COMMERCIAL INSPECTION - 2181 LOGAN AVE - 2-1-24
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 20,000
OCCUPANCY FEE
Total Price
$90.00
$10.00
CUSTOMER #
4431
BILLING DATE
02/14/2024
DUE, DATE
03/20/2024
INVOICE #
2024-00000281
CHARGES
Less Prepayment
Total Due —*
City of Waterloo
$100.00
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
HY VEE, 2181 LOGAN AVE, BLDG 2181 LOGAN AVE, WATERLOO IA S0703
DETAILS
Inspection Date: 02/01/2024 I Inspection Type: Annual Inspection (1Yr) ; Inspection Number: 10327 j Shift: N/A I Station: N/A
Unit: N/A ! Lead Inspector: JEFF SIEBEL ? Other Inspectors: N/A i Fee: $100.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 40 I Violations: 7 I N/A Codes: 26
STATUS CODE DESCRIPTION
FAI L 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
FAI L
Location: Entire store
Original Comment: Provide documentation of testing and repair of all emergency
egress and exit lights with signature and date.
5.2.1 - Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Location: Not Provided
Original Comment: Black Hawk Sprinkler report from 8/1/23 lists discrepancies.
Contractor must upload corrections online to the compliance engine.
Printed on 02/05/2024 @ 08:16
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 509.2 - Equipment access. Approved access shall be provided and maintained for all fire protection system
equipment to permit immediate safe operation and maintenance of such
equipment. Storage, trash and other materials or objects shall not be placed or
kept in such a manner that would prevent such equipment from being readily
accessible.
FAI L
603.6 - Extension cords.
Location: Back door from liquor store
Original Comment: remove all obstructions (carts) to fire alarm pull station.
Maintain a minimum of 36" clearance.
Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Location: behind customer service
Original Comment: remove extension cord to movable register. Install permanent
outlet if permanent or a power strip with a reset button may be utilized.
FAIL 606.3.3.3 - Records. Records for inspections shall state the individual and company performing the
inspection, a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the
cleaning and when the cleaning took place. Such records shall be completed after
each inspection or cleaning and maintained.
Location: kitchen hood exhaust cleaning inspection report.
Original Comment: provide current semi-annual kitchen hood exhaust system
cleaning report with all discrepancies corrected. Currently 206 days past due .
contractor must upload online to the compliance engine.
Printed on 02/05/2024 @ 08:16
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10. Exceptions: 1.The distance of travel to
reach an extinguisher shall not apply to the spectator seating portions of Group
A-5 occupancies. 2.Thirty-day inspections shall not be required and maintenance
shall be allowed to be once every 3 years for dry -chemical or halogenated agent
portable fire extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the following conditions are
met: 2.1.Electronic monitoring shall confirm that extinguishers are properly
positioned, properly charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a trouble signal.
2.3.The extinguishers shall be installed inside of a building or cabinet in a
noncorrosive environment. 2.4.Electronic monitoring devices and supervisory
circuits shall be tested every 3 years when extinguisher maintenance is
performed. 2.5.A written log of required hydrostatic test dates for extinguishers
shall be maintained by the owner to verify that hydrostatic tests are conducted at
the frequency required by NFPA 10. 3.In Group 1-3, portable fire extinguishers
shall be permitted to be located at staff locations.
Location: All fire extinguishers including in the pharmacy 2 years past due.
FAIL 906.6 - Unobstructed and Portable fire extinguishers shall not be obstructed or obscured from view. In
unobscured. rooms or areas in which visual obstruction cannot be completely avoided, means
shall be provided to indicate the locations of extinguishers.
Location: customer service
Original Comment: remove obstruction (shelves) or relocate fire extinguisher to
maintain a minimium of36" clearance at all times.
GENERAL NOTES
JEFF SIEBEL - 02/05/2024 @ 08:06 annual inspection $100
REINSPECTION DATE
02/26/2024
Printed on 02/05/2024 @ 08:16
Page 3 of 4
CONTACT SIGNATURE
Conor Erickson
Signed on: 02/05/2024 @ 08:12
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 02/05/2024 @ 08:12