COMMERCIAL INSPECTION - 2710 CROSSROADS BLVD - 2-22-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
REINSPECTION 3
Total Price j
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
5204
02/26/2024
03/28/2024
2024-00000290
CHARGES
$200.00
Less Prepayment
Total Due —*
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
TIRES PLUS, 2710 CROSSROADS BLVD, BLDG 2710 CROSSROADS BLVD, WATERLOO IA 50702
DETAILS
Inspection Date: 02/22/2024 f Inspection Type: Annual Inspection (1Yr) I Inspection Number: 1715-R17 j Shift: N/A ( Station: N/A
Unit: N/A j Lead Inspector: JEREMIAH VANDYKE I Other Inspectors: N/A I Fee: $200.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 0 I Violations: 4 I N/A Codes: 0
STATUS CODE DESCRIPTION
FAI L
FAIL
2015 IFC - Fire alarm testing Is the fire alarm system powered, operational and displaying normal operation
and maintenance (no troubles, supervisory, or alarms)?
509.1 - Identification
Location: Not Provided
Original Comment: Fire alarm in trouble, needs to be addressed by licensed fire
alarm contractor.
Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems, sprinkler risers and valves, or
other fire detection, suppression or control elements shall be identified for the
use of the fire department. Approved signs required to identify fire protection
equipment and equipment location shall be constructed of durable materials,
permanently installed and readily visible.
Location: Not Provided
Original Comment: Door located in main garage going into tire storage area
needs signage. Must have "Sprinkler Riser, FACP, & Main Electrical panel" for
description.
Printed on 02/22/2024 @ 15:09
Page 1 of 4
STATUS
FAIL
FAI L
CODE
DESCRIPTION
604.2.12 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination
accordance with Sections 1008.3 and 1104.5.1.
Location: Not Provided
Original Comment: Egress lights located in shop and in back parts area tested
and failed.
Chapter 14 - Inspection, Fire alarm system tested at least annually by licensed contractor
resting, and maintenance
Location: Not Provided
Original Comment: Fire alarm need to be inspected by licensed fire alarm
contractor and inspection report uploaded into Compliance Engine by servicing
contractor.
GENERAL NOTES
JEREMIAH VANDYKE - 01/18/2024 @ 15:11 Stopped in for re inspect and nothing has been updated or corrected.
JEREMIAH VANDYKE - 01/18/2024 @ 15:11 Stop by for re inspect, no changes.
Printed on 02/22/2024 @ 15:09
Page 2 of 4
GENERAL NOTES
JEREMIAH VANDYKE - 01/18/2024 @ 15:11
Re -inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections & re -inspections are Monday -
Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on
a weekend, the re -inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier
re -inspection.
JEREMIAH VANDYKE - 01/18/2024 @ 15:11 Re inspection fees may be assessed for subsequent re -inspections. Re -inspection fees
start at $100, then $150, and $200 for all subsequent re-inspections.-
JEREMIAH VANDYKE - 01/18/2024 @ 15:11 RE - inspection fee: $200.00
JEREMIAH VANDYKE - 01/18/2024 @ 15:11 Stopped in at site and Manager Matt E. states that he heard there is a Bid out for
replacement of Alarm.
JEREMIAH VANDYKE - 01/18/2024 @ 15:11 Called Tire Plus and talked with Manager Matt. States nothing has been corrected at
this time.
JEREMIAH VANDYKE - 01/18/2024 @ 15:11 Stopped in at site and Manager Matt E. states that nothing has been updated or
corrected.
JEREMIAH VANDYKE - 02/22/2024 @ 15:07 Stopped in at site, nothing has been updated or corrected.
JEREMIAH VANDYKE - 02/22/2024 @ 15:07 Re Inspection Fee = $200.00
REINSPECTION DATE
03/23/2024
CONTACT SIGNATURE
Scott Graham - District Manager Reason for not collecting a signature: NA
Printed on 02/22/2024 @ 15:09
Page 3 of 4
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 02/22/2024 @ 15:08
QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
uaL
Printed on 02/22/2024 @ 15:09
Page 4 of 4