COMMERCIAL INSPECTION - 1819 LA PORTE RD - 2-22-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price j
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
5404
02/26/2024
03/28/2024
2024-00000293
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
TACO BELL, 1819 LA PORTE RD, BLDG 1819 LA PORTE RD, WATERLOO IA 50702
DETAILS
Inspection Date: 02/22/2024 I Inspection Type: Annual Inspection (1Yr) ; Inspection Number: 12180 j Shift: N/A j Station: N/A j
Unit: N/A I Lead Inspector: JEREMIAH VANDYKE I Other Inspectors: N/A ; Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 31 I Violations: 6 I N/A Codes: 36
STATUS CODE DESCRIPTION
FAIL 305.1 - Clearance from Clearance between ignition sources, such as luminaires, heaters, flame -
ignition sources. producing devices and combustible materials, shall be maintained in an
approved manner.
Location: Water heater.
Original Comment: Maintain 3 feet clear around water heater.
FAIL 506.2 - Key box maintenance. The operator of the building shall immediately notify the fire code official and
provide the new key where a lock is changed or rekeyed. The key to such lock
shall be secured in the key box.
Location: Knox Box.
Original Comment: I will check knox box for proper master key for building. Will
contact business if key does not work.
FAIL 606.3.3.1 - Inspection. Hoods, grease -removal devices, fans, ducts and other appurtenances shall be
inspected at intervals specified in Table 606.3.3.1 or as approved by the fire code
official. Inspections shall be completed by qualified individuals.
Location: Commercial Kitchen Exhaust cleaning
Original Comment: Commercial Kitchen Exhaust cleaning is past due according to
Compliance engine website. Contractor needs to upload report if completed.
Printed on 02/22/2024 @ 15:03
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 904.13.5.2 - Extinguishing Automatic fire -extinguishing systems shall be serviced not less frequently than
system service. every six months and after activation of the system. Inspection shall be by
qualified individuals, and a certificate of inspection shall be forwarded to the fire
code official upon completion.
Location: Kitchen Hood ansul system
Original Comment: Commercial Hood suppression system is past due according
to Compliance engine website. Contractor needs to upload report if completed.
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: All fire extinguishers
Original Comment: All fire extinguishers are past due and need to be serviced
then tagged.
Printed on 02/22/2024 @ 15:03
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL
GENERAL NOTES
906.4.2 - Class K portable fire Where hazard areas include deep fat fryers, listed Class K portable fire
extinguishers for deep fat extinguishers shall be provided as follows: 1.For up to four fryers having a
fryers. maximum cooking medium capacity of 80 pounds (36.3 kg) each: one Class K
portable fire extinguisher of a minimum 1.5-gallon (6 L) capacity. 2.For every
additional group of four fryers having a maximum cooking medium capacity of 80
pounds (36.3 kg) each: one additional Class K portable fire extinguisher of a
minimum 1.5-gallon (6 L) capacity shall be provided. 3.For individual fryers
exceeding 6 square feet (0.55 m2) in surface area: Class K portable fire
extinguishers shall be installed in accordance with the extinguisher
manufacturer's recommendations.
Location: Class K Extinguisher
Original Comment: Class K fire extinguisher is past due and needs to serviced
then tagged.
JEREMIAH VANDYKE - 02/22/2024 @ 15:01 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone # 319-291-2515.
JEREMIAH VANDYKE - 02/22/2024 @ 15:01
Re -inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections & re -inspections are Monday -
Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on
a weekend, the re -inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier
re -inspection. *****Re inspection fees may be assessed for subsequent re -
inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent
re-inspections.-
JEREMIAH VANDYKE - 02/22/2024 @ 15:01 Lt. Van Dyke-jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-
1615
JEREMIAH VANDYKE - 02/22/2024 @ 15:02 Inspection Fee = $80.00
REINSPECT/ON DATE
03/23/2024
Printed on 02/22/2024 @ 15:03
Page 3 of 4