COMMERCIAL INSPECTION - 2929 AIRPORT BLVD - 2-6-24
L Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FE.E
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
4628
03/18/2024
04/20/2024
2024-00000302
$80.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
BOYS SCOUTS OFAMERICA WINNEBAGO COUNCIL, 2929 AIRPORT BLVD, BLDG 2929 AIRPORT
BLVD, WATERLOO /A 50703
DETAILS
Inspection Date: 02/26/2024 I Inspection Type: Annual Inspection (1Yr) I Inspection Number: 221 Shift: N/A I Station: N/A
Unit: N/A Lead Inspector: JEREMIAH VANDYKE I Other Inspectors: N/A I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 22 I Violations: 7 I N/A Codes: 46
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Side/Back Hallway
Original Comment: Exit light tested and failed. Must be repaired or replaced.
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Front Lobby area.
Original Comment: Exit light tested and failed. Must be repaired or replaced.
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: Scout Shop.
Original Comment: Exits lights must be moved to above doors that exit Scout
shop X2. Discussed installing new exit lights.
Printed on 02/26/2024 @ 15:37
Page 1 of 5
STATUS
FAI L
FAI L
CODE
315.3.2 - Means of egress.
DESCRIPTION
Combustible materials shall not be stored in exits or enclosures for stairways
and ramps. Combustible materials in the means of egress during construction,
demolition, remodeling or alterations shall comply with Section 3312.3.
Location: Side/Back Hallway
Original Comment: Hallway leads to a marked exit and must be clear of all
storage.
603.2 - Abatement of unsafe Identified electrical hazards shall be abated. Identified hazardous electrical
conditions and electrical conditions in permanent wiring shall be brought to the attention of the
hazards. responsible code official. Electrical wiring, devices, appliances and other
equipment that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated not be used.
Location: Front Lobby lights & Scout Shop lights.
Original Comment: Open wiring on ceiling lights must be addressed.
Printed on 02/26/2024 @ 15:37
Page 2of5
STATUS
FAI L
CODE
603.5 - Relocatable power
taps and current
taps.Multiplug adapters.
DESCRIPTION
Multiplug adapters, such as cube adapters, unfused plug strips or any other
device not complying with NFPA 70 shall be prohibited. The construction and use
of current taps and relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Break room.
Original Comment: Power strip to be removed near fridge. Refridgerators,
microwaves, toasters, hot plates, coffee makers, air fryers, space heaters are not
to be plugged into power strips and can only be plugged directly into wall outlets.
Printed on 02/26/2024 @ 15:37
Page3of5
STATUS CODE DESCRIPTION
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10.3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: Entire building.
Original Comment: Fire Exinguishers are past due and need to be serviced
annually and tagged.
GENERAL NOTES
JEREMIAH VANDYKE - 02/26/2024 @ 15:24 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone # 319-291-2515.
JEREMIAH VANDYKE - 02/26/2024 @ 15:25
Re -inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections & re -inspections are Monday -
Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on
a weekend, the re -inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier
re -inspection. *****Re inspection fees may be assessed for subsequent re -
inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent
re-inspections.-
JEREMIAH VANDYKE - 02/26/2024 @ 15:25 Lt. Van Dyke-jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-
1615
JEREMIAH VANDYKE - 02/26/2024 @ 15:30 Inspection Fee = $80.00 (Will be sent by city via snail mail. )
Printed on 02/26/2024 @ 15:37
Page 4of5
REINSPECT/ON GATE
03/27/2024
CONTACT SIGNATURE
Jim Madison Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 02/26/2024 @ 15:31