COMMERCIAL INSPECTION - 230 E RIDGEWAY AVE - 2-19-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price j
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
5687
02/26/2024
03/28/2024
2024-00000297
$80.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
/IM LIND, 230 E RIDGEWAYAVE, BLDG 230 E RIDGEWAYAVE, WATERLOO IA 50702
DETAILS
Inspection Date: 02/19/2024 I Inspection Type: Annual Inspection (1Yr) ; Inspection Number: 10182 Shift: N/A I Station: N/A
Unit: N/A ; Lead Inspector: JEFF SIEBEL ( Other Inspectors: N/A I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 27 I Violations: 4 I N/A Codes: 48
STATUS CODE DESCRIPTION
FAIL 2311.2.2 - Waste oil, motor oil Waste oil, motor oil and other Class IIIB liquids shall be stored in approved tanks
and other Class IIIB liquids. or containers, which are allowed to be stored and dispensed from inside repair
garages.
Location: In garage
Original Comment: Install signage on waste oil tanks stating: Waste Oil Only
FAIL 5704.2.3.2 - Label or placard. Tanks more than 100 gallons (379 L) in capacity, which are permanently installed
or mounted and used for the storage of Class I, II or III liquids, shall bear a label
and placard identifying the material therein. Placards shall be in accordance with
NFPA 704. Exceptions: 1.Tanks of 300-gallon (1136 L) capacity or less located on
private property and used for heating and cooking fuels in single-family dwellings.
2.Tanks located underground.
Location: Door to detached storage building
Original Comment: Install NFPA 704 placard on outside of entry door for all bulk
storage tanks. Hazard numbers are assigned for the most hazardous material
and is found in SDS sheet.
Printed on 02/20/2024 @ 10:32
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: behind building by generator
Original Comment: remove obstructions. maintain a minimum of 36"clearance at
all times.
FAIL 603.4 - Working space and A working space of not Working space around electrical equipment shall be
clearancesclearance. provided in accordance with Section 110.26 of NFPA 70 for electrical equipment
rated 1,000 volts or less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space shall be not less
than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches
(1981 mm) in height shall be providedin front of electrical service equipment.
Where the electrical service equipment is wider than 30 inches (762 mm), the
minimum working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1. Where other dimensions are required or allowed by NFPA 70. 2.
Access openings into attics or under -floor areas that provide a minimum clear
opening of 22 inches (559 mm) by 30 inches (762 mm).
Location: in garage by used oil waste
Original Comment: remove obstructions (oil dispensers). maintain a minimum of
36" clearance at all times.
GENERAL NOTES
JEFF SIEBEL - 02/20/2024 @ 10:30 annual inspection $80
JEFF SIEBEL - 02/20/2024 @ 10:30 Dryer vent cleaned by Midtown chimney sweep 1/22/24
Printed on 02/20/2024 @ 10:32
Page 2 of 3
REINSPECTION DATE
03/18/2024
CONTACT SIGNATURE
Kerry Elliot
Signed on: 02/2(1/2024 @ 10:17
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/20/2024 @ 10:17
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 02/20/2024 @ 10:32
Page 3 of 3