COMMERCIAL INSPECTION - 1975 FRANKLIN ST - 1-30-24
L Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
Total Price J
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
21926
02/14/2024
03/20/2024
2024-00000279
CHARGES
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
WATERLOO FIRE RESCUE
INSPECTION REPORT
RAPS SUPER MARKET,1975 FRANKLIN ST, BLDG 1975 FRANKLIN ST, WATERLOO IA 50703
Inspection Date: 01/30/2024 I Inspection Type: Annual Inspection (1Yr) I Inspection Number: 11648 I Shift: N/A I Station: N/A
Unit: N/A Lead Inspector: JEREMIAH VANDYKE I Other Inspectors: N/A I Fee: $80.00
VIOLATIONS AND COMPLIANCES
Showing only violations and images for this inspection. Please reach out to the lead inspector for more details.
Resolved Violations: 0 I Passed Codes: 39 I Violations: 8 I N/A Codes: 27
STATUS CODE DESCRIPTION
FAIL
FAIL
1203.2.15 - Means of egress Emergency power shall be provided for means of egress illumination in
illumination. accordance with Sections 1008.3 and 1104.5.1.
509.2 - Equipment access.
Inspector: JEREMIAH VANDYKE - Comments: Tested light and failed.
Location: By Budweiser sign on ceiling.
Approved access shall be provided and maintained for all fire protection system
equipment to permit immediate safe operation and maintenance of such
equipment. Storage, trash and other materials or objects shall not be placed or
kept in such a manner that would prevent such equipment from being readily
accessible.
Inspector: JEREMIAH VANDYKE - Comments: Cannot block fire extinguisher or pull
station. Remove rack in from area.
Location: Pull station for hood and Class k extinguisher near grill.
Printed on 01 /31 /2024 @ 09:21
Page 1 of 6
STATUS CODE DESCRIPTION
FAIL
FAI L
603.5 - Relocatable power
taps and current
taps.Multiplug adapters.
603.5.2 - Application and
usePower supply.
Multiplug adapters, such as cube adapters, unfused plug strips or any other
device not complying with NFPA 70 shall be prohibited. The construction and use
of current taps and relocatable taps shall be in accordance with NFPA 70 and this
code.
Inspector: JEREMIAH VANDYKE - Comments: Freezer plugged into powerstrip that
is plugged into orange extension cord. Freezer is to be plugged directly into wall
outlet.
Location: Behind grill serving area
Relocatable power taps and current taps shall be directly connected to a
permanently installed receptacle. Exceptions: 1. Where approved for use in a
Group A occupancy or in a meeting room in a Group B occupancy, not more than
five relocatable power taps shall be permitted to be connected together or
connected to an extension cord for temporary use to supply power to electronic
equipment. 2. Current taps and relocatable power taps shall not be required to
connect directly to a permanently installed receptacle outlet where used for 90
days or less for the purpose of testing the performance of such devices.
Inspector: JEREMIAH VANDYKE - Comments: Powerstrip to be secured and not
hanging.
Location: Behind front register area on south wall.
Printed on 01 /31 /2024 @ 09:21
Page 2of6
STATUS
FAIL
CODE
603.5.2 - Application and
usePower supply.
DESCRIPTION
Relocatable power taps and current taps shall be directly connected to a
permanently installed receptacle. Exceptions: 1. Where approved for use in a
Group A occupancy or in a meeting room in a Group B occupancy, not more than
five relocatable power taps shall be permitted to be connected together or
connected to an extension cord for temporary use to supply power to electronic
equipment. 2. Current taps and relocatable power taps shall not be required to
connect directly to a permanently installed receptacle outlet where used for 90
days or less for the purpose of testing the performance of such devices.
Inspector: JEREMIAH VANDYKE - Comments: Hanging powerstrip that must be
secured.
Location: Near grill serving area counter.
