COMMERCIAL INSPECTION - 2834 ANSBOROUGH AVE - 2-1-24
[ Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 20,000
OCCUPANCY FEE
Total Price ]
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
20752
02/14/2024
03/20/2024
2024-00000272
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
HY-VEE, 2834ANSBOR000HAVE, BLDG2S34ANSBOR000HAVE, WATERLOO /A S0701
DETAILS
Inspection Date: 02/01/2024 I Inspection Type: Annual Inspection (1Yr) 1 Inspection Number: 9804 I Shift: N/A I Station: N/A
Unit: N/A I Lead Inspector: JEFF SIEBEL I Other Inspectors: N/A 1 Fee: $100.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 43 I Violations: 10 I N/A Codes: 25
STATUS CODE
DESCRIPTION
Printed on 02/05/2024 @ 08:30
Page 1 of 7
FAIL 1010.2.13.1 - Delayed egress The delayed egress locking system shall be installed and operated in accordance
locking system. with all of the following: 1.The delay electronics of the delayed egress locking
system shall deactivate upon actuation of the automatic sprinkler system or
automatic fire detection system, allowing immediate, free egress. 2.The delay
electronics of the delayed egress locking system shall deactivate upon loss of
power controlling the lock or lock mechanism, allowing immediate free egress.
3.The delayed egress locking system shall have the capability of being deactivated
at the fire command center and other approved locations. 4.An attempt to
egress shall initiate an irreversible process that shall allow such egress in not
more than 15 seconds when a physical effort to exit is applied to the egress side
door hardware for not more than 3 seconds. Initiation of the irreversible process
shall activate an audible signal in the vicinity of the door. Once the delay
electronics have been deactivated, rearming the delay electronics shall be by
manual means only. Exception: Where approved, a delay of not more than 30
seconds is permitted on a delayed egress door. 5.The egress path from any point
shall not pass through more than one delayed egress locking system. Exceptions:
1.In Group 1-1, Condition 2, Group 1-2 or 1-3 occupancies, the egress path from any
point in the building shall pass through not more than two delayed egress
locking systems provided that the combined delay does not exceed 30 seconds.
2.In Group 1-1, Condition 1 or Group 1-4 occupancies, the egress path from any
point in the building shall pass through not more than two delayed egress
locking systems provided that the combined delay does not exceed 30 seconds
and the building is equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1. 6.A sign shall be provided on the door and
shall be located above and within 12 inches (305 mm) of the door exit hardware:
Exception: Where approved, in Group I occupancies, the installation of a sign is
not required where care recipients who, because of clinical needs, require
restraint or containment as part of the function of the treatment area. 6.1.For
doors that swing in the direction of egress, the sign shall read: "PUSH UNTIL
ALARM SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS." 6.2.For doors that
swing in the opposite direction of egress, the sign shall read: "PULL UNTIL ALARM
SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS." 6.3.The sign shall comply
with the visual character requirements in ICC A117.1.7.Emergency lighting shall
be provided on the egress side of the door. 8.The delayed egress locking system
units shall be listed in accordance with UL 294.
Location: walk thru dock door
Original Comment: Provide documentation of fire alarm release of door. Repair
Mag release , currently door does not release after 15 seconds.
Printed on 02/05/2024 @ 08:30
Page 2 of 7
STATUS CODE DESCRIPTION
FAIL 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
Location: Entire Store
Original Comment: provide documentation of emergency egress/exit lights with
all discrepancies corrected with signature and date.
FAIL 1203.4.3 - Records. Records of the inspection, testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,
a summary of conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken. Such records shall be
maintained.
Location: Generator engine service and load bank test
Original Comment: Provide current generator engine service and load bank test
inspection report.
FAIL 305.1 - Clearance from Clearance between ignition sources, such as luminaires, heaters, flame -
ignition sources. producing devices and combustible materials, shall be maintained in an
approved manner.
Location: under stairs from upper level to dock area
Original Comment: remove combustibles from charger under stairs.
Printed on 02/05/2024 @ 08:30
Page 3 of 7
STATUS CODE DESCRIPTION
FAIL 509.2 - Equipment access. Approved access shall be provided and maintained for all fire protection system
equipment to permit immediate safe operation and maintenance of such
equipment. Storage, trash and other materials or objects shall not be placed or
kept in such a manner that would prevent such equipment from being readily
accessible.
FAI L
FAI L
603.9.4 - Prohibited areas.
Location: Fire sprinkler riser by back door.
Original Comment: Remove obstructions. (snow blower) maintain a minimum of
36" clearance at all times
Portable, electric space heaters shall not be operated within 3 feet (914 mm) of
any combustible materials. Portable, electric space heaters shall be operated
only in locations for which they are listed.
Location: Upstairs office and department head office
Original Comment: remove portable electric heaters or provide documentation
of listing for commercial use and proper clearances..
606.3.3.2 - Grease If during the inspection it is found that hoods, grease -removal devices, fans,
accumulation. ducts or other appurtenances have an accumulation of grease, such
components shall be cleaned in accordance with ANSI/IKECA C10.
Location: Asian Kitchen
Original Comment: Clean oily filters above appliances. Excessive grease drips
fueling the fire.
Printed on 02/05/2024 @ 08:30
Page 4 of 7
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the fisting criteria and
manufacturer's installation instructions.
Location: dining room
Original Comment: Replace missing ceiling tile
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: upper club room
Original Comment: replace missing ceiling tile.
Printed on 02/05/2024 @ 08:30
Page 5 of 7
STATUS CODE DESCRIPTION
FAIL 704.1 - Maintaining Where required when the building was originally constructed, materials and
protection. systems used to protect joints and voids in the following locations shall be
maintained. The materials and systems shall be securely attached to or bonded
to the adjacent construction, without openings visible through the construction.
1.Joints in or between fire -resistance -rated walls, floors or floor/ceiling
assemblies and roof or roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids
at the intersection of a horizontal floor assembly and an exterior curtain wall.
4.Voids at the intersection of a horizontal smoke barrier and an exterior curtain
wall. 5.Voids at the intersection of a nonfire-resistance-rated floor assembly and
an exterior curtain wall. 6.Voids at the intersection of a vertical fire barrier and an
exterior curtain wall. 7.Voids at the intersection of a vertical fire barrier and a
nonfire-resistance-rated roof assembly. Unprotected joints and voids do not
need to be protected where such joints and voids were not required to be
protected when the building was originally constructed. Where the system design
number is known, the system shall be inspected to the listing criteria and
manufacturer's installation instructions.
GENERAL NOTES
JEFF SIEBEL - 02/02/2024 @ 19:15
JEFF SIEBEL - 02/02/2024 @ 19:15
REINSPECTION DATE
02/26/2024
CONTACT SIGNATURE
Ashley Jones
Signed on: 02/02/2024 @ 19:22
Location: IN Fruit room
Original Comment: replace missing ceiling tile
annual inspection $100
Fire extinguishers are due in March.