COMMERCIAL INSPECTION - 735 LOGAN AVE - 2-19-24
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price ]
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
14476
02/26/2024
03/28/2024
2024-00000294
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
LO6AN CONVENIENCE STORE, 735 LO6ANAVE, BLDG 735 LOGANAVE, WATERLOO IA 50703
DETAILS
I ulLP (4)
Inspection Date: 02/19/2024 J Inspection Type: Annual Inspection (1Yr) I Inspection Number: 9185 ; Shift: N/A
Station: Station 'I Fire Headquarters I Unit: N/A I Lead Inspector: JEFF SIEBEL ( Other Inspectors: N/A I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 1 Passed Codes: 24 I Violations: 5 I N/A Codes: 44
STATUS CODE DESCRIPTION
FAIL 305.1 - Clearance from Clearance between ignition sources, such as luminaires, heaters, flame -
ignition sources. producing devices and combustible materials, shall be maintained in an
approved manner.
Location: storage room on shelf
Original Comment: remove storage from 36" clearance around water heater.
FAIL 315.3.1 - Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in
nonsprinklered areas of buildings or not less than 18 inches (457 mm) below
sprinkler head deflectors in sprinklered areas of buildings. Exceptions: 1.The 2-
foot (610 mm) ceiling clearance is not required for storage along walls in
nonsprinklered areas of buildings. 2.The 18-inch (457 mm) ceiling clearance is not
required for storage along walls in areas of buildings equipped with an automatic
sprinkler system in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3.
Location: back storage room
Original Comment: lower storage away from ceiling
Printed on 02/19/2024 @ 15:11
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: back storage room
Original Comment: remove obstructions to electric panel. maintain a minimum of
36" clearance at all times.
FAIL 603.9.4 - Prohibited areas. Portable, electric space heaters shall not be operated within 3 feet (914 mm) of
any combustible materials. Portable, electric space heaters shall be operated
only in locations for which they are listed.
Location: behind counter
Original Comment: remove heater or provide documentation of listing for use in
a commercial property and proper clearances.
Printed on 02/19/2024 @ 15:11
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10.3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
REINSPECT/ON DATE
03/19/2024
CONTACT SIGNATURE
Muhammad Bhatti
Signed on: 02/19/2024 @ 15:10
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/19/2024 @ 15:10
Location: by front door
Original Comment: provide annual service for fire extinguisher.