: Not Provided
Original Comment: provide annual service for fire extinguisher. Overdue.
FAIL 906.6 - Unobstructed and Portable fire extinguishers shall not be obstructed or obscured from view. In
unobscured. rooms or areas in which visual obstruction cannot be completely avoided, means
shall be provided to indicate the locations of extinguishers.
Location: behind cooler, freezer
Original Comment: relocate fire extinguisher or appliances. Maintain a minimum
of 36" clearance to fire extinguisher. Mount 4" to 5' above the floor in an
accessible area.
GENERAL NOTES
JEFF SIEBEL - 03/13/2024 @ 10:28 annual inspection $80
Printed on 03/15/2024 @ 10:40
Page 4 of 5
REINSPECTION DATE
04/04/2024
CONTACT SIGNATURE
DILAWAR KHAN 2023
Signed on: 03/15/2024 @ 10:38
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 03/15/2024 @ 10:38
QUESTIONS AEOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 03/15/2024 @ 10:40