COMMERCIAL INSPECTION - 250 ANSBOROUGH AVE - 2-21-24
FOR BILLING INQUIRY: (319)291-4323
[ Description
INSPECTION 2,000
OCCUPANCY FEEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
20789
02/26/2024
03/28/2024
2024-00000288
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
NATIONAL CATTLE CONGRESS PAVILUON, 250 ANSBOROUGH AVE, BLD6 250 ANSBOROUGH
AVE, WATERLOO /A 50701
DETAILS
Inspection Date: 02/21/2024 I Inspection Type: Annual Inspection (1Yr) I Inspection Number: 11321 I Shift: N/A I Station: N/A
Unit: N/A E Lead Inspector: JEFF SIEBEL Other Inspectors: N/A ( Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 36 I Violations: 7 I N/A Codes: 32
STATUS CODE DESCRIPTION
FAIL
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
Location: Not Provided
FAIL 506.1 - Where required. Where access to or within a structure or an area is restricted because of secured
openings or where immediate access is necessary for life-saving or fire -fighting
purposes, the fire code official is authorized to require a key box to be installed in
an approved location. The key box shall be of an approved type listed in
accordance with UL 1037, and shall contain keys to gain necessary access as
required by the fire code official.
Location: Not Provided
Original Comment: Install knox box for fire fighter access on building. Knox box
required for buildings with fire sprinkler and fire alarm. Knox box can be
purchased at knoxbox.com and entering zip code for Waterloo Fire.
Printed on 02/22/2024 @ 1 1 i 18
Page 1 of 4
STATUS CODE DESCRIPTION
AIL 509.1 - Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems, sprinkler risers and valves, or
other fire detection, suppression or control elements fire protection systems
shall be identified for the use of the fire department. Approved signs required to
identify fire protection system equipment and equipment location shall be
constructed of durable materials, permanently installed and readily visible.
FAIL
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
Location: Entry doors to fire sprinkler riser room
Original Comment: Install permanent red sign with white letters stating " Fire
Sprinkler Riser Room" on outside of doors leading to room.
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: Outside by fire hydrant
Original Comment: replace missing outlet cover
FAIL 610.1.2 - Maintenance. The lint trap, mechanical and heating components, and the exhaust duct system
of a clothes dryer shall be maintained in accordance with the manufacturer's
operating instructions to prevent the accumulation of lint or debris that prevents
the exhaust of air and products of combustion.
Location: Not Provided
Original Comment: provide documentation of dryer vent cleaning to the outside
of building with signature and date.
Printed on 02/22/2024 @ 11:18
Page 2 of 4
STATUS CODE DESCRIPTION
903.4 - Sprinkler system
supervision and alarms.
Valves controlling the water supply for automatic sprinkler systems, pumps,
tanks, water levels and temperatures, critical air pressures and waterflow
switches on all sprinkler systems shall be electrically supervised by a listed fire
alarm control unit. Exceptions: 1. Automatic sprinkler systems protecting one -
and two-family dwellings. 2.Limited area sprinkler systems in accordance with
Section 903.3.8.3. Automatic sprinkler systems installed in accordance with NFPA
13R where a common supply main is used to supply both domestic water and the
automatic sprinkler system, and a separate shutoff valve for the automatic
sprinkler system is not provided. 4.Jockey pump control valves that are sealed or
locked in the open position. 5.Control valves to commercial kitchen hoods, paint
spray booths or dip tanks that are sealed or locked in the open position. 6.Valves
controlling the fuel supply to fire pump engines that are sealed or locked in the
open position. 7.Trim valves to pressure switches in dry, preaction and deluge
sprinkler systems that are sealed or locked in the open position. 8. Underground
key or hub gate valves in roadway boxes.
Location: Not Provided
Original Comment: Provide notification with a NFPA 72 Alarm system for
Waterflow, tamper valves and a horn strobe for water flow on outside of building
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
GENERAL NOTES
Location: Not Provided
Original Comment: Provide annual service for fire extinguishers. Has not been
done since 2022
Printed on 02/22/2024 @ 11:18
Page 3 of 4
JEFF SIEBEL- 02/22/2024 @ 09:24
JEFF SIEBEL - 02/22/2024 @ 11:16
JEFF SIEBEL - 02/22/2024 @ 11:16
REINSPECTION DATE
03/12/2024
CONTACT SIGNATURE
Jim Koch
Signed on: 02/22/2024 @ 11:17
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/22/2024 @ 11:17
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
annual inspection $80
Defibrillator is missing from cabinet.
Provide corrections to avoid progressive re -inspection fees
ct" J 2 >
Printed on 02/22/2024 @ 11:18