COMMERCIAL INSPECTION - 3280 UNIVERSITY AVE - 2-5-24
L Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
24327
BILLING DATE
02/14/2024
DUE DATE
03/20/2024
INVOICE #
2024-00000285
CHARGES
Less Prepayment
Total Due —>
City of Waterloo
$80.00
$0.00
S80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
MIKES DINER, 3280 UNIVERSITYAVE, BLDG 3280 UNIVERSITYAVE, WATERLOO /A 50701
DETAILS
Inspection Date: 02/05/2024 I Inspection Type: Annual Inspection (1Yr) j Inspection Number: 11720 ! Shift: N/A I Station: N/A
Unit: N/A j Lead Inspector: JEFF SIEBEL j Other Inspectors: N/A I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 41 I Violations: 10 I N/A Codes: 23
STATUS CODE DESCRIPTION
FAIL 1004.9 - Posting of occupant Every room or space that is an assembly occupancy shall have the occupant load
load. of the room or space posted in a conspicuous place, near the main exit or exit
access doorway from the room or space, for the intended configurations. Posted
signs shall be of an approved legible permanent design and shall be maintained
by the owner or the owner's authorized agent.
Location: Not Provided
Original Comment: Install occupant load sign provided by fire inspector after all
furniture in place.
FAIL 102.4 - Application of building The design and construction of new structures shall comply with the
code. International Building Code , and any alterations, additions, changes in use or
changes in structures required by this code, which are within the scope of the
International Building Code , shall be made in accordance therewith.
Location: water heater
Original Comment: Obtain plumbing permit and inspections for water heater
installation.
Printed on 02/06/2024 @ 08:53
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 1203.2.6 - Exit signs. Emergency power shall be provided for exit signs as required in Section 1013.6.3.
The system shall be capable of powering the required load for a duration of not
less than 90 minutes.
Location: North exit door
Original Comment: repair exit/egress sign on back door.
FAIL 304.3.1 - Spontaneous Materials susceptible to spontaneous ignition, such as oily rags, shall be stored in
ignition. a listed disposal container. Contents of such containers shall be removed and
disposed of daily.
Location: Not Provided
Original Comment: provide listed approved oily waste receptacle for all oily waste
rags. See attached.
FAIL 506.2 - Key box maintenance. The operator of the building shall immediately notify the fire code official and
provide the new key where a lock is changed or rekeyed. The key to such lock
shall be secured in the key box.
Location: Not Provided
Original Comment: Update knox box keys with fire department.
FAIL 509.1 - Identification. Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems, sprinkler risers and valves, or
other fire detection, suppression or control elements fire protection systems
shall be identified for the use of the fire department. Approved signs required to
identify fire protection system equipment and equipment location shall be
constructed of durable materials, permanently installed and readily visible.
Location: outside access to fire sprinkler riser room
Original Comment: Install permanent red sign with white letters stating" Fire
Sprinkler Riser Room" on door to access door.
Printed on 02/06/2024 @ 08:53
Page 2of5
STATUS CODE DESCRIPTION
FAIL
603.2.2 - Unapproved
conditionsOpen electrical
terminations.
Open junction boxes and open -wiring splices shall be prohibited. Approved
covers shall be provided for all switch and electrical outlet boxes.
Location: entry way and ceiling
Original Comment: Provide covers for all outlet and switch boxes as well as install
covers on all junction boxes.
FAIL 603.5.3 - Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors,
under doors or floor coverings, or be subject to environmental or physical
damage.
Location: Dining area to new TVs
Original Comment: Install permanent outlets below the ceiling for TV's with
proper permits and inspections.
FAIL 603.9.4 - Prohibited areas. Portable, electric space heaters shall not be operated within 3 feet (914 mm) of
any combustible materials. Portable, electric space heaters shall be operated
only in locations for which they are listed.
Location: fire sprinkler room
Original Comment: remove portable electric heater from fire sprinkler room and
install permanent heat to maintain 45 deg in fire sprinkler riser room .
Printed an 02/06/2024 @ 08:53
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
GENERAL NOTES
JEFF SIEBEL - 02/06/2024 @ 08:50
JEFF SIEBEL - 02/06/2024 @ 08:51
JEFF SIEBEL - 02/06/2024 @ 08:51
REINSPECT/ON DATE
02/21/2024
CONTACT SIGNATURE
Mike Noel
Signed on: 02/06/2024 @ 08:51
Location: entire store and kitchen
Original Comment: re -install missing ceiling tile.
annual inspection $80
escutcheon replaced during inspection.
call for re -inspection if completed early.
Printed on 02/06/2024 @ 08:53
Page 4of5
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/06/2024 @ 08:52