FAIL 603.6 - Extension cords. Extension cords and flexible cordsshall not be a substitute for permanent wiring
and shall be listed and labeled in accordance with UL 817. Extension cords and
flexible cordsshall not be affixed to structures, extended through walls, ceilings
or floors, or under doors or floor coverings, nor shall such cords be subject to
environmental damage or physical impact. Extension cords shall be used only
with portable appliances. Extension cords marked for indoor use shall not be
used outdoors.
Inspector: JEREMIAH VANDYKE - Comments: Refrigerator to be plugged directly
into wall outlet and not use orange extension cord as permanent wiring.
Location: Grill freezer.
Printed on 01 /31 /2024 @ 09:21
Page 3of6
. STATUS CODE DESCRIPTION
FAIL 603.9.4 - Prohibited areas. Portable, electric space heaters shall not be operated within 3 feet (914 mm) of
any combustible materials. Portable, electric space heaters shall be operated
only in locations for which they are listed.
FAIL
GENERAL NOTES
606.3.3.1 - Inspection.
Inspector: JEREMIAH VANDYKE - Comments: Space heater plugged into
powerstrip. Space heaters must be plugged directly into wall outlet. I unplugged
space heater.
Location: Space heater on grill counter.
Hoods, grease -removal devices, fans, ducts and other appurtenances shall be
inspected at intervals specified in Table 606.3.3.1 or as approved by the fire code
official. Inspections shall be completed by qualified individuals.
Inspector: JEREMIAH VANDYKE - Comments: Deficiencies Reviewed showing 2
deficiencies that need to be addressed by Contractor as soon as possible.
Deficiency Found: install grease catch on fan Deficiency Found: install hinge kit on
fan
Location: Hood system
JEREMIAH VANDYKE - 01/30/2024 @ 16:46 Fire Extinguisher serviced by Superior Fire in December 2023.
JEREMIAH VANDYKE - 01/31/2024 @ 08:46 12/11/2023 S - (Semi -Annual) Kitchen Exhaust AKA SERVICES INC. Reviewed with 2
Deficiencies.
JEREMIAH VANDYKE - 01/31/2024 @ 08:46 12/08/2023 S - Kitchen Hood Suppression SUPERIOR FIRE PROTECTION EQUIPMENT
Reviewed Compliant
Printed on 01/31/2024 @ 09:21
Page 4 of 6
„GENERAL NOTES
JEREMIAH VANDYKE - 01/31/2024 @ 08:46 Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in
the event of an emergency at that address. Phone # 319-291-2515.
JEREMIAH VANDYKE - 01/31/2024 @ 08:47
Re -inspection dates are automatically generated 30 days out from the initial
inspection. Normal operating hours for inspections & re -inspections are Monday -
Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on
a weekend, the re -inspection will typically be performed the following Monday or
Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier
re -inspection. *****Re inspection fees may be assessed for subsequent re -
inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent
re-inspections.-
JEREMIAH VANDYKE - 01/31/2024 @ 08:47 Lt. Van Dyke-jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-
1615
JEREMIAH VANDYKE - 01/31/2024 @ 08:57 Inspection Fee = $80.00
JEREMIAH VANDYKE - 01/31/2024 @ 08:57
REINSPECTION DATE
03/01/2024
CONTACT SIGNATURE
Owner must contact Contractor to have report uploaded to compliance engine
website to avoid future re inspect fees. 2024 Annual inspection is also due for annual
ALCOHOL license and will need to be scheduled. Provide corrections or close kitchen
and cap all gas lines and electrical. Provide corrections to avoid denial of beer and
Liquor licenses. The State is cracking down on extensions and it is getting to the point
we will have to move to deny if we cannot get compliance.
Yasmine Yasmeen Reason for not collecting a signature: NA
INSPECTOR SIGNATURE
JEREMIAH VANDYKE
Signed on: 01/31/2024 @ 08:45
Printed on 01 /31 /2024 @ 09:21
Page 5 of 6
.QUESTIONS ABOUT YOUR INSPECTION?
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
No phone number available
Printed on 01 /31 /2024 @ 09:21
Page 6 of 6