COMMERCIAL INSPECTION - 250 ANSBOROUGH AVE - 2-22-24
FOR BILLING INQUIRY: (319)291-4323
[ Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24040
03/18/2024
04/20/2024
2024-00000303
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
HIPPODROME AUDITORIUM, 2S0ANSBOR000HAVE, BLDG 2S7ANSBOR000HAVE,
WATERLOO IA S0701
DETAILS
Inspection Date: 02/22/2024 j Inspection Type: Annual Inspection (1Yr) I Inspection Number: 10238 I Shift: N/A I Station: N/A I
Unit: N/A j Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 39 I Violations: 10 I N/A Codes: 28
STATUS CODE DESCRIPTION
FAI L
1010.1.3 - Door opening
force Forces to unlatch and
open doors.
The force for pushing or pulling open interior swinging egress doors, other than
fire doors, shall not exceed 5 pounds (22 N). These forces do not apply to the
force required to retract latch bolts or disengage other devices that hold the
door in a closed position. For other swinging doors, as well as sliding and folding
doors, the door latch shall release when subjected to a 15-pound (67 N) force.
The door shall be set in motion when subjected to a 30-pound (133 N) force. The
door shall swing to a full -open position when subjected to a 15-pound (67 N)
force. The forces to unlatch doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to unlatch the door
shall not exceed 15 pounds (66.7 N). 2.Where door hardware operates by
rotation, the operational force to unlatch the door shall not exceed 28 inch -
pounds (315 N-cm). The force to open doors shall comply with the following: 1.For
interior swinging egress doors that are manually operated, other than doors
required to be fire rated, the force for pushing or pulling open the door shall not
exceed 5 pounds (22 N). 2.For other swinging doors, sliding doors or folding
doors, and doors required to be fire rated, the door shall require not more than
a 30-pound (133 N) force to be set in motion and shall move to a full -open
position when subjected to not more than a 15-pound (67 N) force.
Location: exit door between E and D North
Original Comment: Repair door. Must unlatch and swing to full open with less
than 15 # force.
Printed on 03/06/2024 @ 08:21
Page 1 of 6
STATUS CODE DESCRIPTION
FAIL 1010.2.9 - Panic and fire exit Swinging doors serving a Group H occupancy and swinging doors serving rooms
hardware. or spaces with an occupant load of 50 or more in a Group A or E occupancy shall
not be provided with a latch or lock other than panic hardware or fire exit
hardware. Exceptions: 1.A main exit of a Group A occupancy shall be permitted to
have locking devices in accordance with Section 1010.2.4, Item 2 3. 2.Doors
provided with panic hardware or fire exit hardware and serving a Group A or E
occupancy shall be permitted to be electrically locked in accordance with Section
1010.2.12 or 1010.2.11. 3. Exit access doors serving occupied exterior areas shall
be permitted to be locked in accordance with Section 1010.2.4, Item 8.
4.Courtrooms shall be permitted to be locked in accordance with Section
1010.2.13, Item 3. Electrical rooms with equipment rated 1,200 amperes or more
and over 6 feet (1829 mm) wide, and that contain overcurrent devices, switching
devices or control devices with exit or exit access doors, shall be equipped with
panic hardware or fire exit hardware. The doors shall swing in the direction of
egress travel.
FAIL
FAIL
Location: SE corner of lobby
Original Comment: remove chains from door. Only panic hardware allowed.
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
Location: women's restroom SE corner
Original Comment: repair egress light
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
Location: west lobby by side door with fire sprinkler room sign on it
Original Comment: repair egress light
Printed on 03/06/2024 @ 08:21
Page 2 of 6
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: above outside door between A North and A South
Original Comment: repair exit/egress light
FAIL 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
Location: CBS emergency lights around arena
Original Comment: Provide documentation of testing of all emergency lights with
all discrepancies corrected with date and signature or set up a time with
inspector to test with breakers off.
FAIL 603.9.4 - Prohibited areas. Portable, electric space heaters shall not be operated within 3 feet (914 mm) of
any combustible materials. Portable, electric space heaters shall be operated
only in locations for which they are listed.
Location: maintenance office
Original Comment: Remove portable electric heater or provide documentation of
listing for use in a commercial building and proper clearances. Remove plastic
hanging from ceiling.
Printed on 03/06/2024 @ 08:21
Page 3 of 6
STATUS CODE DESCRIPTION
FAIL 606.3.3.3 - Records. Records for inspections shall state the individual and company performing the
inspection, a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be completed after
each inspection or cleaning and maintained.
Location: kitchen hood cleaning
Original Comment: provide current semi-annual kitchen hood exhaust system
cleaning inspection report with all discrepancies corrected. Contractor must
upload online to the compliance engine.
FAIL 606.3.3.3 - Records. Records for inspections shall state the individual and company performing the
inspection, a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be completed after
each inspection or cleaning and maintained.
Location: kitchen hood fire suppression system
Original Comment: provide current semi-annual kitchen hood exhaust fire
suppression inspection report with all discrepancies corrected. Contractor must
upload online to the compliance engine.
Printed on 03/06/2024 @ 08:21
Page 4of6
STATUS CODE DESCRIPTION
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: all fire extinguishers and K guard
Original Comment: Provide annual service. Last was 2022
GENERAL NOTES
JEFF SIEBEL - 02/22/2024 @ 12:59 annual inspection $80
JEFF SIEBEL - 02/22/2024 @ 13:00
JEFF SIEBEL - 02/22/2024 @ 13:00
JEFF SIEBEL - 02/22/2024 @ 13:01
Allow inspection of exit doors NW side , slid open for dirt removal
Allow inspection of kitchen area -was locked
Allow inspector to test exit doors A North and A South. Were chained open.
REINSPECTION DATE
03/26/2024